Plan Review Details - Permit 14090321
Plan Review Stops For Permit 14090321
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-09-10 Cont ID  
Sent By sciard Date 2014-09-10 Time 13:47 Rev Time 0.00
Received By sciard Date 2014-09-10 Time 13:48 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2014-09-10 Cont ID  
Sent By tklarge Date 2014-09-10 Time 14:12 Rev Time 0.00
Received By tklarge Date 2014-09-10 Time 14:12 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2014-09-10 Cont ID  
Sent By tklarge Date 2014-09-10 Time 12:21 Rev Time 0.00
Received By tklarge Date 2014-09-10 Time 12:21 Sent To  
Notes
2014-09-10 12:15:25WPB ADMIN. AMEND. TO 2010 FBC SEC.107.2.1.
 1) SUBMIT 2 COPIESOF THE MANUFACTURER'S SPECIFICATION
 SHEETS FOR THE TANKLESS WATER HEATER. THE WATER HEATER
 SHALL BE LISTED AND LABELED PER THE 2010 FL. GAS CODE
 SEC. 301.3.
 2) SUBMIT A GAS PIPING RISER FOR REVIEW. SHOW THE TYPE
 AND SIZE OF THE PIPING, THE BTU LOAD OF THE
 APPLIANCE,THE TOTAL DISTANCE FROM THE GAS POINT OF
 DELIVERY TO THE MOST REMOTE GAS OUTLET. THE PIPE SHALL
 BE SIZED IN ACCORDANCE WITH SECS.402.2 & 402.4, AND
 402.4.1. OF THE 2010 FL. GAS CODE.
 3) SUBMIT A COPY OF THE SIZING TABLE FROM THE FL. GAS
 CODE FOR THIS INSTALLATION.
 4) INDICATE THE SIZE OF THE WATER LINES TO THE HEATER
 ON THE PLAN.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-10 Cont ID  
Sent By sciard Date 2014-09-10 Time 13:53 Rev Time 0.00
Received By sciard Date 2014-09-10 Time   Sent To  
Notes
2014-09-10 11:19:17ROUTED TO TIM LARGE

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-09-10 Cont ID  
Sent By tklarge Date 2014-09-10 Time 14:12 Rev Time 0.00
Received By tklarge Date 2014-09-10 Time 14:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-09-10 Cont ID  
Sent By tklarge Date 2014-09-10 Time   Rev Time 0.00
Received By tklarge Date 2014-09-10 Time   Sent To  
Notes
2014-09-10 12:20:28WPB ADMIN. AMEND. TO 2010 FBC SEC.107.2.1.
 1) SUBMIT 2 COPIESOF THE MANUFACTURER'S SPECIFICATION
 SHEETS FOR THE TANKLESS WATER HEATER. THE WATER HEATER
 SHALL BE LISTED AND LABELED PER THE 2010 FL. GAS CODE
 SEC. 301.3.
 2) SUBMIT A GAS PIPING RISER FOR REVIEW. SHOW THE TYPE
 AND SIZE OF THE PIPING, THE BTU LOAD OF THE
 APPLIANCE,THE TOTAL DISTANCE FROM THE GAS POINT OF
 DELIVERY TO THE MOST REMOTE GAS OUTLET. THE PIPE SHALL
 BE SIZED IN ACCORDANCE WITH SECS.402.2 & 402.4, AND
 402.4.1. OF THE 2010 FL. GAS CODE.
 3) SUBMIT A COPY OF THE SIZING TABLE FROM THE FL. GAS
 CODE FOR THIS INSTALLATION.
 4) INDICATE THE SIZE OF THE WATER LINES TO THE HEATER
 ON THE PLAN.