| 2014-09-18 15:38:57 | FAILED |
| | |
| | 1) A PODOCARPUS HEDGE, FIVE (5) FOOT TALL AT INSTALL |
| | AND GROWN TO THE HEIGHT OF THE GENERATOR, IS REQUIRED |
| | TO SCREEN THE SOUTH AND WEST SIDES OF THE PROPOSED |
| | UNDERGROUND TANK PAD AND THE PROPOSED GENERATOR. THE |
| | OPENING IN THE HEDGE TO PERMIT ACCESS TO THE GENERATOR |
| | SHALL BE ON THE WEST SIDE. THE EXISTING ARECA PALMS |
| | SHALL SCREEN THE NORTH SIDE AND THE EXISTING SHED SHALL |
| | SCREEN THE EAST SIDE. AN OPAQUE FENCE IS NOT REQUIRED |
| | SO LONG AS THE PREVIOUSLY STATED SCREENING REQUIREMENTS |
| | REMAIN. |
| | |
| | 2) THE NEW LANDSCAPE TO SCREEN THE GENERATOR AREA AND |
| | THE PRE-MANUFACTURED METAL ELECTRICAL EQUIPMENT |
| | BUILDING SHALL BE INSTALLED AS PART OF THIS PERMIT AND |
| | PRIOR TO THE ISSUANCE OF A FINAL (104) INSPECTION |
| | APPROVAL. |
| | |
| | 3) SHEET C-101 SHOWS THE D CURB REQUIRED TO PROTECT THE |
| | LANDSCAPE FROM VEHICULAR ENCROACHMENT BEING INSTALLED |
| | ABUTTING THE UNDERGROUND FUEL TANK. THE LANDSCAPE |
| | SHEETS SHOW THE HEDGE LOCATED SOUTH OF THE D CURB |
| | LOCATION, THUS WITHIN THE EXISTING PARKING LOT. THE D |
| | CURB SHALL BE SHOWN PROTECTING THE LANDSCAPE. |
| | |
| | 4) STAFF DOES NOT OBJECT TO THE REORIENTATION OF THE |
| | GENERATOR PAD AND FUEL TANK AREA. |
| | |
| | 5) THE REVISED LAYOUT SHALL BE SUBMITTED AS PART OF THE |
| | CURRENT OPEN MINOR PLANNED DEVELOPMENT AMENDMENT TO THE |
| | PLANNING DIVISION. |
| | |
| | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
| | |
| | |
| | |