Plan Review Details - Permit 14090269
Plan Review Stops For Permit 14090269
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-09-26 Cont ID  
Sent By dhayes Date 2014-09-26 Time 13:32 Rev Time 0.00
Received By dhayes Date 2014-09-26 Time 12:10 Sent To  
Notes
2014-09-26 13:32:439/26/2014
 PROJECT: PETSMART
 PERMIT#: 14090269
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 PLAN REVIEW APPROVED BASED ON NFPA 70, ARTICLE 760, PER
 DOUG HARVEY, FINAL APPROVAL TO BE DETERMINED BY ON SITE
 FEILD INSPECTIONS AND WPBFD ACCEPTANCE OF SYSTEM
 FUNCTIONALITY.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-09-10 Cont ID  
Sent By dhayes Date 2014-09-10 Time 15:44 Rev Time 0.00
Received By dhayes Date 2014-09-10 Time 15:31 Sent To  
Notes
2014-09-10 16:26:39DATE: 9/10/2014
 PROJECT: PETSMART PBLM
 PERMIT#: 14090269
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 FIRE INSPECTOR COMMENTS.
 1) PER APPROVED MASTER PLANS: MAIN FACP FOR THIS
 BUILDING IS TO BE THE ONLY PANEL TO NOTIFY THE FIRE
 DEPARMENT. NOTIFICATION WILL DESIGNATE SPECIFIC ADDRESS
 OF TENANT WHERE TROUBLE IS LOCATED. EACH BUILDING SHALL
 ALARM/EVACUATE ONLY THE SPACES IN THAT BUILDING (IE AN
 ALARM IN "B" WILL NOT EVACUATE ANY SPACE IN "A", "BII",
 OR "C". EACH TENANT SPACE FACP SHALL BE CONNECTED TO
 MAIN FACP FOR THIS BUILDING VIA MODULES. TENANT SYSTEM
 SHALL BE COMPATIBLE WITH NOTIFIER OR EQUAL APPROVED
 MAIN FACP/HARDWARE EACH FLOW/TAMPER SHALL BE ZONED SO
 THAT AN ALARM WILL SOUND FOR EACH BUILDING SEPARATELY.
 THE PROJECT IS DESIGNED AS A STAND ALONE FIRE ALRM
 SYSTEM. PROVIDE MANUFACTURER COMPATABILITY
 DOCUMENTATION TO SUPPORT THE FIRE INSPECTORS COMMENTS.
  
 2) PROVIDE SUPPORTING DOCUMENTATION FOR THE
 CONTRACTOR'S $4,800.00 STATED VALUATION OF THE PROJECT.
 WPB AMENDMENTS TO THE FBC SECTION 109.3
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-09-22 Cont ID  
Sent By scaldero Date 2014-09-22 Time 11:44 Rev Time 0.00
Received By scaldero Date 2014-09-22 Time 11:44 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-09-09 Cont ID  
Sent By scaldero Date 2014-09-09 Time 18:57 Rev Time 0.00
Received By scaldero Date 2014-09-09 Time 18:57 Sent To E
Notes
2014-09-09 18:58:34PERMIT #14090269
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVISO:
 1) PER APPROVED MASTER PLANS: MAIN FACP FOR THIS
 BUILDING IS TO BE THE ONLY PANEL TO NOTIFY THE FIRE
 DEPARMENT. NOTIFICATION WILL DESIGNATE SPECIFIC ADDRESS
 OF TENANT WHERE TROUBLE IS LOCATED. EACH BUILDING SHALL
 ALARM/EVACUATE ONLY THE SPACES IN THAT BUILDING (IE AN
 ALARM IN "B" WILL NOT EVACUATE ANY SPACE IN "A", "BII",
 OR "C". EACH TENANT SPACE FACP SHALL BE CONNECTED TO
 MAIN FACP FOR THIS BUILDING VIA MODULES. TENANT SYSTEM
 SHALL BE COMPATIBLE WITH NOTIFIER OR EQUAL APPROVED
 MAIN FACP/HARDWARE EACH FLOW/TAMPER SHALL BE ZONED SO
 THAT AN ALARM WILL SOUND FOR EACH BUILDING SEPARATELY.
  
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-26 Cont ID  
Sent By dhayes Date 2014-09-26 Time 13:32 Rev Time 0.00
Received By dhayes Date 2014-09-20 Time 08:44 Sent To  
Notes
2014-09-20 08:44:54INCOMING SENT TO FIRE BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-10 Cont ID  
Sent By dhayes Date 2014-09-10 Time 15:45 Rev Time 0.00
Received By dhayes Date 2014-09-09 Time 12:17 Sent To  
Notes
2014-09-09 12:17:55ROUTED TO FIRE