| 2014-10-16 11:24:09 | 10/16/2014 |
| | PROJECT: COLEMAN RESIDENCE |
| | PERMIT#: 14090254 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) NEC 210.70 LIGHTING OUTLETS SHALL BE INSTALLED WHERE |
| | SPECIFIED IN 210.70(A), (B), AND (C). |
| | (B) FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED |
| | GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL |
| | SWITCH?CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED TO |
| | PROVIDE ILLUMINATION ON THE EXTERIOR SIDE OF OUTDOOR |
| | ENTRANCES OR EXITS WITH GRADE LEVEL ACCESS. INDICATE |
| | ALL REQUIRED SWITCHED LIGHTING OUTLETS AFFECTED BY THE |
| | INSTALLATION OR MODIFICATION OF EXTERIOR DOOR OPENINGS. |
| | |
| | 2) NEC 406.3 RECEPTACLE OUTLETS SHALL BE LOCATED IN |
| | BRANCH CIRCUITS IN ACCORDANCE WITH PART III OF ARTICLE |
| | 210. GENERAL INSTALLATION REQUIREMENTS SHALL BE IN |
| | ACCORDANCE WITH 406.3(A) THROUGH (F). |
| | (D) REPLACEMENT OF RECEPTACLES SHALL COMPLY WITH |
| | 406.3(D)(1),(2), AND (3) AS APPLICABLE. |
| | |
| | (D)(2) GFCI PROTECTED RECEPTACLES SHALL BE PROVIDED |
| | WHERE REPLACEMENTS ARE MADE AT RECEPTACLE OUTLETS THAT |
| | ARE REQUIRED TO BE SO PROTECTED ELSEWHERE IN THIS CODE. |
| | SEE NEC 210.8 |
| | |
| | NEC 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION |
| | FOR PERSONNEL. |
| | (A) DWELLING UNITS. ALL 125-VOLT, SINGLE-PHASE, 15- AND |
| | 20-AMPERE RECEPTACLES INSTALLED IN THE LOCATIONS |
| | SPECIFIED IN (1) THROUGH (8) SHALL HAVE GROUND-FAULT |
| | CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. |
| | (1) BATHROOMS. |
| | (2) GARAGES, AND ALSO ACCESSORY BUILDINGS THAT HAVE A |
| | FLOOR LOCATED AT OR BELOW GRADE LEVEL NOT INTENDED AS |
| | HABITABLE ROOMS AND LIMITED TO STORAGE AREAS, WORK |
| | AREAS, AND AREAS OF SIMILAR USE |
| | (3) OUTDOORS |
| | |
| | 4) REVISED PLANS TO INDICATE ALL SWITCHES, RECEPTACLE |
| | OUTLETS, AND LIGHTS AFFECTED BY THE INSTALLATION OR |
| | MODIFICATION OF THE EXTERIOR DOORS AND WHERE AFFECTED |
| | BY THE OVERALL SCOPE OF DEMOLITION AND RENNOVATION WORK |
| | OF AS REQUIRED. WPB AMENDMENTS TO FBC 107.3.2 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |
| | |