Plan Review Details - Permit 14090248
Plan Review Stops For Permit 14090248
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-10-07 Cont ID  
Sent By jwitmer Date 2014-10-07 Time 07:32 Rev Time 0.00
Received By jwitmer Date 2014-10-07 Time 06:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-09-18 Cont ID  
Sent By jwitmer Date 2014-09-18 Time 17:41 Rev Time 0.00
Received By jwitmer Date 2014-09-18 Time 17:00 Sent To  
Notes
2014-09-18 17:33:32BUILDING PLAN REVIEW
 PERMIT: 14090248
 ADD: 3401 PARKER AVE.
 CONT: TBD
 TEL: (561)803-2068
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. SEPT. 19/2014
 ACTION: DENIED
  
 1) ONLY ONE SET OF STATE APPROVED PLANS AND ENERGY
 CALCULATIONS WERE SUBMITTED, (2) SETS REQUIED.
 107.2.1.3
  
 2) PROVIDE DATES WHEN THIS BUILDING IS TO BE OCCUPIED
 DATE START AND DATE FINISHED WHEN BUILDING IS TO BE
 REMOVED, THE TERM TEMORARY IS 180 DAYS, OTHERWISE IT IS
 CONSIDERED A PERMANENT STRUCTURE. 108.1 GENERAL. THE
 BUILDING OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR
 TEMPORARY STRUCTURES AND TEMPORARY USES. SUCH PERMITS
 SHALL BE LIMITED AS TO TIME OF SERVICE, BUT SHALL NOT
 BE PERMITTED FOR MORE THAN 6MONTHS. THE BUILDING
 OFFICIAL IS AUTHORIZED TO GRANT EXTENSIONS FOR
 DEMONSTRATED CAUSE.
  
 2) MISSING SITE PLANS SHOWING THE LOCATION OF THE
 BUILDING. 107.2.5 THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES AND, AS APPLICABLE,
 FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN FLOOD
 ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN
 ACCURATE BOUNDARY LINE SURVEY. IN THE CASE OF
 DEMOLITION, THE SITE PLAN SHALL SHOW CONSTRUCTION TO BE
 DEMOLISHED AND THE LOCATION AND SIZE OF EXISTING
 STRUCTURES AND CONSTRUCTION THAT ARE TO REMAIN ON THE
 SITE OR PLOT. THE BUILDING OFFICIAL IS AUTHORIZED TO
 WAIVE OR MODIFY THE REQUIREMENT FOR A SITE PLAN WHEN
 THE
 APPLICATION FOR PERMIT IS FOR ALTERATION OR REPAIR OR
 WHEN OTHERWISE WARRANTED.
 107.2.5.1 DESIGN FLOOD ELEVATIONS. WHERE DESIGN FLOOD
 ELEVATIONS ARE NOT SPECIFIED, THEY SHALL BE ESTABLISHED
 IN ACCORDANCE WITH SECTION 1612.3.1.
  
 3) PLEASE REVIEW STATE APPROVED PLANS AND SITE
 INSTALLED ITEMS NOT INCLUDED IN THE PLANS.
 3.1 RAMPS, STAIRS & LANDINGS, WILL NEED TO SHOW
 ENGINEERING.
 3.2 DRINKING FOUNTAINS, BUILDING DRAIN AND SERVICE SINK
 AND HOOK UP TO PLUMBING
 3.3 GLAZED OPENING PROTECTION, (SHUTTERS) PRODUCT
 APPROVALS
 3.4 GUTTER AND DOWN SPOUTS
  
 4) IF THIS IS TO BE A PERMANENT STRUCTURE, BEFORE A
 PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE
 PAID TO PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF
 PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE
 PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE
 CALL (561)233-5025 FOR MORE INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-10-07 Cont ID  
Sent By dhayes Date 2014-10-07 Time 07:51 Rev Time 0.00
Received By dhayes Date 2014-10-07 Time 07:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-09-22 Cont ID  
Sent By dhayes Date 2014-09-22 Time 07:40 Rev Time 0.00
Received By dhayes Date 2014-09-22 Time 07:40 Sent To  
Notes
2014-09-22 07:44:51DATE: 9/22/2014
 PROJECT: RINKER ATHLETIC
 PERMIT#: 14090248
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) TWO SIGNED SEALED SETS REQUIRED.
  
 2) PROVIDE A SITE PLAN, ELECTRICAL SERVICE RISER, AND
 LOAD CALCULATION. INCLUDE THE SIZE, TYPE, GROUNDING
 DETAILS, WHERE IT IS BEING FED FROM AND THE LOCATION OF
 THE UTILITY SOURCE AND THE LOCATION OF THE SERVICE
 DISCONNETING MEANS RELATIVE TO THE MODULAR SITE. WPB
 AMENDMENTS TO FBC 107.3.2
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2014-10-08 Cont ID  
Sent By Mgonzale Date 2014-10-08 Time 09:58 Rev Time 1.00
Received By mgonzale Date   Time   Sent To FIRE
Notes
2014-10-08 09:58:31PASSED WITH PROVISOS AND CONDITION OF C.O.:
  
 #1 PROVIDE A 10' WIDE UTILITIY EASEMENT FOR WATER
 SERVICE. A "LEGAL DESCRIPTION AND SKETCH" TO BE
 SUBMITTED TO THE CITY OF WEST PALM BEACHENGINEERING
 DEPPARTMENT FOR WATER SERVICE.
 WITH THAT SAME SUBMITTAL PROVIDE AS-BUILTS FOR THE
 WATER AND SEWER SERVICES TO THIS NEW FACILITY. EASEMENT
 SHALL INCLUDE WATER METER AND EXCLUDE THE PRIVATE
 BACKFLOW PREVENTER.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES AND PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2014-10-01 Cont ID  
Sent By cranford Date 2014-10-01 Time 09:21 Rev Time 0.00
Received By cranford Date 2014-09-30 Time 15:09 Sent To Z
Notes
2014-09-30 15:17:41ENGINEERING DEPT COMMENTS
  
 1. SUBMIT A LOCATION MAP SHOWING WHERE ON THE RINKER
 ATHLETIC CAMPUS THE BUILDING IS PROPOSED TO BE LOCATED.
  
 2. INDICATE HOW/WHERE THE POTABLE WATER AND SANITARY
 SERVICE LINES ARE PROPOSED TO BE CONNECTED TO THE
 TRAILER.
  
 3. PROVIDE A HYDRAULIC ANALYSIS AND DEMAND ESTIMATE FOR
 THE TRAILER.
  
 4. HOW WILL THE SOLID WASTE (GARBAGE) BE COLLECTED FROM
 THE TRAILER? IF A NEW DUMPSTER LOCATION IS PROPOSED, IT
 WILL NEED TO COMPLY WITH SECTIONS 74-35(A)(5) AND
 94-444 OF THE CODE OF ORDINANCES.
  
 DEPENDING ON HOW LONG THE TRAILER IS INTENDED TO REMAIN
 IN PLACE (SEE BUILDING DEPARTMENT COMMENTS) AND
 WHERE/HOW THE UTILITY CONNECTIONS ARE PROPOSED, AN
 ENGINEERING DEVELOPMENT APPLICATION MAY ALSO BE
 REQUIRED.
  
 KELLY CRANFORD, P.E.
 LAND DEVELOPMENT ENGINEER
 ENGINEERING & PUBLIC WORKS DEPARTMENT
 CITY OF WEST PALM BEACH
 [email protected]
 561-494-1098 (OFFICE)
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-10-09 Cont ID  
Sent By pleduc Date 2014-10-09 Time   Rev Time 0.00
Received By pleduc Date 2014-10-09 Time 16:49 Sent To PC
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-09-11 Cont ID  
Sent By pleduc Date 2014-09-11 Time   Rev Time 0.00
Received By pleduc Date 2014-09-10 Time 16:34 Sent To  
Notes
2014-09-11 11:57:02THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 A SITE PLAN WAS NOT SUBMITTED WITH THE APPLICATION.
  
 A SITE PALN SHALL BE SUBMITTED WITH PROPERTY BOUNDRIES,
 LOCATION OF PROPOSED TRAILER WITH DIMENSIONS OF NEAREST
 STRUCTURES.
  
 A LIFE SAFETY PLAN WAS NOT SUBMITTED.
  
 A LIFE SAFETY PALN IS REQUIRED THAT SHOWS OCCUPANCY
 LOADS, ALL EXIT PATHS, EXITS, EMERGENCY LIGHTING, AND
 EXIT DISCHARGES THAT LEAD TO A PUBLIC WAY.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-10-09 Cont ID  
Sent By pleduc Date 2014-10-09 Time 16:50 Rev Time 0.00
Received By pleduc Date 2014-10-02 Time 17:33 Sent To  
Notes
2014-10-02 17:42:09B06, COULD NOT FIND ORIGINAL SUBMITTAL.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-01 Cont ID  
Sent By jroach Date 2014-10-01 Time 11:35 Rev Time 0.00
Received By jroach Date 2014-09-08 Time 11:38 Sent To  
Notes
2014-09-09 11:24:33SENT TO B3 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2014-10-07 Cont ID  
Sent By jwitmer Date 2014-10-07 Time 07:11 Rev Time 0.00
Received By jwitmer Date 2014-10-07 Time 07:11 Sent To  
Notes
2014-10-07 07:11:17P.B.C. IMPACT FEE STAMP ON PLANS NO FEES DUE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-09-18 Cont ID  
Sent By jwitmer Date 2014-09-18 Time 17:41 Rev Time 0.00
Received By jwitmer Date 2014-09-18 Time 17:41 Sent To  
Notes
2014-09-18 17:33:48BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-10-07 Cont ID  
Sent By tklarge Date 2014-10-07 Time 08:23 Rev Time 0.00
Received By tklarge Date 2014-10-07 Time 08:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-09-24 Cont ID  
Sent By tklarge Date 2014-09-24 Time 05:37 Rev Time 0.00
Received By tklarge Date 2014-09-24 Time 04:12 Sent To  
Notes
2014-09-24 05:17:081) SUBMIT A SITE PLAN THAT SHOWS THE WATER AND SEWER
 CONNECTIONS AND THE SIZE OF THE WATER SERVICE AND SEWER
 CONNECTION.. THE POTABLE WATER SERVICE SHALL BE
 PROTECTED AGAINST BACKFLOW PER THE 2010 FL. PLUMBING
 CODE SEC.608.
 2) INDICATE ON THE PLANS WHAT THE BUOLDING WILL BE USED
 FOR. THE PLANS NOTE "BUSINESS OCCUPANCY". PLEASE BE
 MORE SPECIFIC. WPB AMENDMENTS TO 2010 FBC SEC. 107.2.1.
 3) A DRINKING FOUNTAIN ( HI-LO) IS REQUIRED IN THE
 BUILDING PER TABLE 403.1 OF 2010 FPC.
 4) SUBMIT 2 COPIES OF THE PLANS FOR REVIEW. WPB AMEND.
 TO 2010 FBC SEC.107.1.
 5) PLANS SHOW 2" FIXTURE DRAIN FOR THE WATER
 CLOSETS.THE MIN. SIZE FIXTURE DRAIN FOR A WATER CLOSET
 IS 3" PER TABLE 709.1.
 6) SHT. 3 OF 5 SHOWS 1/2" VENTS THROUGH THE ROUGH.
 CLARIFY. THE MIN. SIZE VTR IS 1 1/4".
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2014-10-09 Cont ID  
Sent By jroach Date 2014-10-09 Time 11:47 Rev Time 0.00
Received By jroach Date 2014-10-09 Time 11:47 Sent To  
Notes
2014-10-09 11:47:32ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 10.09.2014
 PERMIT NO.: 14090248
 ADDRESS: 3401 PARKER AVENUE
 CONTRACTOR/CONTACT: MATT STEVENS
 TELEPHONE NO.: 561.803.2201
 SCOPE OF REVIEW: INSTALLATION OF TEMPORARY LOCKER
 ROOMS.
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. PRIOR TO PASSING FINAL INSPECTION, A SEPARATE
 LANDSCAPE PERMIT APPLICATION SHALL BE SUBMITTED. THE
 LANDSCAPE PERMIT APPLICATION SHALL INCLUDE TWO (2) SETS
 OF SIGNED/SEALED LANDSCAPE PLANS AND A CERTIFIED COST
 ESTIMATE (MATERIALS + LABOR). ALL LANDSCAPE MATERIAL
 SHALL ALSO BE INSTALLED AND PASS FINAL INSPECTION
 BEFORE ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY/COMPLETION.
  
 2. THE TEMPORARY MODULAR STRUCTURE CONTAINING THE
 LOCKER AND RESTROOM FACILITIES SHALL BE REMOVED PRIOR
 TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY (CO) FOR
 THE PERMANENT RECREATION BUILDING. EVERY EFFORT SHOULD
 BE MADE TO RELOCATE THE TREES/PALMS LOCATED AROUND THE
 TEMPORARY STRUCTURE.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1448
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2014-10-01 Cont ID  
Sent By JROACH Date 2014-10-01 Time 11:32 Rev Time 0.00
Received By jroach Date 2014-10-01 Time 11:32 Sent To  
Notes
2014-10-01 11:35:31ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 10.01.2014
 PERMIT NO.: 14090248
 ADDRESS: 3401 PARKER AVENUE
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: TEMPORARY LOCKER ROOMS.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. TWO (2) COPIES OF A CURRENT AND ACCURATE SURVEY
 SHALL BE PROVIDED FOR THE LOCATION OF THE PROPOSED
 LOCKER ROOMS.
  
 2. TWO (2) COPIES OF A SITE PLAN SHALL BE PROVIDED
 SHOWING THE LOCATION OF THE PROPOSED LOCKER ROOMS.
  
 3. LANDSCAPING SHALL BE SUBMITTED UNDER A SEPARATE
 LANDSCAPE PERMIT APPLICATION. THE APPLICATION SHALL BE
 ACCOMPANIED BY TWO (2) SETS OF SIGNED/SEALED LANDSCAPE
 PLANS, AS WELL AS A CERTIFIED COST ESTIMATE FOR
 MATERIAL + LABOR. ALL LANDSCAPING WILL NEED TO BE
 INSTALLED PRIOR TO THE ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY (CO) FOR THE STRUCTURE.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1448
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.WPB.ORG
  
2014-09-19 15:50:309/19/14


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved