| Plan Review Stops For Permit 14090230 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2014-09-09 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2014-09-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2014-09-09 |
Time |
15:56 |
Sent To |
M |
|
| Notes |
| 2014-09-09 16:16:56 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | SHEET F 2 SHOWS A DOOR TO ENTER THE TANK CONTAINMENT | | | SPACE. THERE IS NO INDICATION OR DIMENSIONS OF A CURB | | | UNDER THE DOOR. PLEASE PROVIDE FOR A CURB UNDER THE | | | DOOR FOR CONTAIMENT PURPOSES. | | | | | | SHEET F 3 DOES NOT INDICATE THE INSTALLATION OF | | | LOCATION OF "NO SMOKING" SIGNS OR FUEL PLACARDS. PLEASE | | | PROVIDE FOR THE REQUIRED SIGNAGE AND PLACARDING. | | | | | | THE FIRE INSPECTOR WILL VERIFY EACH DURING INSPECTION. |
|
|