Plan Review Details - Permit 14090135
Plan Review Stops For Permit 14090135
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-09-17 Cont ID  
Sent By jwitmer Date 2014-09-17 Time 12:05 Rev Time 0.00
Received By jwitmer Date 2014-09-17 Time 10:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-10-02 Cont ID  
Sent By rlecky Date 2014-10-02 Time 11:06 Rev Time 0.00
Received By rlecky Date 2014-10-02 Time 10:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-09-16 Cont ID  
Sent By rlecky Date 2014-09-16 Time 14:49 Rev Time 0.00
Received By rlecky Date 2014-09-16 Time 13:43 Sent To  
Notes
2014-09-16 14:56:5914090135
 6901 OKEECHOBEE BLVD #81
 RESTAURANT REMODEL
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 THE TOTAL SCOPE OF THE ELECTRICAL WORK IS NOT CLEAR.
 ARE THE PANELS NEW OR EXISTING? SHOW ALL NEW CIRCUITS
 AND OUTLETS. PROVIDE AN ELECTRICAL RISER SHOWING
 EXISTING AND NEW WORK ANDLOCATION OF MAIN SERVICE
 DISCONNECTS. NEC 215.5
  
 VERIFY A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE ELECTRIC SERVICE, PANEL BOARDS AND MAIN
 DISCONNECTING MEANS HAS BEEN PROVIDED. NEC 110.16,
 110.22
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE ELECTRIC PLAN
 WHICH SHOWS COMPLIANCE WITH THE FLORIDA BUILDING ENERGY
 CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.5;
 505.5.3; T. 505.5.3
  
 PROVIDE A SIGN CIRCUIT AND DISCONNECT. NEC 600.5
  
 CONFIRM THAT THE INTERIOR AND EXTERIOR LIGHTING
 CONTROLS PROVIDED FUNCTION IN ACCORDANCE WITH THE
 FLORIDA ENERGY CODE. EXTERIOR AUTOMATIC CONTROLS SHALL
 BE CAPABLE OF RETAINING PROGRAMMING AND THE TIME
 SETTING DURING LOSS OF POWER FOR A PERIOD OF AT LEAST
 10 HOURS. VERIFY THE LIGHTING AND SIGN TIME CLOCKS HAVE
 BATTERY BACKUP. FBC ENERGY CONSERVATION 505.2
  
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
 561-373-3701
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-09-10 Cont ID  
Sent By pleduc Date 2014-09-10 Time   Rev Time 0.00
Received By pleduc Date 2014-09-09 Time 15:20 Sent To  
Notes
2014-09-10 10:55:53THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 ADD EXITS SIGNS IN THE PATH OF EGRESS AS SHOWN ON THE
 LIFE SAFETY AND ELECTRICAL DRAWINGS WHERE INDICATED.
  
 THE HOOD SYSTEM AND FIRE SUPPRESSION SYSTEM SHALL BE
 DONE UNDER SEPARATE SHOP DRAWINGS.
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2014-10-28 Cont ID  
Sent By tklarge Date 2014-10-21 Time 10:05 Rev Time 0.00
Received By tklarge Date 2014-10-20 Time 10:04 Sent To  
Notes
2014-10-28 10:06:04SEPARATE PERMIT REQD. FOR GAS.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-10-21 Cont ID  
Sent By tklarge Date 2014-10-21 Time 06:38 Rev Time 0.00
Received By tklarge Date 2014-10-16 Time 10:52 Sent To P
Notes
2014-10-17 10:52:57TO T.L'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-10-03 Cont ID  
Sent By hmoser Date 2014-10-03 Time 14:42 Rev Time 0.00
Received By hmoser Date 2014-09-30 Time 15:25 Sent To  
Notes
2014-10-01 15:16:45C04

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-22 Cont ID  
Sent By skennedy Date 2014-09-22 Time 10:51 Rev Time 0.00
Received By skennedy Date 2014-09-04 Time 11:38 Sent To  
Notes
2014-09-05 11:40:23C11

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2014-09-17 Cont ID  
Sent By jwitmer Date 2014-09-17 Time 11:19 Rev Time 0.00
Received By jwitmer Date 2014-09-17 Time 11:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-10-03 Cont ID  
Sent By hmoser Date 2014-10-03 Time 14:41 Rev Time 0.00
Received By hmoser Date 2014-10-03 Time 14:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-09-22 Cont ID  
Sent By rbergsma Date 2014-09-22 Time   Rev Time 1.50
Received By rbergsma Date   Time   Sent To  
Notes
2014-09-22 10:15:43M-1, (1) THERE ARE 3 BATH FANS INDICATED ON THE AIR
 BALANCE CHART, PROVIDE LOCATION OF 3RD BATH.
 (2) THERE ARE A TOTAL OF 5 MUA FANS ON THE DRAWING,
 THERE ARE 6 ON THE AIR BALANCE CHART ?
 (3) AGAIN THE AIR BALANCE CHART INDICATES 10 TEPPAN
 YAKI EXHAUST FANS, ONLY 8 ARE SHOWN?
 (4) MUA DUCT AND FANS ARE SHOWN BETWEEN THE TEPPAN YAKI
 HOODS BUT ARE REMOTE TO THE EXHAUST ON THE ROOF,
 INDICATE DUCT AND SIZES
 AND ROUTING ON PLANS.
 (5) WILL THE MUA UNIT(S) PROVIDE 100% OF THEIR CAPACITY
 IF ONLY ONE TEPPAN YAKI GRILL IS IN OPERATION OR IS IT
 A TWO SPEED STAGGED OPERATION
 (6) PROVDE PARAPET WALL HEIGHT BEHIND MAIN HOOD OR
 STRUCTURAL RAILING DETAIL
 M-2 (1) PROVIDE DETAIL OF GREASE DUCT PENETRATION THRU
 CEILIN, WOOD TRUSSES AND ROOF ASSEMBLY (NFPA 96)
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2014-10-20 Cont ID  
Sent By tklarge Date 2014-10-21 Time 06:38 Rev Time 0.00
Received By tklarge Date 2014-10-20 Time 15:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2014-10-02 Cont ID  
Sent By tklarge Date 2014-10-02 Time 07:49 Rev Time 0.00
Received By tklarge Date 2014-10-02 Time 06:39 Sent To  
Notes
2014-10-02 07:49:021) 2ND REQUEST - SUBMIT MANUF. SPECIFICATION SHEETS FOR
 THE HIBACHI TABLE. THE TABLES SHALL BE LISTED AND
 LABELED PER THE 2010 FLORIDA FUEL GAS CODE SEC. 301.3.
 THE SHEETS THAT WERE SUBMITTED DO NOT SHOW THAT THE
 TABLES ARE LISTED AND LABELED.
 2) YOU HAVE ADDED A TABLE ABOVE THE GAS RISER THAT
 READS "IRON PIPE SIZE". WHAT IS THE REASON FOR THIS
 TABLE?
 3) SUBMIT TWO COPIES OF THE APPLICABLE GAS SIZING
 TABLES THAT ARE BEING USED FOR THIS PROJECT.
 4) SHT. P-1 - I HAVE REFERENCED THE 2010 EDITION
 FLORIDA FUEL GAS CODE IN MY REVIEW COMMENTS AND YOU
 HAVE REFERENCED THE 2006 IFGC. REVISE THE NOTE TO
 COMPLY W/ THE 2010 FLORIDA FUEL GAS CODE.
 5) YOUR RESPONSE TO MY FIRST REVIEW COMMENT #5 REFERS
 TO FLEXIBLE GAS PIPING WITH A POLYETHYLENE SLEEVE. THIS
 DOES NOT SATISY THE REQUIREMENT FOR CONDUIT. COMPLY
 WITH THE 2010 FLORIDA FUEL GAS CODE 404.12.2. TRACPIPE
 ALSO REQUIRES THE CONDUIT. YOUR RESPONSE REFERS TO
 'SUBMITTED ATTACHMENT." THERE WAS NO ATTACHMENT FOR
 TRACPIPE.
 6) SHOW THE LENGTH OF EACH SECTION OF TRACK PIPEON THE
 PLAN AND THE RISER.
 7) SUBMIT THE CORRESPONDING EHD NUMBER FOR THE TRAC
 PIPE FROM THE APPLICABLE SIZING TABLE BEING USED.
 8) PLEASE SHOW THE SIZE OF THE EXISTING GREASE TRAP.
 9) CLARIFY THE SIZE OF THE WATER HEATER. THE PLAN SHOWS
 "7 I". CLARIFY.
 10) INDICATE ON THE PLAN WHAT WILL BE THE USE OF THE
 TWO ADDED SINKS?

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-09-19 Cont ID  
Sent By tklarge Date 2014-09-19 Time 14:02 Rev Time 0.00
Received By tklarge Date 2014-09-19 Time 14:02 Sent To  
Notes
2014-09-19 14:27:38WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 1) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR THE
 HIBACHI TABLES. THE TABLES SHALL BE LISTED AND LABELED
 PER THE 2010 FLORIDA GAS CODE 301.3.
 2) THE ADDED GAS LOAD FOR THE HIBACHI TABLES HAS NOW
 MADE THE ENTIRE GAS SYSTEM UNDERSIZED. THE GAS SYSTEM
 SIZING SHALL COMPLY WITH TABLE 402.4 (2) AS SPECIFIED
 ON THE PLANS FOR A TOTAL RUN OF 128 FT. IF YOU INCREASE
 THE GAS PRESSURE TO A 2 PSI SYSTEM AND SIZE THE SYSTEM
 TO TABLE 402.4 (30 YOU WILL BE IN COMPLIANCE.
 3)SHT. P-2 - THE 3" WASTE LINE WITH THE AIR ADMITTANCE
 VALVES FROM THE HAND SINKS TO THE EXISTING GREASE TRAP
 REQUIRES A VENT TO THE OPEN AIR PER THE 2010 FBCP
 SEC.917.7. THE VENT COULD BE INSTALLED AGAINST THE
 EXTERIOR WALL ON THE OUTSIDE OF THE BUILDING TO COMPLY
 WITH THIS CODE SECTION.
 4) IDENTIFY THE SQUARE ON THE GAS PIPING DIAGRAM WITH
 THE LETTERS "GS" IN IT.
 5) GAS PIPING UNDER THE SLAB TO THE HIBACHI TABLES
 SHALL BE ENCASED IN CONDUIT PER THE 2010 FBCG
 SEC.404.12.2. SUBMIT A DETAIL FOR THIS INSTALLATION
 SHOWING THE SIZE OF THE CONDUIT. THE CONDUIT SHALL
 TERMINATE IN AN ACCESSIBLE PORTION OF THE BUILDING.
 6) SUBMIT A SANITARY AND WATER RISER FOR THE PLUMBING
 WORK TO BE DONE.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2014-09-11 Cont ID  
Sent By ajones Date 2014-09-11 Time 14:59 Rev Time 0.00
Received By ajones Date 2014-09-11 Time 14:59 Sent To  
Notes
***NONE***