| 2014-09-15 14:29:07 | DATE: 9/15/2014 |
| | PROJECT: RIVERWALK LAP POOL HEATERS. |
| | PERMIT#: 14090123 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE A SITE PLAN TO INDICATE THE LOCATION OF THE |
| | FPL TRANSFORMER AND THE ELECTRICAL SERVICE EQUIPMENT. |
| | WPB AMENDMENTS TO FBC 107.2.1 |
| | |
| | 2) A GROUNDING ELECTRODE SYSTEM IS REQUIRED. PROVIDE A |
| | GROUNDING ELECTRODE SYSTEM DETAIL AS OUTLINED IN THE |
| | NEC 250.50 |
| | |
| | 3) PROVIDE A LOAD CALCULATION AND A PANEL SCHEDULE FOR |
| | THE 100AMP PANEL INCLUDE ALL BREAKER TYPES AND SIZES. |
| | |
| | 4) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS |
| | TO FBC 107.2.1 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |