Plan Review Details - Permit 14090024
Plan Review Stops For Permit 14090024
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-09-28 Cont ID  
Sent By skennedy Date 2014-09-28 Time 12:11 Rev Time 0.00
Received By skennedy Date 2014-09-28 Time 12:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-09-10 Cont ID  
Sent By skennedy Date 2014-09-10 Time 15:55 Rev Time 0.00
Received By skennedy Date 2014-09-09 Time 08:29 Sent To  
Notes
2014-09-10 16:26:301ST REVIEW: FBC 2010
  
 FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE
 BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM
 CRITERIA AND DOCUMENTS: A FLOOR PLAN; SITE
 PLAN; FOUNDATION PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS
 LAYOUT; ALL FENESTRATION PENETRATIONS;
 FLASHING; AND ROUGH OPENING DIMENSIONS; AND ALL
 EXTERIOR ELEVATIONS:
  
 PROVIDE STRUCTURAL DETAILS AND CLARIFY CONFLICTS IN THE
 PLAN AS FOLLOWS:
  
 DETAIL THE RETROFIT OPENINGS FOR WINDOWS IDENTIFIED TO
 BE RELOCATED ON SHEET A-3 & A-4.
 PROVIDE DOCUMENTTATION FOR "WINDOWS TO BE RELOCATED" TO
 DEMONSTRATE SUCH WINDOWS COMPLY WITH THE FLORIDA
 BUILDING CODE.
 DETAIL THE CLOSING OF OPENING OF FORMER WINDOWS.
 DETAIL THE NEW OPENINGS FOR NEW WINDOWS AND DOORS ON
 SHEET A-3 &A-4.
 CLARIFY THE ROOF SHEATHING TYPE. THE PLAN CONLICTS
 INDICATING 1/2" AND 5/8."
 CLARIFY ALL SHEATHING NAILING SPECIFICATIONS. ARE RING
 SHANK NAILS INTENDED? NOTES REFER TO A DETAIL WHICH
 APPARENTLY IS NOT UPON THE PLAN.
 CLARIFY THE PORCH CORNER POST. IS IT A 3" PIPE, OR A
 6X6 WOOD POST?
  
 THANK YOU,
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-09-27 Cont ID  
Sent By dhayes Date 2014-09-27 Time 14:40 Rev Time 0.00
Received By dhayes Date 2014-09-27 Time 14:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-09-02 Cont ID  
Sent By dhayes Date 2014-09-02 Time 16:34 Rev Time 0.00
Received By dhayes Date 2014-09-02 Time 16:34 Sent To  
Notes
2014-09-02 16:45:22DATE: 9/2/2014
 PROJECT: 918 30TH ST
 PERMIT#: 14090024
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) IT APPEARS BY WHAT IS INDICATED ON THE PLANS THE
 ELECTRICAL PANEL IS LOCATED IN THE KITCHEN UTILITY
 CLOSET BEHIND WASHER/DRYRER. THE ELECTRICAL PANEL
 REQUIRES CLEAR UNOBSTRUCTED WORKING ACCESS. NEC 110.26.
 REVVISE PLANS FOR CODE COMPLIANCE.
  
 2) ONE GFI RECEPTACLE IS REQUIRED WITHIN SIGHT OF
 MECHANICAL EQUIPMENT. REVISE PLANS TO INDICATE REQUIRED
 OUTLETS BY MECHANICAL EQUIPMENT. NEC 210.63 SEE
 210.8(A)(3),
  
 3) SMOKE/CO DETECTORS ARE REQUIRED PER THE FBC-R 314,
 315. IDENTIFY THE REQUIRED SMOKE DETECTORS.
 FBC-RESIDENTIAL 314.3 AND 314.3.1
  
 4) PROVIDE A RISER DIAGRAM, PANEL SCHEDULE, LOAD
 CALCULATION AND SITE PLAN TO INDICATE THE LOCATION OF
 THE ELECTRICAL SERVICE AND MAIN DISCONNECT FBC 107.2.1,
 NEC 230.70
  
 5) TWO SETS OF PLANS AND SPECIFICATIONS ARE REQUIRED
 FOR REVIEW. WPB FBC 107.3.5
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2014-09-26 Cont ID  
Sent By skennedy Date 2014-09-28 Time 12:11 Rev Time 0.00
Received By fmittner Date 2014-09-26 Time 15:29 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2014-09-02 Cont ID  
Sent By fmittner Date 2014-09-02 Time 13:36 Rev Time 0.00
Received By fmittner Date 2014-09-02 Time 13:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-28 Cont ID  
Sent By skennedy Date 2014-09-28 Time 12:11 Rev Time 0.00
Received By skennedy Date 2014-09-26 Time 15:03 Sent To HIST
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-10 Cont ID  
Sent By skennedy Date 2014-09-10 Time 16:26 Rev Time 0.00
Received By skennedy Date 2014-09-02 Time 16:30 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2014-09-28 Cont ID  
Sent By skennedy Date 2014-09-28 Time 11:28 Rev Time 0.00
Received By skennedy Date 2014-09-27 Time 11:00 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-09-10 Cont ID  
Sent By skennedy Date 2014-09-10 Time 13:07 Rev Time 0.00
Received By skennedy Date 2014-09-10 Time 13:07 Sent To  
Notes
2014-09-10 13:09:071ST REVIEW: FBC 2010
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-09-28 Cont ID  
Sent By skennedy Date 2014-09-28 Time 12:04 Rev Time 0.00
Received By skennedy Date 2014-09-28 Time 11:28 Sent To  
Notes
2014-09-28 12:42:04PROVISO:
  
 THE BREAKER SIZES SPECIFIED ON THE PANEL SCHEDULE ARE
 NOT THE SAME AS ON THE A/C SHEET FOR THE AHU &
 CONDENSER. PLEASE ADVISE IF YOU WOULD LIKE TO RESOLVE
 THIS AS A REVISION LATER, OR A RE-SUBMITTAL PRIOR TO
 ISSUANCE.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-09-10 Cont ID  
Sent By skennedy Date 2014-09-10 Time 14:00 Rev Time 0.00
Received By skennedy Date 2014-09-10 Time 14:00 Sent To  
Notes
2014-09-10 14:01:491ST REVIEW: FBC 2010
  
 FBC- 107.3.5.3 - PROVIDE A LARGER, MORE LEGIBLE
 MECHANICAL PLAN TO SHOW SUPPLY DUCTS PER FBC-R M16 &
 BATH EXHAUST PER FBC-R M15.
  
 FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-09-28 Cont ID  
Sent By skennedy Date 2014-09-28 Time 13:00 Rev Time 0.00
Received By skennedy Date 2014-09-28 Time 13:00 Sent To  
Notes
2014-09-28 13:02:361ST REVIEW: FBC 2010
  
 REVIEW OF 9/10/14 WAS ERRONEOUS.
  
 PROVISIONALLY APPROVED; REVISION REQUIRED FOR PLUMBING
 RISER. FBC 107. MINIMUN PLAN REVIEW CRITERIA.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2014-09-10 Cont ID  
Sent By skennedy Date 2014-09-10 Time 13:11 Rev Time 0.00
Received By skennedy Date 2014-09-10 Time 13:11 Sent To  
Notes
2014-09-10 13:11:56THERE ARE NO PROPOSED PLUMBING MODIFICATIONS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2014-09-28 Cont ID  
Sent By skennedy Date 2014-09-28 Time 12:45 Rev Time 0.00
Received By skennedy Date 2014-09-28 Time 12:45 Sent To  
Notes
2014-09-28 12:45:29ROOFING

Review Stop Z ZONING
Rev No 2 Status P Date 2014-09-26 Cont ID  
Sent By fmittner Date 2014-09-26 Time 15:29 Rev Time 0.00
Received By fmittner Date 2014-09-26 Time 15:29 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2014-09-02 Cont ID  
Sent By fmittner Date 2014-09-02 Time 13:36 Rev Time 0.00
Received By fmittner Date 2014-09-02 Time 13:36 Sent To  
Notes
***NONE***