Plan Review Details - Permit 14090005
Plan Review Stops For Permit 14090005
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-11-03 Cont ID  
Sent By skennedy Date 2014-11-03 Time 14:18 Rev Time 0.00
Received By skennedy Date 2014-11-03 Time 14:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-09-26 Cont ID  
Sent By skennedy Date 2014-09-26 Time 17:29 Rev Time 0.00
Received By skennedy Date 2014-09-26 Time 17:29 Sent To  
Notes
2014-09-26 17:41:591ST REVIEW: FBC 2010
  
 PROVIDE ENGINEERING FOR THE LIGHT POLES (APOGEE S19)
 AND EVIDENCE OF REVIEW BY THE ENGINEER OF RECORD, CHRIS
 ARLANSON, FOR THE POLES BASES, THAT HE HAS REVIEWED AND
 APPROVED THE USE OF THE (APOGEE S19) POLSE UPON THE
 BASE HE HAS DESIGNED.
 FBC 107.3.5.1.1(8) - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-CHAPTER 16
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-10-29 Cont ID  
Sent By dhayes Date 2014-10-29 Time 09:30 Rev Time 0.00
Received By dhayes Date 2014-10-29 Time 09:29 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-09-02 Cont ID  
Sent By dhayes Date 2014-09-02 Time 13:49 Rev Time 0.00
Received By dhayes Date 2014-09-02 Time 13:27 Sent To Z
Notes
2014-09-02 14:01:12DATE: 9/2/2014
 PROJECT: MARRIOTT RESIDENCE INN. SITE LIGHTING
 PERMIT#: 14090005
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE LOCATION OF ELECTRICAL PANEL TO SERVE THE
 SITE LIGHTING LOAD,
  
 2) PROVIDE A PANEL SCHEDULE INDICATING THE NEW
 CIRDCUIT(S) AND A LOAD CALCULATION INDICTING THE NEW
 LOAD.
  
 2) INCICATE COMPLIANCE WITH THE FLORIDA BUILDING CODE
 FOR ENERGY CONSERVATION. FBC-E 505.2.4
  
 3) A SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, PLANS, AND SHOP
 DRAWINGS AS REQUIRED FOR GATE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-11-03 Cont ID  
Sent By skennedy Date 2014-11-03 Time 14:18 Rev Time 0.00
Received By skennedy Date 2014-10-28 Time 14:14 Sent To  
Notes
2014-10-28 14:14:34INCOMING SENT TO D. HAYES'S DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-26 Cont ID  
Sent By skennedy Date 2014-09-26 Time 17:42 Rev Time 0.00
Received By skennedy Date 2014-09-02 Time 13:27 Sent To  
Notes
2014-09-16 12:09:55ROUTED TO MISC 2 BOX.
2014-09-02 08:35:30ROUTED TO ELECTRICAL

Review Stop Z ZONING
Rev No 1 Status P Date 2014-09-16 Cont ID  
Sent By aaponte Date 2014-09-16 Time 12:08 Rev Time 0.00
Received By aaponte Date 2014-09-16 Time 12:08 Sent To  
Notes
2014-09-16 12:09:31PROVISO: PARKING SPACES ON BOTH SIDES OF LIGHT POLE AT
 THE SE CORNER OF PARKING LOT, SHALL BE MINIMUM 9 FEET
 IN WIDTH.