| 2014-09-02 16:34:45 | FBC 2010, 1ST REVIEW: |
| | |
| | PROVIDE A COMPLETE ELECTRICAL PLAN PER THE SCPOE OF |
| | WORK DESCRIBED ON THE ELECTRICAL PERMIT APPLICATION AS |
| | FOLLOWS: |
| | |
| | FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE |
| | SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE |
| | LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON |
| | FLOOR PLAN. |
| | |
| | FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO |
| | FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS. |
| | |
| | FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 |
| | FEET OF EACH SLEEPING ROOM. |
| | |
| | NEC 210.52(A)(1)&(2) OUTLET SPACING, IT APPEARS SOME |
| | POINTS ALONG THE WALL EXCEED 6? FROM AN OUTLET |
| | |
| | NEC 210.12B - OUTLETS TO BE AFCI PROTECTED. |
| | |
| | NEC 210.52 (B) (3) - KITCHEN COUNTER TOP RECEPTACLES |
| | SHALL BE SUPPLIED BY NO FEWER THAN TWO SMALL APPLIANCE |
| | BRANCH CIRCUITS. |
| | |
| | NEC 210.63 - PROVIDE A GFI SERVICE OUTLET FOR WITHIN |
| | 7.5? OF MECHANICAL EQUIPMENT. |
| | |
| | NEC 406.11- PROVIDE TAMPER RESISTANT RECEPTACLES. |
| | |
| | NEC 250.56- SERVICE GROUNDING ELECTRODE TO BE AUGMENTED |
| | BY AN ADDITIONAL ELECTRODE 6 FEET AWAY OR PROVIDE |
| | EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS. |
| | |
| | FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL |
| | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| | DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. |
| | |
| | FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS |
| | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON |
| | SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. |
| | THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, |
| | SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO |
| | RECORDS MANAGEMENT. |
| | |