| 2014-08-30 08:52:00 | BUILDING PLAN REVIEW |
| | PERMIT: 14081246 |
| | ADD: 525 S FLAGLER DR UNIT 8B |
| | CONT: BESSENROTH BUILDERS |
| | TEL: (561)844-2872 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SAT. AUG. 30/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING. ON EACH OF THE |
| | PRODUCT APPROVALS, CIRCLE THE SIZE UNIT, TYPE OF |
| | GLAZING, MULLIONS SIZE AND IF REINFORCIED, AND |
| | ASSOCIATED PRESSURES. IF APPROVAL LIST DIFFERENT ANCHOR |
| | CHOICES, CIRCLE THE TYPE OF ANCHOR TO BE INSTALLED AND |
| | ASSOCIATED PRESSURES. IDENTIFY THE PRODUCT APPROVAL |
| | WITH IDENTIFICATION MARKS 1-5 AS TO WHICH APPROVAL IS |
| | ASSOCIATED WITH IDENTIFICATION MARK ON THE ENGINEERING |
| | SHEETS. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.2.1. INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE |
| | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND |
| | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. |
| | |
| | 2) DISCREPANCY IN PLANS. 2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.2.1. INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. THE ENGINEERING PLAN DOES NOT MATCH THE SIZE |
| | OPENINGS PROVIDED ON THE DETAIL SHEETS. |
| | ON THE ENGINEEERED DRAWINGS IDENTIFICATION MARK # 3 IS |
| | SIZED 115.75 X 100 AND #4 IS SIZED AS 121 X 101 WHERE |
| | AS DETAIL SHEETS SHOW (2) OPENINGS SIZED 120 X 101. |
| | |
| | 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | : WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |