Plan Review Details - Permit 14081208
Plan Review Stops For Permit 14081208
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-10-08 Cont ID  
Sent By jwitmer Date 2014-10-08 Time 09:16 Rev Time 0.00
Received By jwitmer Date 2014-10-08 Time 08:57 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-09-17 Cont ID  
Sent By jwitmer Date 2014-09-17 Time 09:35 Rev Time 0.00
Received By jwitmer Date 2014-09-17 Time 08:08 Sent To  
Notes
2014-09-17 09:35:44BUILDING PLAN REVIEW
 PERMIT: 14081208
 ADD: 1500 ELIZABETH ST.
 CONT: FLORIDA FILTRATION & SPRAYBOOTH SERVICES
 TEL: (561)582-5543
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. SEPT. 17/ 2014
 ACTION: DENIED
  
 1)PLEASE PROVIDE THE MANUFACTURERS SPECIFICATION FOR
 THIS SPRAY BOOTH. SHOW COMPLIANCE WITH THE 2010 FBC-B
 F] 416.4 SPRAY BOOTHS.
 SPRAY BOOTHS SHALL BE DESIGNED, CONSTRUCTED AND
 OPERATED IN ACCORDANCE WITH THE FLORIDA FIRE PREVENTION
 CODE.
  
 2010 FL. FIRE PREVENTION CODE NFPA 1.43.1.3.3 & NFPA
 33:5.3 BOTH REQUIRE A 1 HOUR FIRE RESISTANCE RATING.
  
 2) PLEASE PROVIDE THE WIND DESIGN FOR THE EXHAUST DUCT
 THROUGH THE ROOF.
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 2.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 2.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 2.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 2.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 2.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-10-10 Cont ID  
Sent By dhayes Date 2014-10-10 Time 14:41 Rev Time 0.00
Received By dhayes Date 2014-10-10 Time 14:41 Sent To  
Notes
2014-10-10 15:26:1910/10/2014
 PROJECT: GRAND ILLUSIONS
 PERMIT#: 14081208
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) NEC 430.102 LOCATION.
 AN INDIVIDUAL DISCONNECTING MEANS SHALL BE PROVIDED FOR
 EACH CONTROLLER AND SHALL DISCONNECT THE CONTROLLER.
 THE DISCONNECTING MEANS SHALL BE LOCATED IN SIGHT FROM
 THE CONTROLLER LOCATION
  
 2) SEPARATE ELECTRICAL PERMIT APPLICATIONS IS REQUIRED
 FOR INSTALLATION OF ELECTRICAL
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-09-22 Cont ID  
Sent By dhayes Date 2014-09-22 Time 11:02 Rev Time 0.00
Received By dhayes Date 2014-09-22 Time 11:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-10-16 Cont ID  
Sent By pleduc Date 2014-10-16 Time   Rev Time 0.00
Received By pleduc Date 2014-10-16 Time 12:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-08-28 Cont ID  
Sent By pleduc Date 2014-08-28 Time   Rev Time 0.00
Received By pleduc Date 2014-08-28 Time 15:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-10-27 Cont ID  
Sent By hmoser Date 2014-10-27 Time 13:33 Rev Time 0.00
Received By hmoser Date 2014-10-02 Time 14:20 Sent To  
Notes
2014-10-02 14:21:02RE-SUBMITTAL SENT TO JIM WITMER FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-29 Cont ID  
Sent By skennedy Date 2014-09-29 Time 15:08 Rev Time 0.00
Received By skennedy Date 2014-08-27 Time 07:22 Sent To  
Notes
2014-08-28 07:23:30C09

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-10-27 Cont ID  
Sent By hmoser Date 2014-10-27 Time 13:32 Rev Time 0.00
Received By hmoser Date 2014-10-27 Time 12:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-09-25 Cont ID  
Sent By rbergsma Date 2014-09-25 Time   Rev Time 0.75
Received By rbergsma Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2014-09-04 Cont ID  
Sent By sgraham Date 2014-09-04 Time 12:06 Rev Time 0.00
Received By sgraham Date 2014-09-04 Time 12:06 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved