Plan Review Details - Permit 14081190
Plan Review Stops For Permit 14081190
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-10-01 Cont ID  
Sent By jwitmer Date 2014-10-01 Time 07:30 Rev Time 0.00
Received By jwitmer Date 2014-10-01 Time 07:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-09-02 Cont ID  
Sent By jwitmer Date 2014-09-02 Time 14:16 Rev Time 0.00
Received By jwitmer Date 2014-09-02 Time 13:57 Sent To  
Notes
2014-09-02 14:16:47BUILDING PLAN REVIEW
 PERMIT: 14081190
 ADD: 1855 PALM BEACH LAKES # B03
 CONT: TBD
 TEL: (561)348-4805
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. SEPT. 02
 ACTION: DENIED
  
 1) PB OUTLET MALLS:
 A LETTER FROM THE QUALIFIER OF BOTH THE SHELL
 CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT
 CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT
 PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT
 CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK
 HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY
 WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE
 DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER .
 PLEASE PROVIDE THE PERMIT NUMBER, ADDRESS WITH SUITE
 NUMBER WITHIN THE DOCUMENT.
  
 TRACY BECKER, TENANT COORDINATOR
 [email protected]
 618-514-2128
  
 2) THE PLANS ARE NOT STAMPED APPROVED AS NOTED BY NEW
 ENGLAND DEVELOPMENTPALM BEACH OUTLETS SKY GROUP TENANT
 COORDINATOR.
  
 3) SHEET A1 INDICATES THIS TENANT SPACE TO BE A
 BUSINESS OCCUPANCY W/ 1933 SQ FT/ 100 SQ FT = 20
 OCCUPANTS PLEASE UPDATE PLANS.
 2010 FBC-B TABLE 1004.1.1.
  
 4) NEITHER THE A SHEETS NOR E SHEETS SHOW EXIT SIGNS OR
 DIRECTIONAL EXITS SIGNS FOR THIS SPACE. 2010 FBC-B
 1006.3.1 & 1006.3.4 TACTILE SIGNAGE & 1006.3.8.
 DIRECTIONAL SIGNAGE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-09-11 Cont ID  
Sent By rlecky Date 2014-09-11 Time 12:17 Rev Time 0.00
Received By rlecky Date 2014-09-11 Time 11:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-10-06 Cont ID  
Sent By scaldero Date 2014-10-06 Time 13:30 Rev Time 0.00
Received By scaldero Date 2014-10-06 Time 13:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-09-09 Cont ID  
Sent By scaldero Date 2014-09-09 Time 18:44 Rev Time 0.00
Received By scaldero Date 2014-09-09 Time 18:44 Sent To  
Notes
2014-09-09 18:46:14PERMIT #14081190
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected])
 ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR.
  
 EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN
 STOREROOM TO ENSURE EGRESS PATH REQUIREMENTS ARE
 MAINTAINED AT ALL TIMES.
  
 AN APPROVED WRITTEN EMERGENCY PLAN FOR THE EMERGENCY
 EGRESS OF OCCUPANTS IS REQUIRED PRIOR TO OCCUPANCY. ALL
 EMPLOYEES SHALL BE INSTRUCTED AND PERIODICALLY DRILLED
 WITH RESPECT TO THEIR DUTIES UNDER THE PLAN.
  
 EMPLOYEES SHALL BE PERIODICALLY TRAINED OR INSTRUCTED
 IN THE USE OF PORTABLE FIRE EXTINGUISHERS.
  
 SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO THE
 FIRE ALARM AND SPRINKLER SYSTEM.
  
 WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT
 SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED
 AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE
 MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM
 SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD
 INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY
 BE NEEDED.
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-10-10 Cont ID  
Sent By skennedy Date 2014-10-10 Time 17:00 Rev Time 0.00
Received By skennedy Date 2014-09-22 Time 16:49 Sent To  
Notes
2014-09-22 16:49:44RE-SUBMITTAL SENT TO B14 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-13 Cont ID  
Sent By tklarge Date 2014-09-13 Time 08:52 Rev Time 0.00
Received By tklarge Date 2014-08-27 Time 07:07 Sent To  
Notes
2014-09-13 08:54:311) 9/13/14- PLANS DENIED/E-MAILED CONTRACTOR/PLANS
 PLACED IN SMALL "K".TKL
2014-08-28 07:08:00B08

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2014-09-02 Cont ID  
Sent By jwitmer Date 2014-09-02 Time 14:16 Rev Time 0.00
Received By jwitmer Date 2014-09-02 Time 14:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-09-26 Cont ID  
Sent By rbergsma Date 2014-09-26 Time   Rev Time 0.75
Received By rbergsma Date   Time   Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-09-05 Cont ID  
Sent By hmoser Date 2014-09-05 Time 14:23 Rev Time 0.00
Received By hmoser Date 2014-09-04 Time 14:31 Sent To  
Notes
2014-09-05 14:23:00PLAN DENIED
  
 1) SHOW NAIL STATIONS ON MECHANICAL PLAN
 PER SECTION 107 FBC 2010.
 2) REFER TO TABLE 403.3 MINIMUM VENTILATION RATES
 2010 FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-10-06 Cont ID  
Sent By tklarge Date 2014-10-04 Time 03:50 Rev Time 0.00
Received By tklarge Date 2014-10-04 Time 03:50 Sent To  
Notes
2014-10-04 03:53:23*****PROVISO****
 MANUFACTURER'S SPECIFICATION SHEETS FOR THE PEDICURE
 CHAIRS SHALL BE ONSITE FOR THE PLUMBING INSPECTOR. SOME
 OF THE DETAILS ON THE PLANS WERE ILEGIBLE. WPB AMEND.
 TO 2010 FBC SEC.107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-09-13 Cont ID  
Sent By tklarge Date 2014-09-13 Time 08:46 Rev Time 0.00
Received By tklarge Date 2014-09-13 Time 08:46 Sent To  
Notes
2014-09-13 08:50:46WPB ADMIN. AMEND. TO 2010 FBC SEC.107.2.1.
 1) SUBMIT THE MANUFACTURER'S SPECIFICATION SHEETS FOR
 THE PEDICURE CHAIRS.
 2) REVISE THE F.U. LOAD ON SHEET P-1 TO 45 F.U. IN
 COMPLIANCE W/ TABLE 709.1 OF THE 2010 FPC.
 THE SANITARY RISE SHOWS 10 PEDICURE CHAIRS OM ONE OF
 THE WALLS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2014-09-17 Cont ID  
Sent By eschneid Date 2014-09-17 Time 08:54 Rev Time 0.25
Received By eschneid Date 2014-09-17 Time 08:54 Sent To  
Notes
2014-09-17 09:07:06ROOFTOP MECHANICAL EQUIPMENT SHALL BE SCREENED.