Plan Review Details - Permit 14081186
Plan Review Stops For Permit 14081186
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-09-19 Cont ID  
Sent By jwitmer Date 2014-09-19 Time 15:26 Rev Time 0.00
Received By jwitmer Date 2014-09-19 Time 14:38 Sent To  
Notes
2014-09-19 15:26:02BUILDING PLAN REVIEW
 PERMIT: 14081188
 ADD: 1845 PALM BEACH LAKES TEMP. MAN BLDG.
 CONT: MCINTYRE ELWELL & STRAMMER
 TEL: (561) 401-1349
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. SEPT. 19/2014
 ACTION: BUILDING PROVISO
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
  
 1) THIS MANUFACTURERED BUILDING APPEARS TO HAVE BEEN
 BUILT UNDER THE 1997 SBC WITH WIND SPEED OF 110 MPH
 FASTEST MILE.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 102.7 RELOCATION OF
 MANUFACTURED BUILDINGS. 2.2. A RELOCATED BUILDING SHALL
 COMPLY WITH WIND SPEED REQUIREMENTS OF THE NEW
 LOCATION, USING THE
 APPROPRIATE WIND SPEED MAP. IF THE EXISTING BUILDING
 WAS MANUFACTURED IN COMPLIANCE WITH THE
 STANDARD BUILDING CODE (PRIOR TO MARCH 1, 2002), THE
 WIND SPEED MAP OF THE STANDARD BUILDING
 CODE SHALL BE APPLICABLE. IF THE EXISTING BUILDING WAS
 MANUFACTURED IN COMPLIANCE WITH THE
 FLORIDA BUILDING CODE (AFTER MARCH 1, 2002), THE WIND
 SPEED MAP OF THE FLORIDA BUILDING CODE
 SHALL BE APPLICABLE.. IF THE EXISTING BUILDING WAS
 MANUFACTURED IN COMPLIANCE WITH THE STANDARD BUILDING
 CODE (PRIOR TO MARCH 1, 2002), THE WIND SPEED MAP OF
 THE STANDARD BUILDING CODE SHALL BE APPLICABLE. IF THE
 EXISTING BUILDING WAS MANUFACTURED IN COMPLIANCE WITH
 THE FLORIDA BUILDING CODE (AFTER MARCH 1, 2002), THE
 WIND SPEED MAP OF THE FLORIDA BUILDING CODE SHALL BE
 APPLICABLE.
  
 THE 2010 FL BUILDING CODE WIND DESIGN IS 170MPH VULT
 WHICH EQUALS 132 VASD. WHEN THE 110 MPH FASTESTMILE IS
 CONVERTED INTO VASD IT EQUALS 130 MPH. IF YOU
 INTERPALATE THE 132 MPH VASD FOR THIS LOCATION IT WOULD
 BE 130 MPH. SO THE STRUCTURE WILL WITHSTAND THE
 PRESSURES.
  
 THE ADMINISTRATIVE CODE SECTION 107.2 2. A RELOCATED
 BUILDING SHALL COMPLY WITH WIND SPEED REQUIREMENTS OF
 THE NEW LOCATION, USING THE
 APPROPRIATE WIND SPEED MAP. THIS REGION IS A WIND
 -BORNE DEBRIS REGION THAT WILL REQUIRE STORM SHUTTERS
 SEE 2010 FBC-B 1609.1.2 SINCE THE GLAZING IS NOT LARGE
 MISSILE RESISTANT TESTED. STORM SHUTTERS WILL BE
 REQUIRED UNDER A SEPARATE PERMIT.
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-09-03 Cont ID  
Sent By jwitmer Date 2014-09-03 Time 10:51 Rev Time 0.00
Received By jwitmer Date 2014-09-02 Time 12:00 Sent To  
Notes
2014-09-02 13:43:35BUILDING PLAN REVIEW
 PERMIT: 14081186
 ADD: 1845 PALM BEACH LAKES (MANUFACTURED BLDG)
 CONT: MCINTYRE & ELWELL & STRAMMER GC, INC.
 TEL: (941)377-6800
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. SEPT. 01/ 2014
 ACTION: DENIED
  
 1) THE COVERSHEET INDICATES THE VULT 165 MPH, PLEASE
 SHOW HOW THROUGH INTERPOLATION THE 165 MPH WAS ARRIVED.
 THE WIND SPEED MAP
 SEE FIGURE 1609A.
  
 2) THE MODULAR BUILDING NO LONGER HAS A STATE APPROVED
 PLANS, HOW WILL THE INSPECTIONS TAKE PLACE FOR A
 BUILDING THAT IS ALREADY FINISHED.
 2010 FBC-EXISTING BUILDING CODE1202.7 REQUIRED
 INSPECTION AND REPAIRS.
 THE CODE OFFICIAL SHALL BE AUTHORIZED TO INSPECT, OR TO
 REQUIRE APPROVED PROFESSIONALS TO INSPECT AT THE
 EXPENSE OF THE OWNER, THE VARIOUS STRUCTURAL PARTS OF A
 RELOCATED BUILDING TO VERIFY THAT STRUCTURAL COMPONENTS
 AND CONNECTIONS HAVE NOT SUSTAINED STRUCTURAL DAMAGE.
 ANY REPAIRS REQUIRED BY THE CODE OFFICIAL AS A RESULT
 OF SUCH INSPECTION SHALL BE MADE PRIOR TO THE FINAL
 APPROVAL.
  
 3) PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-09-16 Cont ID  
Sent By rlecky Date 2014-09-16 Time 12:17 Rev Time 0.00
Received By rlecky Date 2014-09-16 Time 12:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-09-11 Cont ID  
Sent By rlecky Date 2014-09-11 Time 10:47 Rev Time 0.00
Received By rlecky Date 2014-09-11 Time 10:39 Sent To  
Notes
2014-09-11 10:47:4114081186
 1845 PALM BEACH LAKES BLVD.
 CONSTRUCTION TRAILER FOR WHOLE FOODS
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE AN ELECTRICAL RISER PLAN FOR THE TEMPORARY
 SERVICE FEEDING THE TEMPORARY TRAILER. NEC 215.5
  
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
 561-373-3701
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-09-05 Cont ID  
Sent By scaldero Date 2014-09-05 Time 14:09 Rev Time 0.00
Received By scaldero Date 2014-09-05 Time 14:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-22 Cont ID  
Sent By tklarge Date 2014-09-22 Time 09:42 Rev Time 0.00
Received By tklarge Date 2014-09-15 Time 16:18 Sent To  
Notes
2014-09-15 16:18:23RE-SUBMITTAL SENT TO C12 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-13 Cont ID  
Sent By tklarge Date 2014-09-13 Time 05:36 Rev Time 0.00
Received By tklarge Date 2014-08-27 Time 07:29 Sent To  
Notes
2014-08-28 07:30:13C12

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-09-22 Cont ID  
Sent By tklarge Date 2014-09-22 Time 09:39 Rev Time 0.00
Received By tklarge Date 2014-09-22 Time 09:39 Sent To  
Notes
2014-09-15 16:18:40NEW SHEETS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-09-13 Cont ID  
Sent By tklarge Date 2014-09-13 Time 05:35 Rev Time 0.00
Received By tklarge Date 2014-09-13 Time 05:30 Sent To  
Notes
2014-09-13 05:35:11WPB ADMIN. AMEND. TO 2010 FBC SEC. 107.2.1.
 DENIED
 1)SUBMITT MANUF. SPEC. SHEETS FOR THE EEMAX TANKLESS
 WATER HEATER.
 2) APPROVAL IS REQUIRED FROM THE PALM BEACH COUNTY
 HEALTH DEPT., ENVIRONMENTAL ENGINEERING SECTION, FOR
 THE INSTALLATION OF THE 300 GAL. HOLDING TANK. YOU CAN
 CONTACT THEM AT 561- 837-5900.
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2014-09-03 Cont ID  
Sent By eschneid Date 2014-09-03 Time 11:42 Rev Time 0.25
Received By eschneid Date 2014-09-03 Time 11:42 Sent To  
Notes
***NONE***