Plan Review Details - Permit 14081141
Plan Review Stops For Permit 14081141
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-09-05 Cont ID  
Sent By rmcdouga Date 2014-09-05 Time 13:09 Rev Time 0.00
Received By rmcdouga Date 2014-09-05 Time 13:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-08-29 Cont ID  
Sent By rmcdouga Date 2014-08-29 Time 08:02 Rev Time 0.00
Received By rmcdouga Date 2014-08-29 Time 07:58 Sent To  
Notes
2014-08-29 09:04:282010 FBC
  
 DENIED BY BUILDING
  
 1) THE VALUE FOR THE POOL APPEARS TO BE LOW. SUBMIT A
 COPY OF THE SIGNED CONTRACT TO VERIFY THE VALUATION.
 CITY AMENDMENTS 109.3
  
 2) THE APPLICATIONS FOR THE PLUMBING AND ELECTRICAL
 SUB-PERMITS ARE REQUIRED TO BE SUBMITTED BEFORE THE
 POOL PERMIT IS ISSUED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-08-29 Cont ID  
Sent By rmcdouga Date 2014-08-29 Time 08:02 Rev Time 0.00
Received By rmcdouga Date 2014-08-29 Time 07:58 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2014-08-29 Cont ID  
Sent By rmcdouga Date 2014-08-29 Time 08:02 Rev Time 0.00
Received By rmcdouga Date 2014-08-29 Time 07:58 Sent To  
Notes
2014-08-29 08:02:27NO GAS SHOWN ON PLANS.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-08-29 Cont ID  
Sent By rmcdouga Date 2014-08-29 Time 08:02 Rev Time 0.00
Received By rmcdouga Date 2014-08-29 Time 07:58 Sent To  
Notes
2014-08-26 15:05:07ROUTED TO ZONING

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-09-05 Cont ID  
Sent By rmcdouga Date 2014-09-05 Time 11:13 Rev Time 0.00
Received By rmcdouga Date 2014-09-05 Time 11:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-08-29 Cont ID  
Sent By rmcdouga Date 2014-08-29 Time 08:02 Rev Time 0.00
Received By rmcdouga Date 2014-08-29 Time 07:58 Sent To  
Notes
2014-08-29 08:39:342010 FBC
  
 DENIED BY PLUMBING
  
 1) THE HAYWARD SP 2610 X 1.5 POOL PUMP SPECIFIED ON
 SHEET 3 OF THE PLANS IS A SINGLE SPEED PUMP. FBC ENERGY
 CONSERVATION SECTION 403.9.4(2) REQUIRES 1HP AND
 GREATER POOL PUMP MOTORS TO OPERATE AT TWO OR MORE
 SPEEDS.
  
 2) SUBMIT THE SPECIFICATIONS AND PUMP CURVE FOR THE
 POOL PUMP THAT WILL BE INSTALLED. FBCR 4101.6.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2014-08-28 Cont ID  
Sent By sgraham Date 2014-08-28 Time 08:35 Rev Time 0.00
Received By sgraham Date 2014-08-28 Time 08:35 Sent To B
Notes
***NONE***