Plan Review Details - Permit 14081130
Plan Review Stops For Permit 14081130
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-09-19 Cont ID  
Sent By dhayes Date 2014-09-19 Time 07:15 Rev Time 0.00
Received By dhayes Date 2014-09-19 Time 07:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-09-08 Cont ID  
Sent By dhayes Date 2014-09-08 Time 16:27 Rev Time 0.00
Received By dhayes Date 2014-09-08 Time 16:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-09-12 Cont ID  
Sent By pleduc Date 2014-09-12 Time   Rev Time 0.00
Received By pleduc Date 2014-09-12 Time 14:36 Sent To E
Notes
2014-09-12 15:13:41THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 SHOWING THE MAIN DOUBLE DOOR SWINGING INTO THE HALL, IN
 THE DIRECTION OF TRAVEL TO USE THE DEVICES, IT THEN
 MUST/SHALL MEET THE REQUIREMENTS OF NFPA 101, 2010 ED.
  
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL NOT LEAVE LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL PROJECT NOT MORE
 THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGEWAY, OR A LANDING, WHEN FULLY
 OPEN.....REMAINDER OF CODE CONDITIONS DO NOT APPLY.
  
 DIMENSIONS OF THE HALLWAY AND DOOR ARE NOT PROVIDED;
 HOWEVER, IF DRAWN TO SCALE IT MAY PROVDE ENOUGH ROOM.
 FINAL APPROVAL, IF INSTALLED, IS CONTINGENT ON REVEIW
 AND VERIFICATION BY A FIRE INSPECTOR. INSPECTION WILL
 FAIL IF THE INSTALLATION DOES NOT MEET THE
 REQUIREMENTS.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-08-28 Cont ID  
Sent By pleduc Date 2014-08-28 Time   Rev Time 0.00
Received By pleduc Date 2014-08-28 Time 12:09 Sent To E
Notes
2014-08-28 12:32:08THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE DOUBLE ENTRY DOOR SWING EGRESS DOES NOT MEET # 3 OF
 THE REQUIREMENTS OF 7.2.1.6.2.
  
 (3) THE DOORS SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE
 LOCATED (40IN TO 48IN) VERTICALLY ABOVE THE FLOOR AND
 WITHIN (60IN) OF THE SECURED DOORS.
  
 THE DOORS AS SHOWN OPEN AGAINST EGRESS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-19 Cont ID  
Sent By dhayes Date 2014-09-19 Time 07:15 Rev Time 0.00
Received By dhayes Date 2014-09-11 Time 09:14 Sent To  
Notes
2014-09-12 09:15:04SENT TO FIRE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-08 Cont ID  
Sent By dhayes Date 2014-09-08 Time 16:27 Rev Time 0.00
Received By dhayes Date 2014-08-26 Time 14:11 Sent To  
Notes
2014-08-26 14:11:29TO FIRE
  