| 2014-10-01 10:23:05 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. JOG RD) TO VERIFY IF IMPACT FEES ARE |
| | DUE. BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID |
| | RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY IMPACT |
| | FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE. |
| | |
| | 2- A) NO OPENINGS ARE ALLOWED WHEN THE WALL IS LESS |
| | THAN 3' FROM THE PROPERTY LINE. TABLE R302.1 OF 2010 |
| | FBC-RESIDENTIAL. REVISE PLANS. |
| | |
| | B) EXTERIOR WALL TO BE 1 HOUR FIRE RATED (TESTED IN |
| | ACCORDANCE WITH ASTM E 119 OR UL 263 WITH EXPOSURE FROM |
| | BOTH SIDES. TABLE R302.1. PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS FOR SUCH 1 HR FIRE RATED WALL. |
| | |
| | 3- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS |
| | FOR ALL DOORS AND WINDOWS AS SHOWN ON PLANS. SPECIFY |
| | ALL HEADERS. PROVIDE FRAMING DETAILS AND SPECIFICATIONS |
| | FOR ARCHED OPENINGS AS SHOWN ON PLANS. SEC. R301.1 OF |
| | 2010 FBC- RESIDENTIAL. |
| | |
| | 4- WALL SECTIONS TO SPECIFY FINISH GRADE TO SHOW |
| | COMPLIANCE WITH SEC. R404.1.6 AND SEC. R704 OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | 5- SPECIFY ROOF VENTILATION AS REQUIRED BY SEC. R806 OF |
| | 2010 FBC-RESIDENTIAL. CLEARLY SPECIFY IF DESIGNING |
| | VENTED OR UNVENTED ATTIC AND SHOW COMPLIANCE IN |
| | DRAWINGS. |
| | |
| | 6- REVISE SPECIFICATIONS IN ALL WALL SECTIONS. MINIMUM |
| | STUCCO THICKNESS IS 7/8". TABLE R702.1(1) OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | 7- PROVIDE SPECIFICATIONS FOR THE ROOF SHEATHING |
| | FASTENING AS REQUIRED BY SEC. R803.2.3.1 OF 2010 |
| | FBC-RESIDENTIAL. SPECIFY THE RING -SHANK NAIL TYPE AND |
| | SPACING FOR ALL ROOF ZONES. |
| | |
| | 8- SPECIFY CARBON MONOXIDE ALARMS IN PLANS AS REQUIRED |
| | BY SEC. R315 OF 2010 FBC-RESIDENTIAL. |
| | |
| | 9- ENERGY CALCULATIONS SUBMITTED: (NEED AN ACCURATELY |
| | COMPLETED FORM. SEC. 103.2.1.1.1 OF 2010 FBC-ENERGY |
| | CONSERVATION). |
| | A) FORM 402-2010 CAN NOT BE USED. SEE FORM 402-2010 |
| | GENERAL INSTRUCTION #1. EXCEEDS THE 20% GLASS AREA. |
| | B) SEE GENERAL INSTRUCTIONS #2 AND #3: ALL THE |
| | INFORMATION ON PAGE 1 IS BASED ON THE INFORMATION ON |
| | TABLE 402A AND VALUES MUST BE EQUAL TO OR MORE |
| | EFFICIENT THAN THE REQUIRED LEVELS. |
| | C) COMPLETE ALL THE INFORMATION ON TOP OF FORM. |
| | INCLUDING BUILDER, PERMITTING OFFICE AND JURISDICTION |
| | #. |
| | D) OWNER/AGENT TO SIGN AND DATE FORM. SEC. 103.2.3.2 OF |
| | 2010 FBC-ENERGY CONSERVATION. |
| | |
| | NOTE: THIS IS A CONTRIBUTING HISTORIC HOUSE. IT'S |
| | EXEMPT FROM THE ENERGY CODE. ENERGY CALCULATIONS ARE |
| | NOT REQUIRED. |
| | |
| | 10- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) WINDOW MULLIONS. NOA 10-1115.03 SUBMITTED WITH |
| | FLORIDA PRODUCT APPROVAL FL15587-R1 EXPIRED ON AUGUST |
| | 19, 2014. NEED TO PROVIDE CURRENT NOA. |
| | |
| | B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED BY THE |
| | ENGINEER IN ALL PLANS AND SECTIONS. ***NOTE: PROVIDE |
| | ONLY THE FLORIDA PRODUCT APPROVAL COVER PAGE AND PAGE |
| | SHOWING THE CONNECTOR. OR PROVIDE THE FLORIDA PRODUCT |
| | APPROVAL NEXT TO THE SPECIFIED CONNECTOR. |
| | |
| | 11- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS, |
| | INCLUDING THE DOORS, WINDOWS, ETC. AS REQUIRED BY SEC. |
| | 107.3.4.1 OF CITY AMENDMENTS TO FBC. |
| | |
| | *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | *** PLEASE REMOVE AND REPLACE ALL REVISED SHEETS. |
| | |