Plan Review Details - Permit 14081077
Plan Review Stops For Permit 14081077
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-09-02 Cont ID  
Sent By jwitmer Date 2014-09-02 Time 16:55 Rev Time 0.00
Received By jwitmer Date 2014-09-02 Time 16:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-09-19 Cont ID  
Sent By dhayes Date 2014-09-19 Time 14:46 Rev Time 0.00
Received By dhayes Date 2014-09-19 Time 14:46 Sent To  
Notes
2014-09-19 14:52:34DATE: 9/19/2014
 PROJECT: PALM BEACH LAKES MALL BUILDING H
 PERMIT#: 14081077 MASTER PERMIT#13120923
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE
 THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES. THE BRANCH CIRCUIT THAT FEEDS UNIT EQUIPMENT
 SHALL BE CLEARLY IDENTIFIED AT THE DISTRIBUTION PANEL.
 EMERGENCY LUMINAIRES THAT OBTAIN POWER FROM A UNIT
 EQUIPMENT AND ARE NOT PART OF THE UNIT EQUIPMENT SHALL
 BE WIRED TO THE UNIT EQUIPMENT AS REQUIRED BY 700.9 AND
 BY ONE OF THE WIRING METHODS OF CHAPTER 3. NEC
 700.12(F)
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-09-15 Cont ID  
Sent By scaldero Date 2014-09-15 Time 17:05 Rev Time 0.00
Received By scaldero Date 2014-09-15 Time 17:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-10-10 Cont ID  
Sent By skennedy Date 2014-10-10 Time 16:57 Rev Time 0.00
Received By skennedy Date 2014-10-02 Time 16:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-29 Cont ID  
Sent By hmoser Date 2014-09-29 Time 10:19 Rev Time 0.00
Received By hmoser Date 2014-08-26 Time 16:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-09-29 Cont ID  
Sent By hmoser Date 2014-09-29 Time 10:19 Rev Time 0.00
Received By hmoser Date 2014-09-29 Time 10:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-09-02 Cont ID  
Sent By jwitmer Date 2014-09-02 Time 16:55 Rev Time 0.00
Received By jwitmer Date 2014-09-02 Time 16:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2014-10-16 Cont ID  
Sent By skennedy Date 2014-10-16 Time 15:26 Rev Time 0.00
Received By skennedy Date 2014-10-16 Time 14:20 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2014-10-10 Cont ID  
Sent By eschneid Date 2014-10-10 Time 16:25 Rev Time 0.75
Received By eschneid Date 2014-10-10 Time 16:25 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2014-09-25 Cont ID  
Sent By eschneid Date 2014-09-25 Time 11:31 Rev Time 0.50
Received By eschneid Date 2014-09-25 Time 11:31 Sent To  
Notes
2014-09-25 11:42:17FAILED
  
 1) SHEET A201 EXTERIOR ELEVATIONS SHOWS THE DUMPSTER
 ENCLOSURE GATE AND WALL AT 8 FEET 8 INCHES IN HEIGHT,
 WHILE SHEET A122 TRASH ENCLOSURE DETAILS SHOW THE
 DUMPSTER ENCLOSURE GATE AND WALL AT 8 FEET IN HEIGHT.
 ALL DRAWINGS SHALL BE THE SAME.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
2014-09-11 14:56:019/11/14