Plan Review Details - Permit 14081072
Plan Review Stops For Permit 14081072
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-09-06 Cont ID  
Sent By dhayes Date 2014-09-06 Time 14:43 Rev Time 0.00
Received By dhayes Date 2014-09-06 Time 14:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-08-25 Cont ID  
Sent By dhayes Date 2014-08-25 Time 17:06 Rev Time 0.00
Received By dhayes Date 2014-08-25 Time 17:06 Sent To  
Notes
2014-08-25 17:12:01DATE: 8/25/2014
 PROJECT: TRUMP PLAZA
 PERMIT#: 14081072
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE MANUFACTURERS PRODUCT DATA SHEETS ON
 MECHANICAL EQUIPMENT ALONG WITH A CLEAR DEFINED SCOPE
 OF WORK.
 2) IINDICATE ELECTRICAL SPECS ON EQUIPMENT AND
 CIRCUITRY FEEDING SAME.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-06 Cont ID  
Sent By dhayes Date 2014-09-06 Time 14:44 Rev Time 0.00
Received By dhayes Date 2014-09-05 Time 17:17 Sent To  
Notes
2014-09-05 17:17:56INCOMING SENT TO D. HAYES DESK . JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2014-08-25 Time   Rev Time 0.00
Received By dhayes Date 2014-08-25 Time 17:06 Sent To  
Notes
***NONE***