Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-10-24 Cont ID  
Sent By shill Date 2014-10-24 Time 16:14 Rev Time 0.00
Received By shill Date 2014-10-24 Time 16:14 Sent To  
Notes
2014-10-24 16:16:15****PROVISO****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PER OWNER - THE SPACE IS CURRENTLY IN USE AS A SHOW
 ROOM WITH AN EXISTING DOOR BETWEEN UNITS A AND B.
  
 2. CONTRACTOR TO PROVIDE A FULL SIZE PLAN FOR
 INSPECTIONS AND A FULL SIZE SIGNED AND SEALED PLAN TO
 THE BUILDING DEPARTMENT FOR RECORD RETENTION.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-10-15 Cont ID  
Sent By shill Date 2014-10-15 Time 07:56 Rev Time 0.00
Received By shill Date 2014-10-15 Time 07:56 Sent To FIRE
Notes
2014-10-15 08:01:39****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1-4. OK
  
 5. PREVIOUS COMMENT REVISED AS SCOPE HAS BEEN REDUCED,
 BUT THE REMAINING COMMENT NOT ADDRESSED.
  
 SHEET S1, PLAN SHOWS "EXISTING AREA" IN TWO PLACES
 WHICH APPEAR TO BE INTERIOR (AIR CONDITIONED). AREAS
 ARE NOT MARKED FOR USE. PLEASE REVISE TO INCLUDE ROOM
 DESIGNATIONS FOR THESE AREAS, FBC 107.
  
 ARE YOU REMOVING A PORTION OF A BEARING WALL, COMBINING
 TWO UNITS? APPLICATION IS FOR SUITE "A & B" PER
 CONTRACTOR BUT NO DESIGNATION PROVIDED ON THE PLAN.
 REVISE TO CLARIFY, FBC 107.
  
 IF THIS IS THE CASE, WHAT IS THE EXISTING USE AND
 OCCUPANCY, PROPOSED USE AND OCCUPANCY (FBC CHAPTER 3)?
  
 NOT ENOUGH INFORMATION WAS PROVIDED FOR A COMPLETE
 CHECKLIST.
  
 2ND REVIEW, NOT ADDRESSED. AFTER SCOPE IS DETERMINED,
 MECHANICAL AND/OR PLUMBING REVIEWS MAY BE REQUIRED.
  
 6 - 7. OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-09-13 Cont ID  
Sent By shill Date 2014-09-13 Time 12:21 Rev Time 0.00
Received By shill Date 2014-09-13 Time 12:21 Sent To  
Notes
2014-09-13 12:38:31****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SEE CALCULATIONS. FBC 2010 CHAPTER 35, ACI REFERENCE
 IS OUTDATED. REVISE AND RE-RUN CALCS. WERE CALCS BASED
 ON SOILS ASSUMPTIONS OR SOILS INVESTIGATION REPORT? IF
 A GEOTECHNICAL REPORT WAS PERFORMED, PLEASE PROVIDE. IF
 ONE WAS NOT PERFORMED, GIVE RATIONALE AS TO WHY IT
 SHOULD NOT BE REQUIRED.
  
 2. CALCULATIONS ARE TO BE IN A FORMAT ACCEPTABLE TO THE
 BOARD (FBPE), FAC61G15-23.002. EITHER EACH SHEET IS TO
 BE SIGNED AND SEALED OR AN INDEX SHEET IS TO BE USED.
 YOU CAN SEE THE REQUIREMENTS AT WWW.FBPE.ORG, LEGAL.
  
 3. NEW STOREFRONT PROPOSED. PROVIDE PRODUCT APPROVALS
 REVIEWED BY DESIGNER OF RECORD, FBC 1609, FBC 107.
  
 4. PROVIDE A DETAIL FOR THE INTERIOR WINDOWS - WALL
 SECTION, GLASS PROPOSED, FBC 107.
  
 5. SHEET S1, PLAN SHOWS "EXISTING AREA" IN TWO PLACES
 WHICH APPEAR TO BE INTERIOR (AIR CONDITIONED). AREAS
 ARE NOT MARKED FOR USE. PLEASE REVISE TO INCLUDE ROOM
 DESIGNATIONS FOR THESE AREAS, FBC 107. PLANS DEPICT NEW
 COLUMNS BUT THERE IS NO STRUCTURAL DETAIL FOR THE
 COLUMNS, HEADER, OR REFERENCE TO THIS WORK IN THE BOX
 "SCOPE OF WORK." SO, IT APPEARS THAT UNFINISHED STEEL
 COLUMNS AND HEADERS ARE PROPOSED, NOT CLEAR WHY THIS IS
 TO BE INSTALLED OR WHAT PURPOSE THEY SERVE. REVISE PLAN
 TO PROVIDE CLARIFICATION.
  
 ARE YOU REMOVING A PORTION OF A BEARING WALL, COMBINING
 TWO UNITS? APPLICATION IS FOR SUITE "A & B" PER
 CONTRACTOR BUT NO DESIGNATION PROVIDED ON THEE PLAN.
 REVISE TO CLARIFY, FBC 107.
  
 IF THIS IS THE CASE, WHAT IS THE EXISTING USE AND
 OCCUPANCY, PROPOSED USE AND OCCUPANCY (FBC CHAPTER 3)?
  
 NOT ENOUGH INFORMATION WAS PROVIDED FOR A COMPLETE
 CHECKLIST.
  
 6. THIS PARCEL IS LOCATED IN A SPECIAL HAZARD FLOOD
 ZONE. PLEASE PROVIDE A COPY OF THE ELEVATION
 CERTIFICATE FOR THIS PARCEL SO ADDITIONAL REQUIREMENTS,
 IF ANY, CAN BE DETERMINED. THE ELEVATION CERTIFICATE
 MAY BE SENT VIA EMAIL FOR PRELIMINARY REVIEW, FBC 1612.
 GUIDANCE OF BENEFIT TO THE PROPERTY OWNER MAY BE
 AVAILABLE IF AN ELEVATION CERTIFICATE IS PROVIDED AS
 PRELIMINARY MAPS HAVE BEEN ISSUED AND WE ARE CURRENTLY
 IN THE PUBLIC COMMENT TIME PERIOD (90 DAYS).
  
 7. PROVIDE A COPY OF THE CONTRACT, FBC 109.
  
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-10-16 Cont ID  
Sent By pleduc Date 2014-10-16 Time   Rev Time 0.00
Received By pleduc Date 2014-10-16 Time 08:51 Sent To PC
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-10-16 Cont ID  
Sent By pleduc Date 2014-10-16 Time   Rev Time 0.00
Received By pleduc Date 2014-10-06 Time 11:42 Sent To  
Notes
2014-10-15 08:58:4310/15 TO FIRE
  
2014-10-06 11:42:55RE-SUBMITTAL SENT TO SAMANTHA HILL FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-16 Cont ID  
Sent By shill Date 2014-09-13 Time   Rev Time 0.00
Received By pleduc Date 2014-08-25 Time 07:34 Sent To Z
Notes
2014-08-26 07:35:26TO ZONING BOX

Review Stop Z ZONING
Rev No 1 Status N Date 2014-08-26 Cont ID  
Sent By pleduc Date 2014-10-16 Time 08:59 Rev Time  
Received By sgraham Date   Time   Sent To  
Notes
***NONE***