Plan Review Details - Permit 14081005
Plan Review Stops For Permit 14081005
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-08-26 Cont ID  
Sent By jwitmer Date 2014-08-26 Time 07:09 Rev Time 0.00
Received By jwitmer Date 2014-08-26 Time 06:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-09-08 Cont ID  
Sent By dhayes Date 2014-09-08 Time 12:10 Rev Time 0.00
Received By dhayes Date 2014-09-08 Time 12:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-08-25 Cont ID  
Sent By scaldero Date 2014-08-25 Time 16:04 Rev Time 0.00
Received By scaldero Date 2014-08-25 Time 16:04 Sent To  
Notes
2014-08-25 16:06:02PERMIT # 14081005
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ADDITIONAL EMERGENCY EXIT SIGN WITH DIRECTIONAL
 INDICATED IS NEEDED TO DIRECT OCCUPANTS FROM OUTSIDE
 THE VESTIBULE TO THE NEAREST EXIT. (REAR EXIT)
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected])
 ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 ENTRY DOORS: THUMB-TURN LOCK(S) TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR. IF ENTRY CONSISTS OF DOUBLE
 DOORS, BOTH DOORS REQUIRE INDICATORS.
  
 EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 AN APPROVED WRITTEN EMERGENCY PLAN FOR THE EMERGENCY
 EGRESS OF OCCUPANTS IS REQUIRED PRIOR TO OCCUPANCY. ALL
 EMPLOYEES SHALL BE INSTRUCTED AND PERIODICALLY DRILLED
 WITH RESPECT TO THEIR DUTIES UNDER THE PLAN.
  
 EMPLOYEES SHALL BE PERIODICALLY TRAINED OR INSTRUCTED
 IN THE USE OF PORTABLE FIRE EXTINGUISHERS.
  
 SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO THE
 FIRE ALARM AND SPRINKLER SYSTEM.
  
 WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT
 SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED
 AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE
 MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM
 SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD
 INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY
 BE NEEDED.
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-15 Cont ID  
Sent By dhayes Date 2014-09-08 Time 08:29 Rev Time 0.00
Received By dhayes Date 2014-08-22 Time 11:10 Sent To  
Notes
2014-08-25 11:10:49SENT TO B21 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-08-28 Cont ID  
Sent By hmoser Date 2014-08-28 Time 13:31 Rev Time 0.00
Received By hmoser Date 2014-08-28 Time 13:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-08-26 Cont ID  
Sent By jwitmer Date 2014-08-26 Time 07:09 Rev Time 0.00
Received By jwitmer Date 2014-08-26 Time 06:45 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2014-09-17 Cont ID  
Sent By echneid Date 2014-09-17 Time 11:16 Rev Time 0.25
Received By eschneid Date 2014-09-17 Time 11:16 Sent To PC
Notes
2014-09-17 11:16:44ROOFTOP MECHANICAL EQUIPMENT SHALL BE SCREENED.
2014-08-26 13:56:528/26/14