| 2014-08-25 07:18:58 | BUILDING PLAN REVIEW |
| | PERMIT: |
| | ADD: |
| | CONT: |
| | TEL: (561 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | REVIEW |
| | DATE: |
| | ACTION: DENIED |
| | |
| | 1) THIS LOCATION IS IN AN A-7 FLOOD ZONE, MIN. |
| | ELEVATION SLAB IS 12.5 FT. NGVD. FBC BUILDING 3110.1.2 |
| | / CITY OF WPB CODE OF ORDINANCES SECTION 94-546. |
| | STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A FLOOD |
| | ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE REVIEW |
| | CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE AN |
| | ADDITIONAL 6 INCHES OF ELEVATION |
| | |
| | |
| | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE |
| | REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES |
| | REQUIRED: |
| | (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE |
| | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR |
| | HEIGHT. |
| | (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND |
| | ELEVATION CERTIFICATE IS REQUIRED |
| | (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY |
| | OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE |
| | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR |
| | ATTENDANT |
| | A/C PADS OR OTHER SLABS FOR GENERATORS |
| | |
| | FEMA FORM OMB NO. 1660-0008 EXPIRES: |
| | JULY 31,2015 |
| | |
| | FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR |
| | USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015. |
| | FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE |
| | NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT: |
| | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM. |
| | |
| | 2) SCHLETTER COVER LETTER FOR CANOPY NEEDS TO INDICATE |
| | THE AMOUNT OF PAGES THAT ARE WITHIN THE REPORT TO BE |
| | COVERED BY THE ENGINEERS SEAL. |
| | 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX |
| | SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND |
| | THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE |
| | PRODUCTION & PREPARATION OF EACH SECTION OF THE |
| | ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION |
| | ON THE COVER SHEET OR INDEX. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |