| 2014-09-19 10:41:19 | DATE: 9/18/2014 |
| | PROJECT: FAU SCOREBOARDS |
| | PERMIT#: 14080951 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: PROVISO |
| | |
| | SITE AND ELECTRICAL PLANS FOR SCOREBOARDS ON PERMIT |
| | #12110275. |
| | |
| | 1) 600.3 LISTING. |
| | ELECTRIC SIGNS, SECTION SIGNS, AND OUTLINE LIGHTING ? |
| | FIXED, MOBILE, OR PORTABLE ? SHALL BE LISTED AND |
| | INSTALLED IN CONFORMANCE WITH THAT LISTING, UNLESS |
| | OTHERWISE APPROVED BY SPECIAL PERMISSION. |
| | |
| | 2) 600.4 MARKINGS. |
| | (A) SIGNS AND OUTLINE LIGHTING SYSTEMS. SIGNS AND |
| | OUTLINE LIGHTING SYSTEMS SHALL BE MARKED WITH THE |
| | MANUFACTURER?S NAME, TRADEMARK, OR OTHER MEANS OF |
| | IDENTIFICATION; AND INPUT VOLTAGE AND CURRENT RATING. |
| | (B) SIGNS WITH LAMPHOLDERS FOR INCANDESCENT LAMPS. |
| | SIGNS AND OUTLINE LIGHTING SYSTEMS WITH LAMPHOLDERS FOR |
| | INCANDESCENT LAMPS SHALL BE MARKED TO INDICATE THE |
| | MAXIMUM ALLOWABLE LAMP WATTAGE PER LAMPHOLDER. THE |
| | MARKINGS SHALL BE PERMANENTLY INSTALLED, IN LETTERS AT |
| | LEAST 6 MM (1?4 IN.) HIGH, AND SHALL BE LOCATED WHERE |
| | VISIBLE DURING RELAMPING. |
| | (C) SECTION SIGNS. SECTION SIGNS SHALL BE MARKED TO |
| | INDICATE THAT FIELD-WIRING AND INSTALLATION |
| | INSTRUCTIONS ARE REQUIRED. THE ELECTRICAL CONNECTIONS |
| | TO SAME ARE UNDER A DIFFERENT PERMIT. |
| | |
| | 3) NEC 600.6(A)(1) LOCATION. |
| | DISCONNECTS. EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR |
| | FEEDER CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR |
| | OUT-LINE LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN |
| | EXTERNALLY OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL |
| | OPEN ALL UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN |
| | OR OUTLINE LIGHTING SYSTEM THAT IT CONTROLS. |
| | |
| | 4) FBC-E 505.2 ENERGY CONSERVATION |
| | ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 SHALL |
| | HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN |
| | NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME |
| | CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES |
| | SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS |
| | OF POWER FOR A MINIMUM OF 10 HOURS. FBC-E 505.2 |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |