Plan Review Details - Permit 14080942
Plan Review Stops For Permit 14080942
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-03-25 Cont ID  
Sent By tklarge Date 2015-03-25 Time 08:18 Rev Time 0.00
Received By rmcdouga Date 2015-03-25 Time 09:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-03-09 Cont ID  
Sent By rmcdouga Date 2015-03-09 Time 18:13 Rev Time 0.00
Received By rmcdouga Date 2015-03-09 Time 18:13 Sent To E
Notes
2015-03-09 17:52:413RD REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ON SHEET SP-1 THE OCCUPANCY TYPE IS INCORRECTLY
 SPECIFIED AS R-3. THIS STRUCTURE IS A DETACHED PRIVATE
 GARAGE THAT IS BEING CONVERTED TO A UTILITY SPACE.
 BASED ON THE PLANS THIS IS NON-HABITABLE SPACE. IT IS A
 GROUP U OCCUPANCY. FBC 312
  
 2) ON SHEET SP-1 THE CONSTRUCTION TYPE IS SPECIFIED AS
 TYPE V AND IT SHOULD BE TYPE V-B. FBC 601
  
 3) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE
 STORM PANELS HAS CONFLICTING INFORMATION MARKED. THE
 DIRECT MOUNT INSTALLATION ( SECTION 8) WAS SELECTED ON
 SHEET 4 OF 15. THIS SYSTEM CAN NOT BE USED WITH THE
 TAPCON ANCHORS THAT IS MARKED ON SHEET 10 OF 13. THE
 ANCHORS REQUIRED FOR THIS SYSTEM IS PANELMATES,
 CALK-IN, SOLID SET OR CF TAP-GRIP.
  
 4) THE VALUE OF $1800.00 IS TOO LOW FOR THIS SCOPE OF
 WORK. ALL OF THE WORK THAT WAS DONE TO THE EXISTING
 GARAGE WITHOUT PERMITS OR INSPECTIONS IS REQUIRED TO BE
 INCLUDED IN THE VALUE ( TOTAL REPLACEMENT COST). FBC
 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-01-08 Cont ID  
Sent By rmcdouga Date 2015-01-08 Time 10:57 Rev Time 0.00
Received By rmcdouga Date 2015-01-08 Time 10:19 Sent To  
Notes
2015-01-08 10:57:172ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 THE PLANS THAT WERE RESUBMITTED INDICATE THAT THE
 STRUCTURE WILL BE USED AS A STORAGE/UTILITY ROOM. THIS
 IS NOT CONSIDERED A CHANGE OF OCCUPANCY FROM A GARAGE.
 THEREFORE, ONLY THE IMPROVEMENTS THAT WERE DONE WITHOUT
 PERMITS AND INSPECTIONS WILL NEED TO BE ADDRESSED. I
 COULD NOT LOCATE ANY RECORDS THAT INDICATE THAT THE
 WORK TO ADD THE BATHROOM, UTILITY SINK OR TANKLESS GAS
 WATER HEATER TO THE GARAGE WAS DONE WITH THE REQUIRED
 PERMITS AND INSPECTIONS. UNLESS YOU CAN PROVIDE
 DOCUMENTATION THAT THE WORK WAS PERMITTED AND
 INSPECTED, THE WORK WILL BE REQUIRED TO COMPLY WITH THE
 2010 FBC AND 2008 NEC. ALL OF THE WORK IS REQUIRED TO
 BE PERMITTED AND INSPECTED. YOU CAN CONTACT DIANNE
 FULCHER VIA EMAIL AT [email protected] IF YOU WISH TO
 MAKE A RESEARCH REQUEST. SEE ZONING COMMENTS.
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-09-13 Cont ID  
Sent By rmcdouga Date 2014-09-13 Time 09:48 Rev Time 0.00
Received By rmcdouga Date 2014-09-13 Time 08:05 Sent To P
Notes
2014-09-13 09:09:25PLAN REVIEW COMMENTS
  
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 THE CITY RECORDS INDICATE THAT THE STRUCTURE SHOWN ON
 THE DRAWINGS IS A DETACHED GARAGE. I COULD NOT LOCATE
 ANY RECORDS THAT INDICATE THAT THE WORK TO ADD THE
 BATHROOM, KITCHEN SINK OR TANKLESS GAS WATER HEATER TO
 THE GARAGE WAS DONE WITH THE REQUIRED PERMITS AND
 INSPECTIONS. IT APPEARS THAT THE DETACHED GARAGE WAS
 CONVERTED TO HABITABLE SPACE WITHOUT PERMITS. UNLESS
 YOU CAN PROVIDE DOCUMENTATION THAT THE WORK WAS
 PERMITTED AND INSPECTED, THE STRUCTURE WILL BE REQUIRED
 TO BE RETURNED TO A GARAGE OR BE BROUGHT INTO
 COMPLIANCE WITH THE 2010 FBC AS A CHANGE OF OCCUPANCY
 FROM A GARAGE TO AN OFFICE (PENDING ZONING APPROVAL).
 ALL OF THE WORK IS REQUIRED TO BE PERMITTED AND
 INSPECTED. YOU CAN CONTACT DIANNE FULCHER VIA EMAIL AT
 [email protected] IF YOU WISH TO MAKE A RESEARCH
 REQUEST. SEE ZONING COMMENTS.
  
 THESE COMMENTS WILL NEED TO BE ADDRESSED IF THE
 STRUCTURE IS TO BE CONVERTED FROM A GARAGE TO A
 HABITABLE SPACE.
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 2) FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING
 PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
 3) FBC EXISTING BUILDING 912.6.1 EXTERIOR WALL RATING
 FOR CHANGE OF OCCUPANCY CLASSIFICATION TO A HIGHER
 HAZARD CATEGORY.
 WHEN A CHANGE OF OCCUPANCY GROUP IS MADE TO A HIGHER
 HAZARD CATEGORY AS SHOWN IN TABLE 912.6, EXTERIOR WALLS
 SHALL HAVE FIRE RESISTANCE AND EXTERIOR OPENING
 PROTECTIVES AS REQUIRED BY THE FLORIDA BUILDING CODE,
 BUILDING. SUBMIT TWO COPIES OF A SURVEY SHOWING THE
 LOCATION OF THE STRUCTURES ON THE PROPERTY.
  
 4) FBC EXISTING BUILDING 912.6.3 OPENINGS IN EXTERIOR
 WALLS SHALL BE PROTECTED AS REQUIRED BY THE FLORIDA
 BUILDING CODE, BUILDING. WHERE OPENINGS IN THE EXTERIOR
 WALLS ARE REQUIRED TO BE PROTECTED BECAUSE OF THEIR
 DISTANCE FROM THE PROPERTY LINE, THE SUM OF THE AREA OF
 SUCH OPENINGS SHALL NOT EXCEED 50 PERCENT OF THE TOTAL
 AREA OF THE WALL IN EACH STORY.
  
  
 5) FBC EXISTING BUILDING 907.2 WIND LOADS.
 BUILDINGS AND STRUCTURES SUBJECT TO A CHANGE OF
 OCCUPANCY WHERE SUCH CHANGE IN THE NATURE OF OCCUPANCY
 RESULTS IN A HIGHER RISK CATEGORY BASED ON THE FLORIDA
 BUILDING CODE, BUILDING TABLE 1604.5, SHALL BE ANALYZED
 AND SHALL COMPLY WITH THE APPLICABLE WIND LOAD
 PROVISIONS OF THE FLORIDA BUILDING CODE, BUILDING.
  
 6) FBC EXISTING BUILDING 911.1 LIGHT AND VENTILATION.
 LIGHT AND VENTILATION SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING FOR
 THE NEW OCCUPANCY.
  
 7) SHOW COMPLIANCE WITH 2010 FBC ENERGY CONSERVATION
 SECT. 101.4.3 & 103.2 BY SUBMITTING THE PROPER
 CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS
 402 OR 405.
  
 8) FBC EXISTING BUILDING 912.4.1 MEANS OF EGRESS FOR
 CHANGE TO HIGHER HAZARD CATEGORY.
 WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS MADE TO A
 HIGHER HAZARD CATEGORY, THE MEANS OF EGRESS SHALL
 COMPLY WITH THE REQUIREMENTS OF CHAPTER 10 OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 9) PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE.
 CALL 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED WITH A COPY OF RECEIPT AS APPLICABLE.
  
 10) THE DESCRIPTION OF WORK AND VALUATION ON THE
 APPLICATION WILL NEED TO BE REVISED TO REFLECT THE
 SCOPE OF WORK. FBC 109.3
  
 IN ORDER TO REDUCE PLAN REVIEW TIMES, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-03-12 Cont ID  
Sent By dhayes Date 2015-03-12 Time 09:38 Rev Time 0.00
Received By dhayes Date 2015-03-12 Time 09:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-01-08 Cont ID  
Sent By dhayes Date 2015-01-08 Time 11:03 Rev Time 0.00
Received By dhayes Date 2015-01-08 Time 11:03 Sent To  
Notes
2015-01-08 11:03:18DATE: 01/08/2015
 PROJECT: PARADELO
 PERMIT#: 14080942
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 AS CLEARLY INDICATED IN THE PREVIOUS REVIEWS, THE CITY
 RECORDS INDICATE THAT THE STRUCTURE SHOWN ON THE
 DRAWINGS IS A DETACHED GARAGE. NO RECORDS COULD BE
 LOCATED TO INDICATE THE BATHROOM, KITCHEN, OR TANKLESS
 GAS WATER HEATER WERE ADDED TO THE GARAGE WITH THE
 REQUIRED PERMITS AND INSPECTIONS. SEE BUILDING,
 PLUMBING AND ZONING COMMENTS. ASIDE FROM THE BUILDING
 AND ZONING COMMENTS, THERE ARE SERVERE DESIGN FLAWS
 THROUGHOUT THE ELECTRICAL PLAN SUBMITTED. COSIDER
 CONSULTING WITH A DESIGN PROFESSIONAL FOR SOME
 ASSISTANCE IN COMPLETING THIS OVERALL DESIGN.
 PROVIDED IT IS ALLOWED BY BUILDING, PLUMBING AND ZONING
 AND IN ORDER TO MAKE THE CONVERSION MEET CURRENT
 ELECTRICAL CODE THE FOLLOWING COMMENTS WOULD NEED TO BE
 ADDRESSED:
  
 1) SUFFICIENT CLEAR ACCESS AND DEDICATED WORKING SPACE
 SHALL BE PROVIDED AND MAINTAINED ABOUT ALL ELECTRICAL
 EQUIPMENT TO ALLOW READY AND SAFE OPERATION AND
 MAINTENANCE OF SUCH EQUIPMENT. NEC 110.26 THE KITCHEN
 COUNTER TOP, REFRIGERATOR, DRYER, AND TANKLESS WATER
 HEATER APPEAR TO BE ENCROACHING ON THE REQUIRED WORKING
 CLEARANCES DESCRIBED IN THE NEC 110.26.
  
 2) THE SERVICE DISCONNECTING MEANS SHALL BE INSTALLED
 AT A READILY ACCESSIBLE LOCATION EITHER OUTSIDE OF A
 BUILDING OR STRUCTURE OR INSIDE NEAREST THE POINT OF
 ENTRANCE OF THE SERVICE CONDUCTORS. NEC 230.70(A)(1)
 INDICATE THE LOCATION OF THE ELECTRICAL SERVICE AND THE
 FEED TO THE PANEL IN THE GARAGE.THE SUB PANEL AT THE
 UTILITY STRUCTURE IS INDICATED TO BE FED FROM THE HOUSE
 PANEL WITH A 50AMP BREAKER ON #1 WIRE WITH A 175AMP
 TOTAL CONNECTED LOAD INDICATED AT THE SUB PANEL WITH A
 100AMP MAIN BREAKER.
  
 3) PROVIDE A REVISED RISER DIAGRAM, LOAD CALCULATION
 AND PANEL DIRECTORIES SHOWING COMPLETE FEEDER DETAILS
 AREA IN SQUARE FEET OF THE BUILDING, THE TOTAL
 CALCULATED LOAD BEFORE APPLYING DEMAND FACTORS, THE
 DEMAND FACTORS USED, THE CALCULATED LOAD AFTER APPLYING
 DEMAND FACTORS, AND THE SIZE AND TYPE OF CONDUCTORS TO
 BE USED. NEC 215.5 THE RISER DIAGRAM SUBMITTED DOES NOT
 ADAQUATELY MEET THE MINIMUM DESIGN CRITERIA REQUIRED.
 PROVIDE THE GROUNDING ELECTRODE DETAIL, THE UTILITY
 METERING, SUBMITTALS ON THE GENERATOR AND MTS, A
 REVISED DESIGN IS REQUIRED ON THE RISER TO INDICATE HOW
 THE MTS AND GENERATOR WILL PROVIDE OPTIONAL STANDBY
 POWER FOR THE SERVICE WITHOUT A BACKFEED. THE LOADS
 CALCULATED ON THE PLAN INDICATE A TOTAL OF 415 AMPS
 WITH A 200 AMP MAIN AND A 2/0 FEEDER. THE SUB PANEL AT
 THE UTILITY STRUCTURE IS INDICATED TO BE FED FROM THE
 HOUSE PANEL WITH A 50AMP BREAKER ON #1 WIRE WITH A
 175AMP TOTAL CONNECTED LOAD INDICATED AT THE SUB PANEL.
  
 4) EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE
 LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND
 SPECIFIC PURPOSE OR USE. NEC 408.4 PROVIDE REVISED
 PANEL SCHEDULES.THE PANEL SCHEDULES DO NOT ADAQUATELY
 INDICATE ALL REQUIRED CIRCUITRY OR SHOW ALL CIRCUITRY
 USED ON THE PLAN. THE PANEL SCHEDULE MUST COINCIDE WITH
 THE CIRCUITRY ON THE FLOOR PLAN. NOT ALL CIRCUITS ON
 THE FLOOR PLAN ARE INDICATED IN THE PANEL SCHEDULE.
  
 5) ALL GROUNDING ELECTRODES AS DESCRIBED IN
 250.52(A)(1) THROUGH (A)(7) THAT ARE PRESENT AT EACH
 BUILDING OR STRUCTURE SERVED SHALL BE BONDED TOGETHER
 TO FORM THE GROUNDING ELECTRODE SYSTEM. NEC 250.50
  
 6) WHERE INSTALLED IN OR ATTACHED TO A BUILDING OR
 STRUCTURE, A METAL PIPING SYSTEM(S), INCLUDING GAS
 PIPING, THAT IS LIKELY TO BECOME ENERGIZED SHALL BE
 BONDED TO THE SERVICE EQUIPMENT ENCLOSURE, THE GROUNDED
 CONDUCTOR AT THE SERVICE, THE GROUNDING ELECTRODE
 CONDUCTOR WHERE OF SUFFICIENT SIZE, OR THE ONE OR MORE
 GROUNDING ELECTRODES USED NEC 250.104(3)(B)
  
 7) THE CONNECTION OF A GROUNDING ELECTRODE CONDUCTOR AT
 EACH BUILDING OR STRUCTURE WHERE SUPPLIED BY A
 FEEDER(S) OR BRANCH CIRCUIT(S), SHALL BE MADE AS
 SPECIFIED 250.32, 250.68(A) AND (B).
  
 8) THE VALUE OF THE PROJECT ISN?T REALISTIC AND WILL BE
 REVISED TO INCLUDE THE OVERALL SCOPE OF WORK. FBC WPB
 AMENDMENTS. SECTION 109.3
  
 9) THE PLAN IS STILL NOT SIGNED BY THE DESIGNER. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS TO FBC
 107.2.1
  
 10) A SEPARATE ELECTRICAL PERMIT APPLICATION IS STILL
 REQUIRED WITH THE SUBMITTAL FOR THE ISSUANCE OF AN
 ELCTRICAL PERMIT FOR THE INSTALLATION OF PROPOSED
 ELECTRICAL SCOPE.
  
 11) A SEPARATE ELECTRICAL PERMIT APPLICATION
 ACCOMPANIED BY THE MANUFACTURER PRODUCT APPROVAL
 DOCUMENTATION IS REQUIRED FOR THE GENERATOR AND MTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-09-17 Cont ID  
Sent By dhayes Date 2014-09-17 Time 08:16 Rev Time 0.00
Received By dhayes Date 2014-09-17 Time 08:16 Sent To  
Notes
2014-09-17 08:21:46DATE: 9/17/2014
 PROJECT:
 PERMIT#:
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 AS CLEARLY INDICATED IN THE PREVIOUS REVIEWS, THE CITY
 RECORDS INDICATE THAT THE STRUCTURE SHOWN ON THE
 DRAWINGS IS A DETACHED GARAGE. NO RECORDS COULD BE
 LOCATED TO INDICATE THE BATHROOM, KITCHEN, OR TANKLESS
 GAS WATER HEATER WERE ADDED TO THE GARAGE WITH THE
 REQUIRED PERMITS AND INSPECTIONS. SEE BUILDING,
 PLUMBING AND ZONING COMMENTS.
 PROVIDED IT IS ALLOWED BY BUILDING, PLUMBING AND ZONING
 AND IN ORDER TO MAKE THE CONVERSION MEET CURRENT
 ELECTRUCAL CODE THE FOLLOWING COMMENTS WOULD NEED TO BE
 ADDRESSED:
  
 1) SUFFICIENT CLEAR ACCESS AND DEDICATED WORKING SPACE
 SHALL BE PROVIDED AND MAINTAINED ABOUT ALL ELECTRICAL
 EQUIPMENT TO ALLOW READY AND SAFE OPERATION AND
 MAINTENANCE OF SUCH EQUIPMENT. NEC 110.26 THE KITCHEN
 COUTER TOP, REFRIDGERATOR, DRYER, AND TANKLESS WATER
 HEATER APPEAR TO BE ENCHROCHING ON THE REQUIRED WORKING
 CLEARANCES DESCRIBED IN THE NEC 110.26.
  
 2) BRANCH CIRCUITS FOR LIGHTING AND FOR APPLIANCES,
 INCLUDING MOTOR-OPERATED APPLIANCES, SHALL BE PROVIDED
 TO SUPPLY THE LOADS CALCULATED IN ACCORDANCE WITH
 220.10. IN ADDITION, BRANCH CIRCUITS SHALL BE PROVIDED
 FOR SPECIFIC LOADS NOT COVERED BY 220.10 WHERE REQUIRED
 ELSEWHERE IN THIS CODE AND FOR DWELLING UNIT LOADS AS
 SPECIFIED IN THE NEC 210.11(C).
 (A) NUMBER OF BRANCH CIRCUITS. THE MINIMUM NUMBER OF
 BRANCH CIRCUITS SHALL BE DETERMINED FROM THE TOTAL
 CALCULATED LOAD AND THE SIZE OR RATING OF THE CIRCUITS
 USED. IN ALL INSTALLATIONS, THE NUMBER OF CIRCUITS
 SHALL BE SUFFICIENT TO SUPPLY THE LOAD SERVED. IN NO
 CASE SHALL THE LOAD ON ANY CIRCUIT EXCEED THE MAXIMUM
 SPECIFIED BY 220.18.
 (B) LOAD EVENLY PROPORTIONED AMONG BRANCH CIRCUITS.
 WHERE THE LOAD IS CALCULATED ON THE BASIS OF
 VOLT-AMPERES PER SQUARE METER OR PER SQUARE FOOT, THE
 WIRING SYSTEM UP TO AND INCLUDING THE BRANCH-CIRCUIT
 PANELBOARD(S) SHALL BE PROVIDED TO SERVE NOT LESS THAN
 THE CALCULATED LOAD. THIS LOAD SHALL BE EVENLY
 PROPORTIONED AMONG MULTIOUTLET BRANCH CIRCUITS WITHIN
 THE PANELBOARD(S). BRANCH-CIRCUIT OVERCURRENT DEVICES
 AND CIRCUITS SHALL BE REQUIRED TO BE INSTALLED ONLY TO
 SERVE THE CONNECTED LOAD.
 (C) SMALL-APPLIANCE BRANCH CIRCUITS. IN ADDITION TO THE
 NUMBER OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS OF
 THIS SECTION, TWO OR MORE 20-AMPERE SMALL-APPLIANCE
 BRANCH CIRCUITS SHALL BE PROVIDED FOR ALL RECEPTACLE
 OUTLETS SPECIFIED BY 210.52(B).
 (D) LAUNDRY BRANCH CIRCUITS. IN ADDITION TO THE NUMBER
 OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS OF THIS
 SECTION, AT LEAST ONE ADDITIONAL 20-AMPERE BRANCH
 CIRCUIT SHALL BE PROVIDED TO SUPPLY THE LAUNDRY
 RECEPTACLE OUTLET(S) REQUIRED BY 210.52(F). THIS
 CIRCUIT SHALL HAVE NO OTHER OUTLETS.
 (E) BATHROOM BRANCH CIRCUITS. IN ADDITION TO THE NUMBER
 OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS OF THIS
 SECTION, AT LEAST ONE 20-AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS.
  
 3) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL
 314 AND 315.
  
 4) VERIFY THE WATER HEATER HAS THE REQUIRED ELECTRIC
 DISCONNECT. NEC 422.31
  
 5) THE SERVICE DISCONNECTING MEANS SHALL BE INSTALLED
 AT A READILY ACCESSIBLE LOCATION EITHER OUTSIDE OF A
 BUILDING OR STRUCTURE OR INSIDE NEAREST THE POINT OF
 ENTRANCE OF THE SERVICE CONDUCTORS. NEC 230.70(A)(1)
 INDICATE THE LOCATION OF THE ELECTRICAL SERVICE AND THE
 FEED TO THE PANEL IN THE GARAGE.
  
 6) PROVIDE A RISER DIAGRAM SHOWING FEEDER DETAILS.
 INCLUDE THE AREA IN SQUARE FEET OF THE BUILDING, THE
 TOTAL CALCULATED LOAD BEFORE APPLYING DEMAND FACTORS,
 THE DEMAND FACTORS USED, THE CALCULATED LOAD AFTER
 APPLYING DEMAND FACTORS, AND THE SIZE AND TYPE OF
 CONDUCTORS TO BE USED. NEC 215.5
  
 7) PROVIDE A COMPLETE LOAD CALCULATION. PROVIDE A PANEL
 SCHEDULE SHOWING ALL LOADS BALANCED. INDICATE THE
 PROPOSED WIRING METHOD, WIRE SIZE WITH OVER CURRENT
 PROTECTION FOR ALL CIRCUITS. NEC 220.12, 220.14, 230.31
  
 8) ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI
 PROTECTED. NEC 210.12 NEW RECEPTACLES MUST BE TAMPER
 RESISTANT. NEC 406.11
  
 9) THE CONNECTION OF A GROUNDING ELECTRODE CONDUCTOR AT
 EACH BUILDING OR STRUCTURE WHERE SUPPLIED BY A
 FEEDER(S) OR BRANCH CIRCUIT(S), SHALL BE MADE AS
 SPECIFIED IN THE 2008 EDITION OF THE NEC ARTICLE
 250.68(A) AND (B).
  
 10) ALL 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES
 INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8)
 SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION
 FOR PERSONNEL. NEC 210.8. ALL OUTLETS IN THE KITCHEN
 SHALL BE GFCI PROTECTED.
  
 11) ARC-FAULT PROTECTION IS NOW REQUIRED IN RESIDENTIAL
 OCCUPANCIES ON ALL 15 AND 20 AMP BRANCH CIRCUITS THAT
 ARE NOT ALREADY REQUIRED TO BE PROTECTED BY GROUND
 FAULT INTERRUPTERS CIRCUITS (GFCI) OR OVER 120 VOLTS
 210.12(B)
  
 12) MULTI-WIRE BRANCH CIRCUITS THAT SHARE A COMMON
 GROUND CONDUCTOR (NEUTRAL) MUST SHARE A COMMON
 DISCONNECT OR THE NEUTRALS MUST BE DISCONNECTED AT THE
 SAME TIME 210.4(B).
  
 13) OCCUPIABLE BALCONIES AND PORCHES OVER 20 SQ FT MUST
 NOW HAVE A RECEPTACLE OUTLET (GFCI PROTECTED)
 (210.52(E)(3).
  
 14) RECEPTACLES SHALL BE INSTALLED SUCH THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY WALL
 SPACE IS MORE THAN 6 FEET FROM A RECEPTACLE OUTLET. NEC
 210.52(A)(1)
  
 15) ANY SPACE 2 FEET OR MORE IN WIDTH (INCLUDING SPACE
 MEASURED AROUND CORNERS) AND UNBROKEN ALONG THE FLOOR
 LINE BY DOORS, FIREPLACES, AND SIMILAR OPENINGS. NEC
 210.52(A)(2)(1)
  
 16) SMALL-APPLIANCE BRANCH CIRCUITS IN ADDITION TO THE
 NUMBER OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS OF
 THIS SECTION, TWO OR MORE 20-AMPERE SMALL-APPLIANCE
 BRANCH CIRCUITS SHALL BE PROVIDED FOR ALL RECEPTACLE
 OUTLETS SPECIFIED BY NEC 210.52(B).
  
 17) THE VALUE OF THE PROJECT ISNT REALISTIC AND WILL BE
 REVISED TO INCLUDE THE OVERALL SCOPE OF WORK. FBC WPB
 AMENDMENTS. SECTION 109.3
  
 18) FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET ACCESSIBLE WHILE STANDING AT
 GRADE LEVEL AND LOCATED NOT MORE THAN 2.0 M (61.2 FT)
 ABOVE GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF
 THE DWELLING. NEC 210.52(E)(3)
  
 19) PROVIDE MANUFACTURER PRODUCT ELECTRICAL
 SPECIFICATIONS FOR THE WALL MOUNTED A/C UNIT. INDICATE
 A COMPATABLE ELECTRICAL RECEPTACLE OUTLET FOR SAME.
  
 20) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS
 TO FBC 107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2015-03-21 Cont ID  
Sent By rmcdouga Date 2015-03-21 Time 08:18 Rev Time 0.00
Received By tklarge Date 2015-03-21 Time 07:32 Sent To B
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2015-02-15 Cont ID  
Sent By tklarge Date 2015-02-15 Time 06:14 Rev Time 0.00
Received By tklarge Date 2015-02-15 Time 05:45 Sent To  
Notes
2015-02-15 05:58:371) SUBMIT COPIES OF THE APPLICABLE GAS SIZING TABLE
 FROM THE 2010 FBCR SEC. G2413.3 OR REFERENCE THE
 SPECIFIC SIZING TABLES ON THE PLANS FOR EACH TYPE OF
 PIPE MATERIAL USED FOR THE GAS SYSTEM. 3RD REQUEST.
 2) SUBMIT MANUFACTURER SPECIFICATION SHEETS FOR THE GAS
 REGULATORS. REGULATORS SHALL COMPLY W/ 2010 FBCR
 SEC.G2421.3. 3RD REQUEST.
 3) SPECS FOR A GAS RANGE HAVE BEEN SUBMITTED AND A GAS
 RANGE IS SHOWN ON THE GAS RISER.THE ZONING CODE DOES
 NOT ALLOW A KITCHEN IN THIS STRUCTURE AS IT CAN ONLY BE
 USED AS AN ACCESSORY STRUCTURE TO THE MAIN HOUSE.
 REMOVE THE THE GAS RANGE PIPNG FROM THE GAS RISER
 DIAGRAM COMPLETELY. DO NOT SHOW A CAPPED LINE.
 4) SUBMIT 2 COPIES OF A FULL SET OF MANUFACTURER'S
 SPECIFICATIONS FOR THE PORTABLE GENERATOR AND THE GAS
 BBQ GRILL. THE INFORMATION THAT WAS SUBMITTED IS
 INADEQUATE AND INCOMPLETE. WPB AMEND. TO 2010 FBC SEC.
 107.2.1.3RD REQUEST.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2014-12-22 Cont ID  
Sent By tklarge Date 2014-12-22 Time 15:11 Rev Time 0.00
Received By tklarge Date 2014-12-22 Time 15:11 Sent To  
Notes
2014-12-22 14:40:381) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE
 GENERATOR & BBQ GRILL. FBCR SEC.G2404.3. 2ND REQUEST
 2) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE
 TANKLESS WATER HEATER PER SEC.304 OF THE 2010 FBCR
 SEC.G2407
 3) SUBMIT COPIES OF THE APPLICABLE GAS SIZING TABLE
 FROM THE 2010 FBCR SEC. G2413.3.
 4) SHOW THE TOTAL DISTANCE FROM THE GAS POINT OF
 DELIVERY TO THE MOST REMOTE OUTLET. FBCR SEC. G2413.3.
 5) SHOW THE PIPE SIZES FOR ALL SECTIONS OF THE PIPING
 SYSTEM.WPB AMEND. TO 2010 FBC SEC.107.2.1.
 6) THE VENT SHALL TERMINATE A MINIMUM OF 2 FT. ABOVE
 THE WALL/ROOF PER 2010 FBCR SEC.G2427.6.3 OR MANUF.
 INSTALLATION INSTRUCTIONS. SHOW THIS ON THE PLAN. 2ND
 REQUEST.
 7) GALVANIZED PIPING IS NOT APPROVED FOR USE
 UNDERGROUND PER THE 2010 FBCR SEC.G2414.8, G2415.9.
 8) THE PRESSURE REGULATOR FOR THE TANKLESS WATER HEATER
 SHALL BE VENTED TO THE EXTERIOR PER THE 2010 FBCR
 SEC.2421.3.
 9) SUBMIT MANUF. SPEC. SHEETS FOR THE
 REGULATORS.REGULATORS SHALLL COMPLY WITH 2010 FBCR
 SEC.G2421.1.
 10) A LISTED SHUTOFF VALVE SHALL BE LOCATED IMMEDIATELY
 AHEAD OF EACH MP (MEDIUM PRESSURE) REGULATOR.FBCR
 SEC.G2420.4.
 SEARCH OF CITY RECORDS SHOWS A PERMIT WAS ONLY ISSUED
 FOR THE RANGE. ANY OTHER GAS WORK THAT HAS BEEN
 INSTALLED HAS BEEN DONE WITHOUT THE PROPER PERMITS OR
 INSPECTIONS AND SHALL BE EXPOSED FOR INSPECTION.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2014-09-16 Cont ID  
Sent By tklarge Date 2014-09-16 Time 06:39 Rev Time 0.00
Received By tklarge Date 2014-09-15 Time 13:54 Sent To  
Notes
2014-09-15 14:19:581) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE
 TANKLESS WATER HEATER, GENERATOR,& BBQ GRIL. FBCR
 SEC.G2404.3.
 2) SUBMIT A LEGIBLE GAS DRAWING. THE SUBMITTED DRAWING
 IS TOO DIFFICULT TO READ DUE TO THE SMALL PRINTING.
 PLANS SHALL BE DRAWN TO A MIN. 1/8 " SCALE. WPB ADMIN.
 AMEND. TO 2010 FBC SEC.107.2.1.4.
 3) THE GAS RISER SHALL SHOW THE BTU LOAD FOR EACH
 APPLIANCE. THE BTU LOAD FOR THE TANKLESS WATER HEATER
 SHALL BE SPECIFIC ( THE PLAN SHOWS A RANGE OF
 10,300-180,000 BTU'S.
 4) SUBMIT COPIES OF THE APPLICABLE GAS SIZING TABLE FOR
 THIS INSTALLATION.
 5) SHOW THE DIMENSION OF EACH SECTION OF PIPE AND THE
 TOATAL DISTANCE FROM THE GAS POINT OF DELIVERY TO THE
 MOST REMOTE OUTLET.
 6) SHOW THE PIPE SIZES FOR ALL SECTIONS OF THE PIPING
 SYSTEM.
 7) SHOW THE TYPE OF VENT FOR THE TANKLESS WATER HEATER.
 THE VENT SHALL TERMINATE A MINIMUM OF 2 FT. ABOVE THE
 WALL/ROOF PER 2010 FBCR SEC.G2427.5.3.
 8) SEARCH OF CITY RECORDS SHOWS A PERMIT WAS ONLY
 ISSUED FOR THE RANGE. ANY OTHER GAS WORK THAT HAS BEEN
 INSTALLED HAS BEEN DONE WITHOUT THE PROPER PERMITS OR
 INSPECTIONS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status   Date   Cont ID  
Sent By tlarge Date   Time   Rev Time 0.00
Received By dhayes Date 2015-03-18 Time 16:23 Sent To G
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-03-12 Cont ID  
Sent By dhayes Date 2015-03-12 Time 09:46 Rev Time 0.00
Received By dhayes Date 2015-02-10 Time 08:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-01-08 Cont ID  
Sent By dhayes Date 2015-01-08 Time 11:19 Rev Time 0.00
Received By dhayes Date 2014-12-19 Time 17:15 Sent To  
Notes
2014-12-19 17:15:11R06
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-17 Cont ID  
Sent By dhayes Date 2014-09-17 Time 08:16 Rev Time 0.00
Received By dhayes Date 2014-08-21 Time 07:31 Sent To  
Notes
2014-08-22 07:31:38R-17

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-02-15 Cont ID  
Sent By tklarge Date 2015-02-15 Time 05:45 Rev Time 0.00
Received By tklarge Date 2015-02-15 Time 05:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-12-22 Cont ID  
Sent By tklarge Date 2014-12-22 Time 14:18 Rev Time 0.00
Received By tklarge Date 2014-12-22 Time 11:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-09-16 Cont ID  
Sent By tklarge Date 2014-09-16 Time 06:30 Rev Time 0.00
Received By tklarge Date 2014-09-16 Time 06:30 Sent To  
Notes
2014-09-16 06:37:131) CITY RECORDS DO NOT SHOW ANY PERMITS THAT WERE
 ISSUED FOR THE INSTALLATION OF THE PLUMBING WORK THAT
 IS PRESENT. THIS WORK SHALL BE LEGALLY PERMITTTED AND
 INSPECTED OR IT SHALL BE REMOVED IF NOT PERMITTED BY
 THE ZONING DEPT. SEE ZONING COMMENTS.WPB ADMIN. AMEND.
 TO 2010 FBC SEC.105.1.
 2) SHOW THE SHOWER DIMENSIONS ( LXW) ON THE PLANS. THE
 SHOWER SHALL BE A MIN. OF 30" IN WIDTH AND A MIN. OF
 900 SQ. INCHES. 2010 FBCR SEC.P2708.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2015-02-11 Cont ID  
Sent By dkittred Date 2015-02-11 Time 15:10 Rev Time 0.00
Received By dkittred Date 2015-02-11 Time 09:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2014-12-23 Cont ID  
Sent By dkittred Date 2014-12-23 Time 13:32 Rev Time 0.00
Received By dkittred Date 2014-12-23 Time 13:16 Sent To  
Notes
2014-12-23 13:32:51PLANNING AND ZONING COMMENTS:
  
 12/23/14
  
 IMPROVEMENTS TO ACCESSORY STRUCTURE FOR USE WITH MAIN
 HOUSE ONLY. CURRENT AND/OR FUTURE USE OF THE ACCESSORY
 STRUCTURE AS AN ACCESSORY APARTMENT IS NOT PERMITTED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2014-08-27 Cont ID  
Sent By llouie Date 2014-08-27 Time 10:18 Rev Time 0.00
Received By dkittred Date 2014-08-27 Time 09:06 Sent To  
Notes
2014-08-27 10:18:47PLANNING AND ZONING COMMENTS: ***FAILED***
  
 8/26/14
  
 1. IT IS UNCLEAR FROM THE PLANS WHAT IS NEW AND WHAT IS
 EXISTING. PERMIT APPLICATION INDICATES 'REPAIRS',
 HOWEVER, IT APPEARS A COMPLETE REMODEL OF THE ACCESSORY
 STRUCTURE IS PROPOSED. PLEASE CLARIFY ON THE PLANS.
 (FOR EXAMPLE, ARE THE BATHROOM AND STORAGE ROOM
 CURRENTLY EXISTING AND REPAIRS ARE PROPOSED OR ARE
 THESE COMPLETELY NEW INTERIOR SPACES BEING PROPOSED?)
  
 2. PLEASE NOTE THAT USE OF THE RENOVATED ACCESSORY
 STRUCTURE FOR AN ACCESSORY APARTMENT IS NOT PERMITTED
 AT THIS LOCATION. THE PLANS DO NOT INDICATE AN
 ACCESSORY APARTMENT AS THE INTENDED USE, HOWEVER,
 IMPROVEMENTS PROPOSED ARE MORE CONSISTENT WITH AN
 ACCESSORY APARTMENT THAN A HOME OFFICE. KITCHEN/COOKING
 FACILITIES ARE NOT PERMITTED IN THE ACCESSORY
 STRUCTURE. PROPOSED REFRIGERATOR SHALL BE 'UNDER
 COUNTER' STYLE ONLY TO MEET THIS INTENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  
2014-08-26 13:50:418/26/14