Plan Review Details - Permit 14080938
Plan Review Stops For Permit 14080938
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2014-09-11 Cont ID  
Sent By tklarge Date 2014-09-11 Time 06:04 Rev Time 0.00
Received By tklarge Date 2014-09-11 Time 06:03 Sent To  
Notes
2014-09-11 06:02:401) THE SUBMITTED SPECIFICATION SHEETS FOR THE
 FIREPLACE, DRYER, RANGE AND POOL HEATER ARE
 UNACCEPTABLE. MANUFACTURER'S SPEC SHEETS SHALL BE ON
 JOBSITE AT ROUGH GAS INSPECTION. SPEC. SHEETS MUST SHOW
 THE EQUIPMENT IS LISTED AND LABELED.9/11/14. TKL

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2014-08-26 Cont ID  
Sent By   Date 2014-08-26 Time   Rev Time 0.00
Received By tklarge Date 2014-08-26 Time 11:50 Sent To  
Notes
2014-08-26 12:25:401) SUBMIT MANUFACTURER SPEC. SHEETS FOR THE TANKLESS
 WATER HEATER,RANGE,DRYER, POOL HEATER & FIREPLACE.
 APPLIANCES SHALL BE LISTED AND LABELED PER THE 2010 FGC
 SEC.301.3.
 2) SUBMIT A CLEAR AND LEGIBLE SURVEY SHOWING THE
 DISTANCE OF THE WATER FROM THE PROPERTY LINES ( SIDE &
 REAR)
 3) SUBMIT A GAS RISER DIAGRAM SHOWINGTHE LOCATION OF
 SHUTOFF VALVES AND SECOND STAGE REGULATORS AND THE
 LENGTHS OF THE SECTIONS OF PIPE. CITY WPB ADMIN. AMEND.
 TO 2010 FBC SEC.107.3.5.3. (12).
 4) SUBMIT A COPY OF THE APPROPRIATE TABLE FOR THE CSST
 PIPE FROM THE GAS CODE.SHOW THE CORRESPONDING EHD FOR
 THE CSST ON THE PLAN FROM THE APPROPRIATE GAS SIZING
 TABLE.
 5) INDICATE THE PSI FOR THE CSST SYSTEM.CITY OF WPB
 ADMIN. AMEND. TO 2010 FBC SEC.107.2.1.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2014-09-11 Time   Rev Time 0.00
Received By jwitmer Date 2014-09-05 Time 16:34 Sent To  
Notes
2014-09-05 16:35:14INCOMING SENT TO PLUMBING <$5 K BOX. JW