| 2014-09-03 11:04:30 | DATE: 9/3/2014 |
| | PROJECT: 640 FOREST HILL BLVD |
| | PERMIT#: 14080935 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) THE ELECTRICAL SERVICE RISER INDICATES THE UTILITY |
| | METER IS FEEDING THE PANEL. THE PANEL IS LOCATED INSIDE |
| | THE HOUSE BY THE ATTIC ACCESS. A MAIN DISCONNECT NEEDS |
| | TO BE INSTALLED NEXT TO THE METER. SEE NEC 230.70 |
| | (1)THE SERVICE DISCONNECTING MEANS SHALL BE INSTALLED |
| | AT A READILY ACCESSIBLE LOCATION EITHER OUTSIDE OF A |
| | BUILDING OR STRUCTURE OR INSIDE NEAREST THE POINT OF |
| | ENTRANCE OF THE SERVICE CONDUCTORS. |
| | |
| | 2) PERMANENT LADDERS OR STAIRWAYS SHALL BE PROVIDED TO |
| | GIVE SAFE ACCESS TO THE WORKING SPACE AROUND ELECTRICAL |
| | EQUIPMENT INSTALLED ON PLATFORMS, BALCONIES, OR |
| | MEZZANINE FLOORS OR IN ATTIC OR ROOF ROOMS OR SPACES. |
| | NEC 110.33(B) |
| | |
| | 3) THE OCPD INDICATED IN THE PANEL SCHEDULE/LOAD |
| | CALCULATION IS SHOWN AS AN 80AMP BREAKER WITH #8 WIRE. |
| | SEE NEC 310.16 FOR APPROPRIATE WIRE SIZE. IF AN 80AMP |
| | OCPD IS NEEDED FOR THE TANKLESS WATER HEATER A LARGER |
| | WIRE IS REQUIRED TO SUPPORT THE LOAD IN A SAFE AND CODE |
| | COMPLIANT MANNER. |
| | |
| | 4) THE TANKLESS WATER HEATER IS INDICATED TO BE |
| | INSTALLED IN THE SAME LOACTION AS OR ABOVE THE DRYER. |
| | SEE NEC 110.26 SPACES ABOUT ELECTRICAL EQUIPMENT. |
| | SUFFICIENT ACCESS AND WORKING SPACE SHALL BE PROVIDED |
| | AND MAINTAINED ABOUT ALL ELECTRICAL EQUIPMENT TO PERMIT |
| | READY AND SAFE OPERATION AND MAINTENANCE OF SUCH |
| | EQUIPMENT. |
| | |
| | 5) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS |
| | TO FBC 107.2.1 HAVE THE DESIGNER OF RECORD PRINT THEIR |
| | NAME AND SIGN THE PLANS. |
| | |
| | 6) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL |
| | 314 AND 315 BUILDINGS WITH AN ATTACHED GARAGE REQUIRE |
| | CARBON MONOXIDE SMOKE DETECTORS WITHIN 10' OF SLEEPING |
| | AREAS. |
| | |
| | 7) THE ELECTRICAL APPLICATION CALLS FOR "LOW VOLTAGE |
| | WORK" THE PLANS DO NOT INDICATE ANY SPECIFICE LOW |
| | VOLTAGE WORK. PLEASE REVISE PLANS TO INCLUDE ALL |
| | PROPOSED WORK. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT |
| | /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| | ITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |