Plan Review Details - Permit 14080915
Plan Review Stops For Permit 14080915
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-09-22 Cont ID  
Sent By shill Date 2014-09-22 Time 12:54 Rev Time 0.00
Received By shill Date 2014-09-22 Time 12:54 Sent To  
Notes
2014-09-22 13:04:26****PROVISO****
 ****ISSUED AT CONTRACTOR'S RISK****
 ****REVISION REQUIRED****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SEE FBC 3103, TEMPORARY STRUCTURES. THE FOLLOWING
 ITEMS ARE REQUIRED:
  
 3103.2, CONSTRUCTION DOCUMENTS ARE TO INCLUDE
 INFORMATION DELINEATING THE MEANS OF EGRESS AND
 OCCUPANT LOAD. PLAN IS NOT CLEAR AND OCCUPANT NOT LOAD.
 SUBMIT AS A REVISION.
  
 3103.3, TEMPORARY STRUCTURES SHALL BE LOCATED IN
 ACCORDANCE WITH THE REQUIREMENTS OF TABLE 602. IT IS
 NOT CLEAR WHETHER THIS IS ATTACHED TO AN EXISTING
 BUILDING OR FREE STANDING, AND IF IT IS ATTACHED TO AN
 EXISTING BUILDING, HOW THE PROPOSED TENT WILL AFFECT
 THE EXITING FOR THE EXISTING BUILDING.
  
 3103.4, EXIT ACCESS TRAVEL DISTANCE NOT TO EXCEED 100
 FEET.
  
 PROVIDE A LIFE SAFETY PLAN WHICH SHOWS OCCUPANT LOAD,
 EXITING, TRAVEL DISTANCE, FBC CHAPTER 10.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-09-11 Cont ID  
Sent By dhayes Date 2014-09-11 Time 16:40 Rev Time 0.00
Received By dhayes Date 2014-09-11 Time 16:40 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-09-02 Cont ID  
Sent By pleduc Date 2014-09-02 Time 12:44 Rev Time 0.00
Received By dhayes Date 2014-09-02 Time 09:38 Sent To B
Notes
2014-09-02 09:44:45DATE: 9/2/2014
 PROJECT: IBIS TEMP TENT
 PERMIT#: 14080915
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) THERE IS NO ELECTRICAL INFORMATION INCLUDED IN
 SUBMITTAL PACKAGE. PLEASE PROVIDE THE MINIMAL PLAN
 REVIEW CRITERIA TO INCLUDE BUT NOT BE LIMITED TO THE
 FOLLOWING:
 A. A RISER DIAGRAM, LOAD CALCULATION, AND PANEL
 SCHEDULE(S)
 B. A FLOOR PLAN INDICATING GENERAL LIGHTING, LIGHTING
 CONTROL, EMERGENCY AND EXIT LIGHTING, PROVIDING A SAFE,
 ILLUMINATED MEANS OF EGRESS.
 C. THE FLOOR PLAN TO ALSO INDICATE GENERAL POWER
 OUTLET(S) GFI(S) EQUIPMENT LOCATIONS, INCLUDING LOAD
 AND VOLTAGE, WIRING METHODS, AND CONNECTION DETAILS
 INDICATING DISCONNECTS AS REQUIRED,
 D. A SITE PLAN TO INCLUDE LOCATIONS FOR UTILITIES,
 ELECTRICAL SERVICE EQUIPMENT, AIR CONDITIONING UNITS
 WITH ASSOCIATED WIRING AND DISCONNECTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-09-12 Cont ID  
Sent By pleduc Date 2014-09-12 Time   Rev Time 0.00
Received By pleduc Date 2014-09-12 Time 13:55 Sent To B
Notes
2014-09-12 14:14:37THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE APPROVAL IS CONTIGENT ON VERIFICATIONS FROM A SITE
 FIRE INSPECTION BY A WEST PALM BEACH FIRE INSPECTOR.
  
 THE OCCUPANCY LOADS SHALL BE VERIFIED AND OCCUPANCY
 LOADS SIGNS SHALL BE INSTALLED.
  
 EXIT SIGNS AND EMERGENCY LIGHTING SHALL BE VERIFIED.
 THE FIRE INSPECTOR RESERVES THE AUTHORITY TO ADD EXIT
 SIGNS AND/OR EMERGENCY LIGHTING AS NEEDED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-08-21 Cont ID  
Sent By pleduc Date 2014-08-21 Time   Rev Time 0.00
Received By pleduc Date 2014-08-21 Time 12:11 Sent To E
Notes
2014-08-21 12:44:22THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE PROPOSED LOCATION OF THE TENT WAS NOT, IS NOT,
 DESIGNED FOR THIS TYPE OF OCCUPANCY OR STRUCTURE.
  
 IN THE EVENT OF AN EMERGENCY IN THE EXISTING BUILDING
 AND/OR IN THE PROPOSED TENT STRUCTURE, THE OCCUPANTS
 SHALL BE AFFORDED A CLEAR, SAFE EXIT PATH, EXIT DOOR
 AND EXIT DISCHARGE LEADING TO A PUBLIC WAY.
  
 NO EXITS, EXIT DISCHARGES, OR EMERGENCY LIGHTS ARE
 IDENTIFIED ON THE PLAN. THE WORD "DOOR" IS ON THE PLAN;
 HOWEVER, THE SIZE OF THE DOOR IS NOT INDICATED OR THE
 TYPE OF EXIT DOOR HARDWARE THAT IS REQUIRED FOR THIS
 ASSEMBLEY OCCUPANCY.
  
 NOT EXIT PATH LEADING TO A PUBLIC WAY FROM THE EXIT
 DISCHARGE (DOOR) IS NOT IDENTIFIED ON THE PLAN.
  
 A LIFE SAFETY PLAN, INCLUDING ALL EXITS, EXIT PATHS,
 CORRIDORS, EXIT DISCHARGES, OCCUPANCY LOADS, EMERGENCY
 LIGHTING SHALL BE PROVIDED.
  
 A COMPREHENSIVE LIFE SAFETY PLAN THAT INCLUDES THE
 EXISTING BUILDING'S OCCUPANY LOADS, EXIT PATHS, AND
 EXIT DISCHARGES OF THE SURROUNDING STRUCTURES,
 INCLUDING FENCING, MUST BE CONSIDERED, PLANNED FOR AND
 SUBMITTED FOR APPROVAL.
  
 THE SEATING PLAN IS NOT APPROVED AND MUST BE SUBMITTED
 SEPARATLY, INLUDING ALL DIMENSIONS BETWEEN CHAIRS AND
 TABLES AND ENSURING A CLEAR AND CONTINUOUS EXIT PATH
 LEADING TO AN EXIT.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-22 Cont ID  
Sent By shill Date 2014-09-22 Time 13:04 Rev Time 0.00
Received By shill Date 2014-09-09 Time 16:40 Sent To  
Notes
2014-09-11 16:41:54MISC. 2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-02 Cont ID  
Sent By dhayes Date 2014-09-02 Time 10:16 Rev Time  
Received By dhayes Date   Time   Sent To  
Notes
2014-08-21 10:35:13ROUTED TO FIRE (TWO APPLICATIONS ARE TOGETHER IN THIS
 PACKAGE ONE FOR THE TEMPORARY TENT AND ONE FOR THE
 ELECTRICAL)