| Plan Review Stops For Permit 14080885 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2014-11-07 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-11-07 |
Time |
13:26 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-11-07 |
Time |
13:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2014-11-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-11-04 |
Time |
18:20 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-11-04 |
Time |
16:49 |
Sent To |
|
|
| Notes |
| 2014-11-04 18:23:15 | PLAN REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | BUILDING | | | | | | 1) ONE OF THE TWO REQUIRED PLAN SETS IS MISSING SHEET | | | S-1. FBC 107.1 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2014-10-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-10-14 |
Time |
10:45 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-10-14 |
Time |
10:45 |
Sent To |
|
|
| Notes |
| 2014-10-14 11:39:38 | PLAN REVIEW COMMENTS | | | | | | | | | 2ND REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | BUILDING | | | | | | 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. SHEETS C-1 AND | | | E-1 ARE REQUIRED TO HAVE THE NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR THE DRAWING. | | | | | | 2) FBC R301.2.1 SPECIFY THE METHOD OF ATTACHMENT THAT | | | WILL BE USED TO INSTALL THE CONCRETE ROOF TILE. IF A | | | ROOF TILE ADHESIVE IS USED SUBMIT TWO COPIES OF IT'S | | | PRODUCT APPROVALS THAT HAVE BEEN APPROVED IN WRITING BY | | | THE DESIGNER OF RECORD. DCA RULE 9N-3 AND FBC 107.3.4.1 | | | | | | 3) ON SHEET S-2 THE EXPOSURE CATEGORY IS SPECIFIED AS | | | "D" . EXPOSURE CATEGORY "C" IS SPECIFIED ON SHEETS A-1 | | | AND A-2. THIS STRUCTURE IS LOCATED IN EXPOSURE C, THE | | | WINDLOAD PRESSURES ARE INCREASED IN EXPOSURE D. PLEASE | | | CORRECT. FBC R301.1.3 AND FBC R301.2.1.4.3 | | | | | | 4) THE PLANS INDICATE THAT THE LOCATION OF THE | | | SKYLIGHTS IS TO BE DETERMINED ON THE JOB. THE SKYLIGHTS | | | HAVE A DESIGN PRESSURE OF +60 PSF, -100 PSF. THEY WILL | | | NOT MEET THE UPLIFT PRESSURES OF THE CORNERS (ROOF ZONE | | | 3) FOR EXPOSURE D. FBC R301.1.3 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2014-09-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-09-16 |
Time |
18:53 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-09-16 |
Time |
18:04 |
Sent To |
|
|
| Notes |
| 2014-09-16 18:53:38 | PLAN REVIEW COMMENTS | | | | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | BUILDING | | | | | | 1) SHEET A-2 OF THE PLANS CONTAINS STRUCTURAL DETAILS | | | AND THE NAME OF THE ENGINEER IS IN THE TITLE BLOCK. | | | THEREFORE, THIS SHEET IS REQUIRED TO BE SIGNED AND | | | SEALED BY THE ENGINEER PER CHAPTER 471, FLORIDA | | | STATUTES AND FAC 61G15-23.002. | | | | | | 2) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 | | | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING, | | | SLIDING GLASS DOOR (THE ONE SUBMITTED HAS BEEN | | | SUPERSEDED) AND SKY LIGHT SUBMITTALS. CIRCLE THE | | | APPLICABLE INFORMATION SUCH AS GLASS TYPE, FASTENERS, | | | DESIGN PRESSURES ON THE PRODUCT APPROVALS. IF AN | | | ADHESIVE WILL BE USED TO ATTACH THE ROOF TILES, THEN | | | SUBMIT PRODUCT APPROVALS FOR IT ALSO. | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2014-11-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-11-04 |
Time |
17:57 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-11-04 |
Time |
16:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2014-10-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-10-14 |
Time |
10:43 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-10-14 |
Time |
10:43 |
Sent To |
|
|
| Notes |
| 2014-10-14 10:44:48 | PLAN REVIEW COMMENTS | | | | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | ELECTRICAL | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. THE NAME AND | | | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE ELECTRICAL | | | DESIGN IS MISSING FROM THE ELECTRICAL PLAN. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2014-09-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-08-20 |
Time |
18:20 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-08-20 |
Time |
18:20 |
Sent To |
|
|
| Notes |
| 2014-09-16 18:55:51 | PLAN REVIEW COMMENTS | | | | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | ELECTRICAL | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. THE NAME AND | | | SIGNATURE IS MISSING FROM THE ELECTRICAL PLAN. | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2014-11-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-11-04 |
Time |
18:23 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-10-28 |
Time |
16:50 |
Sent To |
|
|
| Notes |
| 2014-10-28 16:51:00 | RE-SUBMITTAL SENT TO ROBERT MCDOUGAL FOR REVIEW. JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-10-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-10-14 |
Time |
10:45 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-10-07 |
Time |
15:03 |
Sent To |
|
|
| Notes |
| 2014-10-07 15:03:54 | TO RM'S DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-09-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-09-16 |
Time |
18:53 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-08-20 |
Time |
18:19 |
Sent To |
|
|
| Notes |
| 2014-09-13 14:23:36 | 9/13 TO RM DESK | | | | | 2014-08-20 18:19:59 | SENT TO ZONING |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2014-08-21 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2014-08-21 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2014-08-21 |
Time |
15:28 |
Sent To |
B |
|
| Notes |
|
|