Plan Review Details - Permit 14080872
Plan Review Stops For Permit 14080872
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-10-08 Cont ID  
Sent By rmcdouga Date 2014-10-08 Time 14:25 Rev Time 0.00
Received By rmcdouga Date 2014-10-08 Time 14:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-09-25 Cont ID  
Sent By rmcdouga Date 2014-09-25 Time 09:30 Rev Time 0.00
Received By rmcdouga Date 2014-09-22 Time 07:07 Sent To  
Notes
2014-09-24 18:13:20PLAN REVIEW COMMENTS
  
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) VALUATION - FBC 109.3 BUILDING PERMIT VALUATION. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. BASED
 ON THE LATEST ICC VALUATION THE VALUE OF THIS SINGLE
 FAMILY DWELLING IS $265, 326.00.
  
 2) THE " ROOF OVERHUNG" DETAIL AND SECTION ON SHEET A-2
 IS MISSING INFORMATION. SUCH AS, THE 2 X 6 LEDGER TO
 WALL ATTACHMENT, THE RAFTERS TO 4 X 6 HEADER ATTACHMENT
 , THE 4 X 4 ANGLE BRACE END ATTACHMENT, ETC. SPECIFY
 THE CONNECTORS AND/OR FASTENERS THAT WILL BE USED. ALSO
 SPECIFY THE SLOPE OF THIS ROOF. FBC-R 301.1
  
 3) ON SHEET A-3, THE WINDLOAD DATA LISTS THE ROOF SLOPE
 AS 6:12 AND THE END ZONE A = 3.0 FT. THE PLANS SPECIFY
 THE ROOF SLOPE AS 5:12 AND FBC-R FIGURE R301.2(7)
 SPECIFIES END ZONE 5 AS A = 4.0 FT. IN ALL CASES.
 PLEASE CORRECT.
  
 4) THE FLOOR AND ROOF TRUSS CONNECTIONS TO THE WALLS
 ARE REQUIRED TO BE SPECIFIED ON THE PLANS BY THE
 STRUCTURAL ENGINEER OF RECORD. FAC 61G15-31.003 ON
 SHEET S-2 SOME OF THE TRUSS TO WALL CONNECTIONS THAT
 ARE THE RESPONSIBILITY OF THE STRUCTURAL ENGINEER OF
 RECORD ARE LABELED PER TRUSS MANUFACTURER.
  
 5) SPECIFY THE CONNECTORS THAT WILL BE USED TO ATTACH
 THE FLOOR TRUSSES TO THE WALL LEDGERS. FBC-R501.2
  
 6) ON SHEET S-3 THE NEGATIVE UPLIFT PRESSURES ARE ROOF
 ZONES 2 AND 3 ARE THE SAME IN THE ROOF CLADDING SERVICE
 (NOMINAL) WIND LOAD SCHEDULE. THE NEGATIVE (UPLIFT)
 PRESSURES FOR ROOF ZONE 3 SHOULD BE MORE ( - 73.9 PSF
 ). FBC-R TABLE R301.2(2) AND R301.2.1
  
 7) SPECIFY THE SIZE OF THE OVERHEAD GARAGE DOOR ON THE
 PLANS.
  
 8) SPECIFY THE OVERHEAD GARAGE DOOR AND FRONT DOOR
 COMPONENT & CLADDING PRESSURES ON THE PLANS.
  
 9) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE 7' TALL
 OUTSWING FRONT DOOR AND THE DOUBLE OUTSWING FRENCH
 DOORS AS REQUIRED BY DCA RULE 9N-3. THE ONES THAT WERE
 SUBMITTED (NOA NO. 11-1013.22) EXPIRED IN 2012.
  
 10) SPECIFY THE ATTACHMENT METHOD THAT WILL BE USED TO
 INSTALLED THE CLAY ROOF TILES. IF ONE OF THE APPROVED
 ADHESIVES LISTED IN THE ROOF TILE PRODUCT APPROVAL WILL
 BE USED, THEN SUBMIT TWO SETS OF PRODUCT APPROVALS FOR
 IT. DCA RULE 9N-3 AND FBC-R905.3
  
 11) FBC 107.3.4 - THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9N-3 ARE REQUIRED TO BE REVIEWED AND APPROVED
 IN WRITING BY THE DESIGNER OF RECORD.
  
 IN ORDER TO REDUCE PLAN REVIEW TIMES, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-10-08 Cont ID  
Sent By rmcdouga Date 2014-10-08 Time 14:25 Rev Time 0.00
Received By rmcdouga Date 2014-10-08 Time 14:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-09-22 Cont ID  
Sent By rmcdouga Date 2014-09-22 Time 18:27 Rev Time 0.00
Received By rmcdouga Date 2014-09-22 Time 18:27 Sent To  
Notes
2014-09-22 18:39:07APPROVED WITH EXCEPTION.
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
  
 1) NEC 210.8 (A) (1)-(8) - GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION REQUIRED. PROVIDE GFCI
 PROTECTION IN THE GARAGE, UTILITY ROOM AND RECEPTACLES
 SERVING THE KITCHEN COUNTERTOPS.
  
 2) NEC 210.70 PROVIDE A SWITCH CONTROLLED LIGHTING
 OUTLET IN EACH ATTIC SPACE.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-10-22 Cont ID  
Sent By rmcdouga Date 2014-10-22 Time 16:18 Rev Time 0.00
Received By rmcdouga Date 2014-10-21 Time 11:32 Sent To  
Notes
2014-10-22 11:33:30IMPACT FEES STAMPED PLANS SENT TO ROBERT MCDOUGAL FOR
 PROCESSING. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-10-08 Cont ID  
Sent By rmcdouga Date 2014-10-08 Time 14:28 Rev Time 0.00
Received By rmcdouga Date 2014-09-29 Time 07:45 Sent To  
Notes
2014-09-30 07:46:47RE-SUBMITTAL SENT TO ZONING SHELF FOR DANIELLE'S
 REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-25 Cont ID  
Sent By rmcdouga Date 2014-09-25 Time 09:30 Rev Time 0.00
Received By rmcdouga Date 2014-08-20 Time 18:32 Sent To  
Notes
2014-08-20 18:32:41R04

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2014-10-22 Cont ID  
Sent By rmcdouga Date 2014-10-22 Time 16:18 Rev Time 0.00
Received By rmcdouga Date 2014-10-22 Time 16:18 Sent To  
Notes
2014-10-22 16:20:08MU-2014-22969, PAID $1518.49

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2014-10-08 Cont ID  
Sent By rmcdouga Date 2014-10-08 Time 14:26 Rev Time 0.00
Received By rmcdouga Date 2014-10-08 Time 14:26 Sent To  
Notes
2014-10-08 14:27:13IMPACT FEES
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-09-22 Cont ID  
Sent By rmcdouga Date 2014-09-22 Time 07:08 Rev Time 0.00
Received By rmcdouga Date 2014-09-22 Time 07:08 Sent To  
Notes
2014-09-22 07:09:19IMPACT FEES
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-08-28 Cont ID  
Sent By hmoser Date 2014-08-28 Time 15:12 Rev Time 0.00
Received By hmoser Date 2014-08-28 Time 13:51 Sent To  
Notes
2014-08-28 15:12:28PROVISO
 REFER TO SECTION M1503.4 MAKEUP AIR REQUIRED
 2010 FBC RESIDENTIAL.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-09-19 Cont ID  
Sent By tklarge Date 2014-09-13 Time 11:47 Rev Time 0.00
Received By tklarge Date 2014-09-13 Time 04:40 Sent To  
Notes
2014-09-13 04:41:43**** PROVISO****
 SUBMIT REVISED SANITARY RISER DIAGRAM FOR REVIEW AND
 APPROVAL PRIOR TO PLUMBING GROUND ROUGH INSPECTION.

Review Stop Z ZONING
Rev No 2 Status P Date 2014-09-30 Cont ID  
Sent By dkittred Date 2014-09-30 Time 08:53 Rev Time 0.00
Received By dkittred Date 2014-09-30 Time 08:41 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2014-08-26 Cont ID  
Sent By llouie Date 2014-08-26 Time 16:11 Rev Time 0.00
Received By dkittred Date 2014-08-26 Time 14:35 Sent To  
Notes
2014-08-26 16:11:35PLANNING AND ZONING COMMENTS: ***FAILED***
  
 8/26/14
  
 1. STRUCTURAL INTRUSIONS ARE NOT TO PROJECT GREATER
 THAN THREE (3) FEET INTO A REQUIRED SETBACK [ZLDR SEC.
 94-305(B)(2)]. THE ROOF COVERING PROVIDED ON THE FRONT
 OF THE RESIDENCE EXTENDS 3'-6" INTO THE REQUIRED FRONT
 SETBACK. PLEASE REVISE.
  
 2. REAR SETBACK IS LABELED INCORRECTLY AS 'FRONT'.
 PLEASE REVISE.
  
 3. A SEPARATE PERMIT NEEDS TO BE SUBMITTED FOR THE
 LANDSCAPING PLAN. PLEASE NOTE, ON THE PLAN PROVIDED THE
 OPEN SPACE SHOULD BE 3,446 SQ. FT. RATHER THAN 2,350
 SQ. FT. WHICH APPEAR TO HAVE INCLUDED THE SECOND FLOOR
 SQUARE FOOTAGE IN THE CALCULATION. ADDITIONALLY, PER
 ZLDR SEC. 94-442(2)(A) THE CALCULATION FOR REQUIRED
 NUMBER OF TREES WILL NEED TO BE ADJUSTED TO 1 PER 1,200
 SQUARE FEET OF OPEN SPACE RATHER THAN 1 PER 1,600
 SQUARE FEET. AS, A RESULT A MINIMUM OF THREE (3) TREES
 AND SEVEN (7) SHRUBS WILL BE REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  
2014-08-26 13:46:398/26/14