Plan Review Details - Permit 14080810
Plan Review Stops For Permit 14080810
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-12-09 Cont ID  
Sent By shill Date 2014-12-09 Time 11:16 Rev Time 0.00
Received By shill Date 2014-12-09 Time 11:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-09-04 Cont ID  
Sent By eschneid Date 2014-09-02 Time 16:27 Rev Time 0.00
Received By shill Date 2014-09-04 Time 18:21 Sent To  
Notes
2014-09-04 18:25:33****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. NOT ENOUGH INFORMATION WAS PROVIDED TO GIVE AN
 ACCURATE CORRECTION LIST.
  
 FBC 107, PROVIDE A SITE PLAN SHOWING PROPOSED LOCATION.
  
 FBC CHAPTER 10, CHAPTER 31, PROVIDE PROPOSED HEIGHT.
  
 IT IS NOT CLEAR WHETHER THE PROPOSED CANOPY WILL EXTEND
 OVER PUBLIC PROPERTY, PRIVATE PROPERTY, AND WHETHER IT
 IS TO BE INSTALLED OVER A PEDESTRIAN AREA.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-12-09 Cont ID  
Sent By shill Date 2014-12-09 Time 11:16 Rev Time 0.00
Received By shill Date 2014-11-14 Time 08:03 Sent To  
Notes
2014-11-15 08:04:57ROUTED TO ZONING. COULD NOT LOCATE APPLICATION AND
 DENIED PLANS.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-04 Cont ID  
Sent By shill Date 2014-09-04 Time 18:25 Rev Time 0.00
Received By shill Date 2014-08-18 Time 17:24 Sent To  
Notes
2014-08-18 17:24:35ZONING
  

Review Stop Z ZONING
Rev No 2 Status F Date 2014-12-04 Cont ID  
Sent By eschneid Date 2014-12-04 Time 13:40 Rev Time 0.25
Received By eschneid Date 2014-12-04 Time 11:49 Sent To B
Notes
2014-12-04 11:50:18IN REVIEW
  
 1) REPEAT COMMENT: THE MANAGEMENT STAMP WAS NOT
 PROVIDED ON THE DRAWINGS.
  
 2) REPEAT COMMENT: THE PALM BEACH OUTLETS DESIGN
 GUIDELINES PERMIT A MAXIMUM PROJECTION OF CANOPIES AND
 AWNINGS TO BE FOUR (4) FEET. THE PLANS AND
 SPECIFICATION SHEETS SHOW THE METAL RAIN HOOD CANOPIES
 CALLED SIX (6) FEET. PLEASE NOTE THAT ZONING STAFF WAS
 UNDER THE IMPRESSION THAT THESE WERE DESIGNED AS PART
 OF THE STRUCTURAL BUILDING SHELL (WHICH WOULD NO LONGER
 MAKE THEM CANOPIES SUBJECT TO THE FOUR FOOT LIMITATION)
 AND NOT AS ADD ON CANOPIES AS SHOWN ON THIS PERMIT.
  
 3) PARTIAL REPEAT COMMENT: NO SPECIFICATION SHEETS WERE
 PROVIDED FOR THE METAL AWING ON THE WEST SIDE OF THE
 BUILDINGS (PLANS SHOW FOUR FOOT PROJECTION) OR THE
 METAL AWNING ON THE NORTH SIDE OF THE BUILDING (PLANS
 SHOW A SIX FOOT PROJECTION). THE METAL AWNING MAY NOT
 PROJECT SIX (6) FEET.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2014-09-02 Cont ID  
Sent By eschneid Date 2014-09-02 Time 14:45 Rev Time 0.25
Received By eschneid Date 2014-09-02 Time 14:45 Sent To B
Notes
2014-09-02 16:26:52FAILED
  
 1) THE MANAGEMENT STAMP WAS NOT PROVIDED ON THE
 DRAWINGS.
  
 2) NO BUILDING ELEVATION PLAN WAS PROVIDED TO SHOW
 WHERE THE AWNINGS AND CANOPIES ARE LOCATED. ALL THE
 PROPOSED AWNING/CANOPY TYPES SHALL BE SPECIFICALLY TIED
 TO THEIR LOCATION ON THE ELEVATION PLAN.
  
 3) THE ELEVATION PLAN SHALL VERIFY THAT THE MINIMUM
 CLEARANCE OF EACH AWNING IS EIGHT (8) FEET ABOVE GRADE.
  
 4) THE AWNINGS AND CANOPIES SHALL BE CENTERED ABOVE THE
 OPENINGS THAT THEY COVER.
  
 5) THE PALM BEACH OUTLETS DESIGN GUIDELINES PERMIT A
 MAXIMUM PROJECTION OF CANOPIES AND AWNINGS TO BE FOUR
 (4) FEET. THE PLANS SHOW THE CANOPIES CALLED OUT ON
 SHEETS 1 THROUGH 3 OF 4 AT SIX (6) FEET AND ONE AWNING
 SHOWN ON SHEET 4 OF 4 AT SIX (6) FEET.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
2014-08-20 12:38:028/20/14 ZONING SENT TO ES. SG