Plan Review Details - Permit 14080805
Plan Review Stops For Permit 14080805
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-09-05 Cont ID  
Sent By hmoser Date 2014-09-06 Time 10:36 Rev Time 0.00
Received By jwitmer Date 2014-09-05 Time 07:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-08-27 Cont ID  
Sent By jwitmer Date 2014-08-27 Time 06:15 Rev Time 0.00
Received By jwitmer Date 2014-08-26 Time 17:00 Sent To  
Notes
2014-08-26 17:03:06BUILDING PLAN REVIEW
 PERMIT: 14080805
 ADD: 201 NARCISSUS AVE.
 CONT: URBAN BUILDING CONCEPT
 TEL: (561)727-8343
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. AUGUST 27/2014
 ACTION: DENIED
  
 1) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS,
  
 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3A) THE PLANS DO NOT INDICATE IF THIS ENCLOSED SPACE IS
 TO BE AIR CONDITIONED OR NATURALLY VENTILATED? 2010
 FBC-B
 1203.4 NATURAL VENTILATION.
 NATURAL VENTILATION OF AN OCCUPIED SPACE SHALL BE
 THROUGH WINDOWS, DOORS, LOUVERS OR OTHER OPENINGS TO
 THE OUTDOORS. THE OPERATING MECHANISM FOR SUCH OPENINGS
 SHALL BE PROVIDED WITH READY ACCESS SO THAT THE
 OPENINGS ARE READILY CONTROLLABLE BY THE BUILDING
 OCCUPANTS.
 1203.4.1 VENTILATION AREA REQUIRED. THE MINIMUM
 OPENABLE AREA TO THE OUTDOORS SHALL BE 4 PERCENT OF THE
 FLOOR AREA BEING VENTILATED.
  
 3B) IF THIS SPACE IS TO BE AIR CONDITIONED PLEASE
 PROVIDE THE MINIMUM AMOUNTS OF INSULATION REQUIRED TO
 MEET THE REQUIREMENT IN THE 2010 FBC-ENERGY CODE
 502.2.1.2 CEILING INSULATION & 502.2.2.1.1. WALL
 INSULATION ABOVE GRADE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-08-19 Cont ID  
Sent By jwitmer Date 2014-08-27 Time 06:21 Rev Time 0.00
Received By dhayes Date 2014-08-19 Time 07:26 Sent To FIRE
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-08-19 Cont ID  
Sent By pleduc Date 2014-08-19 Time   Rev Time 0.00
Received By pleduc Date 2014-08-19 Time 12:03 Sent To  
Notes
2014-08-19 12:20:10THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 NO EXIT DOOR SHALL BE LOCKED FROM THE EGRESS SIDE. ANY
 AND ALL LOCKING MECHANISMS SHALL BE COMPLAINT WITH
 CHAPTER 7 OF THE FLORIDA FIRE PREVENTION CODE AND
 PRE-APPROVED (PRIOR TO INSTALLATION) BY THE BUREAU OF
 FIRE PREVENTION. CLOSE COORDINATION WITH THE BUREAU OF
 FIRE PREVENTION IS STRONGLY ENCOURAGED TO AVOID
 MISUNDERSTANDINGS, MISINTERPRETATIONS AND DELAYS
 RELATED TO EGRESS REQUIREMENTS.
  
 DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE
 EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. LOCKS,
 IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, TOOL,
 OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE
 EGRESS SIDE.
  
 PER SECTION 7.2.1.5.9, THE LOCK/LATCH RELEASING
 MECHANISM ON ALL DOORS SHALL OPEN THE DOOR WITH NOT
 MORE THAN ONE RELEASING OPERATION. THE RELEASING
 MECHANISM SHALL HAVE AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY OPERATED UNDER ALL LIGHTING CONDITIONS.
 THE RELEASING DEVICE SHOULD BE CAPABLE OF BEING
 OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE TIGHT
 GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST TO
 OPERATE.
  
 A THUMB TURN LOCK IS NOT PERMITTED ON THE MAIN ENTRY
 DOOR(S). IN LIEU OF PANIC HARDWARE, THE MAIN ENTRY IS
 PERMITTED TO BE EQUIPPED WITH A KEYED LOCK WITH
 LOCK/UNLOCK INDICATOR WINDOW AND SIGNAGE STATING THE
 DOOR IS TO REMAIN UNLOCKED DURING BUSINESS HOURS. NO
 OTHER LOCKING OR LATCHING MECHANISMS ARE PERMITTED.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-06 Cont ID  
Sent By hmoser Date 2014-09-06 Time 10:36 Rev Time 0.00
Received By hmoser Date 2014-09-02 Time 09:38 Sent To B
Notes
2014-09-03 09:39:17TO J.W'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-08-27 Cont ID  
Sent By jwitmer Date 2014-08-27 Time 06:21 Rev Time 0.00
Received By jwitmer Date 2014-08-18 Time 07:19 Sent To E
Notes
2014-08-19 07:26:02B10
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-09-18 Cont ID  
Sent By jwitmer Date 2014-09-18 Time 15:37 Rev Time 0.00
Received By jwitmer Date 2014-09-18 Time 15:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-09-06 Cont ID  
Sent By hmoser Date 2014-09-06 Time 10:35 Rev Time 0.00
Received By hmoser Date 2014-09-06 Time 10:01 Sent To  
Notes
2014-09-06 10:35:43PLAN DENIED
  
 1) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS
 2010 FLORIDA ENERGY CODE.
 2) PROVIDE DETAIL FROM A ENGINEER ON THE MOUNTING OF
 THE CONDENSER TO THE WALL. PER SECTION 301.12 WIND
 RESISTANCE
 2010 FBC (M) CUT SHEET WAS NOT PROVIDED.
 3) REFER TO SECTION 606.2.1 SUPPLY AIR SYSTEM 2010 FBC
 (M)
 4) PROVIDE NOA ON WALL MOUNTED LOUVER FOR FRESH AIR.
 5) PROVIDE A SIGNATURE AND LIC. NUMBER OF WHO EVER DREW
 THE PLANS
 PER SECTION 107 FBC 2010
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676