| 2014-08-26 17:03:06 | BUILDING PLAN REVIEW |
| | PERMIT: 14080805 |
| | ADD: 201 NARCISSUS AVE. |
| | CONT: URBAN BUILDING CONCEPT |
| | TEL: (561)727-8343 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. AUGUST 27/2014 |
| | ACTION: DENIED |
| | |
| | 1) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, |
| | |
| | 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 3A) THE PLANS DO NOT INDICATE IF THIS ENCLOSED SPACE IS |
| | TO BE AIR CONDITIONED OR NATURALLY VENTILATED? 2010 |
| | FBC-B |
| | 1203.4 NATURAL VENTILATION. |
| | NATURAL VENTILATION OF AN OCCUPIED SPACE SHALL BE |
| | THROUGH WINDOWS, DOORS, LOUVERS OR OTHER OPENINGS TO |
| | THE OUTDOORS. THE OPERATING MECHANISM FOR SUCH OPENINGS |
| | SHALL BE PROVIDED WITH READY ACCESS SO THAT THE |
| | OPENINGS ARE READILY CONTROLLABLE BY THE BUILDING |
| | OCCUPANTS. |
| | 1203.4.1 VENTILATION AREA REQUIRED. THE MINIMUM |
| | OPENABLE AREA TO THE OUTDOORS SHALL BE 4 PERCENT OF THE |
| | FLOOR AREA BEING VENTILATED. |
| | |
| | 3B) IF THIS SPACE IS TO BE AIR CONDITIONED PLEASE |
| | PROVIDE THE MINIMUM AMOUNTS OF INSULATION REQUIRED TO |
| | MEET THE REQUIREMENT IN THE 2010 FBC-ENERGY CODE |
| | 502.2.1.2 CEILING INSULATION & 502.2.2.1.1. WALL |
| | INSULATION ABOVE GRADE. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |