Plan Review Details - Permit 14080799
Plan Review Stops For Permit 14080799
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-09-10 Cont ID  
Sent By dhayes Date 2014-09-10 Time 12:37 Rev Time 0.00
Received By dhayes Date 2014-09-10 Time 11:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-08-26 Cont ID  
Sent By dhayes Date 2014-08-26 Time 15:36 Rev Time 0.00
Received By dhayes Date 2014-08-26 Time 15:36 Sent To  
Notes
2014-08-26 15:35:59DATE: 8/26/2014
 PROJECT: POTTER
 PERMIT#: 14080799
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 DUPLICATE COMMENTS:
 1) PROVIDE A SITE PLAN TO INDICATE THE LOCATION OF THE
 ELECTRICAL PANEL TO BE CHANGED TO ILLUSTRATE THE
 REQUIRED SERVICE ENTRANCE OVER CURRENT PROTECTIVE
 DEVICE AS PER NEC 230.91 LOCATION.
 REVISE THE RISER DIAGRAM TO INDICATE THE LOCATION OF
 THE MAIN DISCONNECT (SERVICE OCPD)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-08-19 Cont ID  
Sent By dhayes Date 2014-08-19 Time 13:32 Rev Time 0.00
Received By dhayes Date 2014-08-19 Time 13:32 Sent To  
Notes
2014-08-19 13:52:31DATE: 8/19/2014
 PROJECT: POTTER
 PERMIT#: 14080799
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) THE GROUNDING ELECTRODE CONDUCTOR INDICATED ON THE
 PLANS IS UNDERSIZED. PRODIDE ADAQUATE GEC SIZE PER NEC
 250.66.
  
 2) PROVIDE A SITE PLAN TO INDICATE THE LOCATION OF THE
 ELECTRICAL PANEL TO BE CHANGED TO ILLUSTRATE THE
 REQUIRED SERVICE ENTRANCE OVER CURRENT PROTECTIVE
 DEVICE AS PER NEC 230.91 LOCATION.
 REVISE THE RISER DIAGRAM TO INDICATE THE LOCATION OF
 THE MAIN DISCONNECT (SERVICE OCPD)
  
 3) REVISE THE VALUATION OF THE PROJECT INDICATED ON THE
 PERMIT APPLICATION AND PROVIDE SUPPORTING DOCUMENTATION
 FOR THE VALUATION OF THE PROJECT ON THE APPLICATION.
 INCLUDE ALL LABOR MATERIAL, SUB CONTRACTS ASSOCIATED
 UTLITY COSTS OVERHEAD PROFIT ETC... FBC WPB AMENDMENTS.
 SECTION 109.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By dhayes Date 2014-08-29 Time 11:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-08-26 Cont ID  
Sent By dhayes Date 2014-08-26 Time 15:36 Rev Time 0.00
Received By dhayes Date 2014-08-22 Time 08:45 Sent To  
Notes
2014-08-25 08:46:01RE-SUBMITTAL SENT TO DAVID HAYES' DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-08-19 Cont ID  
Sent By dhayes Date 2014-08-19 Time 13:32 Rev Time 0.00
Received By dhayes Date 2014-08-18 Time 15:01 Sent To  
Notes
2014-08-18 15:01:41ROUTED TO ELECTRICAL $5000 & UNDER