Plan Review Details - Permit 14080649
| Plan Review Stops For Permit 14080649 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2014-09-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2014-09-26 |
Time |
16:18 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2014-09-26 |
Time |
16:18 |
Sent To |
|
|
| Notes |
| 2014-09-26 16:21:44 | ****PROVISO**** | | | ****ISSUED AT CONTRACTOR'S RISK**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | ORIGINAL SIGNED, SEALED, DATED CALCS FOR THE FIXTURES | | | REQUIRED. PROVIDE AT INSPECTION. | | | | | | SUBJECT TO FIELD INSPECTOR'S DISCRETION, A REVISION MAY | | | BE REQUIRED. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2014-09-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2014-09-09 |
Time |
14:18 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2014-09-09 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2014-09-09 14:19:43 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. PLANS SHOW DESIGN CRITERIA AS EXPOSURE B; THIS IS | | | LOCATED IN EXPOSURE C, FBC 1609. PLEASE REVISE. | | | | | | IT IS ACKNOWLEDGED THAT CALCS WERE TO EXPOSURE C. | | | | | | 2. PROVIDE CALCS FOR THE LIGHT FIXTURE, FBC 1609. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2014-09-21 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-09-21 |
Time |
12:47 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-09-21 |
Time |
12:39 |
Sent To |
B |
|
| Notes |
| 2014-09-21 13:48:53 | TO S.H'S DESK | | | | | | | | | | | 2014-09-21 13:48:00 | DATE: 9/21/2014 | | | PROJECT: SOUTHWIND PLAZA | | | PERMIT#: 14080649 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 2ND ELECTRICAL PLAN REVIEW | | | ACTION: PROVISO | | | | | | 1) INSTALLATION SHALL COMPLY WITH THE PROVISIONS OF THE | | | NEC ARTICLE 410 PART XIII AND THE FBC - ENERGY CHAPTER | | | 5 SECTION 505.2.4 EXTERIOR LIGHTING CONTROLS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: | | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | | SHEETS FOR COMPARATIVE REVIEW. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2014-08-22 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-08-22 |
Time |
15:17 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-08-22 |
Time |
15:01 |
Sent To |
Z |
|
| Notes |
| 2014-08-22 15:17:18 | DATE: 8/22/2014 | | | PROJECT: SOWTHWIND PLAZA | | | PERMIT#: 14080649 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | 1) PROVIDE FIXTURE MANUFACTURER SPECIFICATIONS ON POLE | | | HEADS AND SPECIFY THE NUMBER OF HEADS PER POLE. | | | 2) SPECIFY WIRING MEATHODS AND INCLUDE A DETAIL FOR | | | RECONNECTING THE NEW POLES IN THE NEW LOCATIONS TO THE | | | EXISTING CIRCUITRY. INCLUDE A DETAIL ON GROUNDING. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: | | | HTTP://WPB.ORG/DEVELOPMENT | | | /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM | | | ITTAL_FORM_04132010.PDF | | | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | | SHEETS FOR COMPARATIVE REVIEW. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-09-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2014-09-26 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2014-09-19 |
Time |
15:41 |
Sent To |
|
|
| Notes |
| 2014-09-19 15:42:05 | TO DAH DESK | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-09-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2014-09-09 |
Time |
14:19 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2014-08-14 |
Time |
12:02 |
Sent To |
|
|
| Notes |
| 2014-08-14 12:03:11 | ROUTED TO ELECTRIC |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2014-08-28 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2014-08-28 |
Time |
15:58 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
B |
|
| Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy