Plan Review Details - Permit 14080611
Plan Review Stops For Permit 14080611
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-08-27 Cont ID  
Sent By shill Date 2014-08-27 Time 18:53 Rev Time 0.00
Received By shill Date 2014-08-27 Time 18:50 Sent To  
Notes
2014-08-27 18:53:25***PROVISO***
 ***ISSUED AT CONTRACTOR'S RISK****
  
 FBC R310, FBC EB 604.1. FOR SLEEPING ROOM WINDOWS, THE
 CLEAR EMERGENCY ESCAPE AND RESCUE OPENING CANNOT BE
 REDUCED BY MORE THAN 5%.
  
 A 3030 WINDOW IS SHOWN ON THE FLOOR PLAN. IF THIS
 WINDOW IS LOCATED IN A SLEEPING ROOM, SUBMIT A REVISION
 WITH CALCULATIONS TO SHOW THAT THE CLEAR OPENING IS NOT
 REDUCED BY MORE THAN 5%.
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-08-27 Cont ID  
Sent By shill Date 2014-08-27 Time 18:53 Rev Time 0.00
Received By shill Date 2014-08-14 Time 12:21 Sent To  
Notes
2014-08-14 12:22:14ROUTED TO BLDG $5000 & UNDER