Plan Review Details - Permit 14080586
Plan Review Stops For Permit 14080586
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-11-05 Cont ID  
Sent By jgomez Date 2014-11-05 Time 18:01 Rev Time 0.00
Received By jgomez Date 2014-11-05 Time 18:00 Sent To  
Notes
2014-11-05 18:03:20 
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-10-24 Cont ID  
Sent By jgomez Date 2014-10-24 Time 16:43 Rev Time 0.00
Received By jgomez Date 2014-10-24 Time 16:43 Sent To  
Notes
2014-10-24 16:54:01RESIDENTIAL (R3) ADDITION/ALTERATION, SECOND BUILDING
 REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- NEED TO PROVIDE TWO COMPLETE SET OF DRAWINGS. ONE
 SET OF DRAWINGS SUBMITTED IS MISSING THE STRUCTURAL
 DRAWINGS S1 THRU S4. SEC. 107.1 CITY AMENDMENTS TO FBC.
  
 2- PROVIDE 2 COPIES OF THE ESR 1826 ICYNENE EVALUATION
 REPORT TO VERIFY COMPLIANCE WITH SEC. R316.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR ALL SIMPSON STRUCTURAL CONNECTORS
 SPECIFIED ON PLANS AND DETAILS. PROVIDE ONLY THE
 PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING THE
 SPECIFIED CONNECTOR OR WRITE DOWN THE PRODUCT APPROVAL
 NUMBER NEXT TO EACH SPECIFIED CONNECTOR. (REPEAT
 COMMENT).
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-09-11 Cont ID  
Sent By jgomez Date 2014-09-11 Time 18:35 Rev Time 0.00
Received By jgomez Date 2014-09-11 Time 18:35 Sent To  
Notes
2014-09-11 19:00:07RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- BOTH SET OF PLANS SUBMITTED NEED TO BE SIGNED AND
 SEALED BY THE ARCHITECT OF RECORD AS REQUIRED BY
 CHAPTER 481 FLORIDA STATUTES.
 ***NOTE: MAKE SURE BOTH SETS ARE THE SAME. ONE SET
 SUBMITTED WAS DATED 05/15/2014 AND THE OTHER ONE WAS
 DATED 07/01/2014. COORDINATE THE DRAWINGS BEFORE
 RE-SUBMITTAL TO AVOID CONFLICTS AND DELAYS.
  
 2- BRING PLANS TO PALM BEACH COUNTY TO VERIFY IF IMPACT
 FEES ARE DUE. BRING BACK COUNTY STAMPED PLANS AND COPY
 OF PAID RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY
 IMPACT FEE ORDINANCE OF THE LAND DEVELOPMENT CODE.
  
 3- SHEET SP-1:
 A) NOTE REGARDING THE EXISTING BUILDING ALTERATION
 LEVEL IS INCOMPLETE. COMPLETE THE ALTERATION LEVEL
 INFORMATION AND ALSO KEEP IN MIND THAT THIS IS AN
 ADDITION ALSO. SEC. 401.4 OF 2010 FBC-EXISTING BUILDING
  
 B) FIRE DEPARTMENT NOTES AND REFERENCED CODE SECTIONS
 DON'T APPLY TO SINGLE FAMILY RESIDENCES. THESE NOTES
 ARE NOT NEED IT. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 4- NEW MASTER BEDROOM EGRESS WINDOWS: PROVIDE
 MANUFACTURERS CUT SHEETS SHOWING SIZES SPECIFIED IN
 PLANS TO VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS
 OF SEC. R310 OF 2010 FBC-RESIDENTIAL.
  
 5- PROVIDE ICYNENE EVALUATION REPORT TO SHOW COMPLIANCE
 WITH SEC. R316.
  
 6- SHEET S4:
 A) PROVIDE COMPLETE SPECIFICATIONS FOR THE TYPE OF
 SECOND FLOOR SHEATHING AND ROOF SHEATHING. THERE IS NO
 INFORMATION ON PLANS. SEC. R301 OF 2010
 FBC-RESIDENTIAL.
  
 B) ROOF SHEATHING NAILS NEED TO BE RING SHANK NAILS AS
 REQUIRED BY SEC. R803.2.3.1 OF 2010 FBC-RESIDENTIAL.
 CLEARLY INDICATE THAT NAILS NEED TO BE RING SHANK
 NAILS.
  
 7- A) DESIGN PROFESSIONAL TO CLEARLY SPECIFY ON PLANS
 TYPE OF ROOFING SYSTEM, MATERIALS AND FASTENING AS
 REQUIRED BY SEC. 107.2.1.2 OF CITY AMENDMENTS TO FBC.
 (NOTE: IF USING FOAM ADHESIVE FOR TILE INSTALLATION,
 THEN, CLEARLY IDENTIFY ON TABLE 3A-2 OF FLORIDA PRODUCT
 APPROVAL FL7804-R7 SUBMITTED WHICH ADHESIVE IS GOING TO
 BE USED TO VERIFY COMPLIANCE WITH THE ATTACHMENT
 RESISTANCE).
  
 B) PRODUCT APPROVAL FL14317-R5 ROOFING UNDERLAYMENT
 SUBMITTED MAY NOT BE USED. DESIGN PRESSURES SHOWN ON
 LIMITATION 5.5.2 THRU 5.5.2.3 DON'T MEET THE REQUIRED
 DESIGN PRESSURES OF SEC. R301. NEED TO USE ANOTHER
 PRODUCT. AND, COORDINATE WITH ITEMS #6(C) AND #7(A)
 ABOVE.
  
 C) PRODUCT APPROVAL FL11915-R3 SUBMITTED. CLEARLY
 SPECIFY WHICH SPECIFIC UNDERLAYMENT IS GOING TO BE
 USED. COORDINATE WITH DESIGN PROFESSIONAL
 SPECIFICATIONS REQUIRED BY ITEM # 7(A) ABOVE.
  
 8- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR THE INSTALLATION OF THE ROUND WINDOW AS SPECIFIED
 ON PLANS. SEC. R612.10.2 OF 2010 FBC-RESIDENTIAL.
  
 9- PROVIDE PROVIDE PRODUCT APPROVAL (2 COPIES) AS
 REQUIRED BY DCA RULE 9N-3 FOR:
 A) ROOF TILE UNDERLAYMENT IF USING SELF ADHERING
 UNDERLAYMENT. FLORIDA PRODUCT APPROVAL FL14317-R5
 SUBMITTED CAN'T BE USED. SEE ITEM #7(B) ABOVE.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON ALL
 DETAILS/ SECTIONS AND SPECIFICATIONS. (NOTE: PROVIDE
 ONLY THE PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING
 THE CONNECTOR OR WRITE DOWN THE PRODUCT APPROVAL NUMBER
 NEXT TO THE SPECIFIED STRUCTURAL CONNECTORS IN ALL
 DETAILS).
  
 10- DESIGN PROFESSIONAL OF RECORD TO REVIEW AND APPROVE
 IN WRITING (NOT SIGNING AND SEALING) ALL PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
 TO FBC.
  
 ***NOTES:
 *** PROVIDE RESPONSE LETTER ADDRESSING EACH COMMENT TO
 EXPEDITE THE REVIEW PROCESS.
 *** PLEASE REMOVE AND REPLACE ANY REVISED SHEET WHEN
 RE-SUBMITTING TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-11-03 Cont ID  
Sent By dhayes Date 2014-11-03 Time 08:47 Rev Time 0.00
Received By dhayes Date 2014-11-03 Time 08:47 Sent To B
Notes
2014-11-03 12:55:22TO JG'S DESK.
  
  
2014-11-03 12:14:23DATE: 11/3/2014
 PROJECT: BARCELONA RD RENNOVATION
 PERMIT#: 14080856
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 3RD ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) INDICATE THE LOCATION FOR THE ELECTRICAL PANELS.
 2010 WPB AMENDMENTS TO THE FBC107.3.5
  
 2) REVISE PANEL SCHEDULE "A" TO CORRECT PROBABLE TYPO
 FOR "KITCHEN" CIRCUIT #23 INDICATING A SINGLE POLE
 60AMP OCPD WITH #6 WIRE.
 WHICH 110V 1POLE CIRCUIT IS IDENTIFIED AS "KITCHEN"?
 PLEASE CLARIFY BY INDICATING CIRCUIT NUMBERS ON THE
 FLOOR PLAN TO CORRESPOND TO CIRCUIT NUMBERS ON THE
 PANEL SCHEDULES.
  
 3) REVISE THE RISER DIAGRAM AN VERIFY THE METAL NATURAL
 GAS PIPING BE BONDED IN ACCORDANCE WITH THE NEC
 250.104(B)
  
 4) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 5) VERIFY LUMINAIRES AND EXHAUST FANS LOCATED IN THE
 BATHROOMS OVER BATHTUB OR SHOWER SHALL BE IN ACCORDANCE
 WITH THE NEC 410.10(D) BATHTUB AND SHOWER, AND
 NEC110.3(B) LISTING AND LABELING
  
 6) VERIFY ALL RECEPTACLE OUTLETS INSTALLED THROUGHOUT
 THE HOUSE SHALL BE INSTALLED IN COMPLIANCE WITH NEC
 210.52(A)(1) SHALL BE INSTALLED SUCH THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY WALL
 SPACE IS MORE THAN (6 FT) FROM A RECEPTACLE OUTLET.
  
 7) A GFI OUTLET SHALL BE INSTALLED AT EACH COUNTERTOP
 SPACE THAT IS 12" OR WIDER. GFI OUTLETS SHALL BE
 INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE
 THAN 24" HORIZONTALLY FROM AN OUTLET IN THAT SPACE. NEC
 210.52(C)(1). THERE APPEAR TO BE ADDITIONAL OUTLETS
 REQUIRED AT COUNTERTOP WALL SPACE AREAS IN THE KITCHEN.
  
 8) ALL 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES
 INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8)
 SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION
 FOR PERSONNEL. ALL OUTLETS IN THE KITCHEN, BATHROOM,
 OUTDOORS, LAUNDRY, UTILITY, AND WET BAR SINKS SHALL BE
 GFCI PROTECTED. NEC 210.8.
  
 9) METAL FRAMING MEMBERS SHALL BE BONDED TO THE
 EQUIPMENT GROUNDING CONDUCTOR FOR THE CIRCUIT THAT MAY
 ENERGIZE THE FRAMING AND BE SIZED IN ACCORDANCE WITH
 THE NEC TABLE 250.122. FOR THE PURPOSE OF THIS SECTION,
 A GROUNDED METAL OUTLET BOX ATTACHED TO THE FRAMING
 SHALL BE PERMITTED. FBC 2704
  
 SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR SECURITY, CCTV, STUCTURED CABLING,
 NETWORK, AUDIO/VIDEO, GENERATOR, SWIMMING POOL,
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-10-21 Cont ID  
Sent By dhayes Date 2014-10-21 Time 07:25 Rev Time 0.00
Received By dhayes Date 2014-10-21 Time 07:25 Sent To  
Notes
2014-10-09 10:21:39DATE: 10/21/2014
 PROJECT: BARCELONA RD RENNOVATION
 PERMIT#: 14080856
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) REVISE THE RISER DIAGRAM TO INDICATE A LOGICAL
 DESIGN UTILIZING FULL SIZE SERVICE ENTRANCE CONDUCTORS
 FEEDING PANELS "A" AND "B" NEC 310.15.(B)(6) .
  
 2) REVISE THE RISER DIAGRAM TO INCLUDE AN EQUIPMENT
 GROUNDING CONDUCTOR IN THE FEEDER TO THE GARAGE PANEL.
 NEC 250.122
  
 3) REVISE THE PANEL "A" SCHEDULE TO TO CORRECT PROBABLE
 TYPO FOR KITCHEN CIRCUIT #23 INDICATING A 60AMP OCPD
 WITH #12 WIRE.
  
 4) CLARIFY THE TYPE, RATING, SIZE AND USE FOR THE
 GUTTER INDICATED ABOVE PANELS "A" AND "B" ON THE RISER
 DIAGRAM. WPB AMENDMENTS TO THE FBC 107.3.2
  
 5) VERIFY LUMINAIRES IN CLOTHES CLOSETS SHALL BE
 INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF THE NEC
 410.16(A) AND (B).
  
 6) VERIFY ALL RECEPACLE OUTLETS INSTALLED THROUGHOUT
 SHALL BE IN COMPLIANCE WITH NEC 210.52(A)(1) SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 1.8
 M (6 FT) FROM A RECEPTACLE OUTLET.
  
 7) INDICATE THE REQUIRED WORKING CLEARANCES FOR THE A/C
 DISCONNECTS. SEE NEC 110.26
 SUFFICIENT ACCESS AND WORKING SPACE SHALL BE PROVIDED
 AND MAINTAINED ABOUT ALL ELECTRICAL EQUIPMENT TO PERMIT
 READY AND SAFE OPERATION AND MAINTENANCE OF SUCH
 EQUIPMENT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-09-17 Cont ID  
Sent By dhayes Date 2014-09-17 Time 15:24 Rev Time 0.00
Received By dhayes Date 2014-09-17 Time 15:18 Sent To  
Notes
2014-09-17 17:04:07DATE: 9/17/2014
 PROJECT: BARCELONA RD RENNOVATION
 PERMIT#: 14080856
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) ADDITIONAL RECEPTACLES ARE REQUIRED. ADD RECEPTACLES
 SO THAT NO WALL SPACE IS MORE THAN 6 FEET FROM A
 RECEPTACLE AND ALL WALL SPACES MORE THAN 2 FEET IN
 WIDTH HAVE A RECEPTACLE. NEC 210.52(A)(1)
  
 2) AT LEAST ONE RECEPTACLE SHALL BE INSTALLED AT EACH
 ISLAND COUNTERTOP SPACE WITH ALONG DIMENSION OF 600 MM
 (24 IN.) OR GREATER AND A SHORT DIMENSION OF 300 MM (12
 IN.) OR GREATER.NEC 210.52(C)(2)
  
 3) KITCHEN COUNTER TOP RECEPTACLES SHALL BE SUPPLIED BY
 NO FEWER THAN TWO SMALL APPLIANCE BRANCH CIRCUITS. NEC
 210.52 (B)(3)
  
 4) ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI
 PROTECTED. NEC 210.12 NEW RECEPTACLES MUST BE TAMPER
 RESISTANT. NEC 406.11
  
 5) FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET ACCESSIBLE WHILE STANDING AT
 GRADE LEVEL AND LOCATED NOT MORE THAN 2.0 M (61.2 FT)
 ABOVE GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF
 THE DWELLING. NEC 210.52(E)(3)
  
 6) PROVIDE A LIGHTING OUTLET AND SWITCH FOR ATTIC
 ACCESS. 210.70(A)(3)
  
 7) INDICATE THE LOCATION FOR THE ELECTRICAL PANELS.
  
 8) INDICATE LOCATION OF A/C CONDENSING UNITS AND THE
 ELECTRICAL CIRCUITS AND REQUIRED DISCONNECTS.
  
 9) ONE 125VOLT, SINGLE-PHASE, 15 OR 20AMP GFI
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING,
 AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND
 WITHIN 25FT OF THE HEATING, AIR-CONDITIONING, AND
 REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET SHALL
 NOT BE CONNECTED TO THE LOAD SIDE OF THE EQUIPMENT
 DISCONNECTING MEANS. NEC 210.63 SEE 210.8(A)(3),
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status N Date 2014-10-27 Cont ID  
Sent By fmittner Date 2014-10-27 Time 11:46 Rev Time 0.00
Received By jgomez Date   Time   Sent To  
Notes
2014-10-27 11:46:47ALREADY APPROVED 8/13/14. JG.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2014-08-13 Cont ID  
Sent By fmittner Date 2014-08-13 Time 09:27 Rev Time 0.00
Received By fmittner Date 2014-08-13 Time 09:27 Sent To  
Notes
2014-08-13 09:28:19PASSED BASED ON PREVIOUS APPROVAL. SPOKE TO OWNER WHO
 INTENDS TO SUBMIT FOR A NEW/DIFFERENT WINDOW PRODUCT.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-11-05 Cont ID  
Sent By jgomez Date 2014-11-05 Time 18:03 Rev Time 0.00
Received By jgomez Date 2014-10-31 Time 06:48 Sent To  
Notes
2014-11-01 06:44:35GAVE TO DHAYES

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-10-27 Cont ID  
Sent By jgomez Date 2014-10-27 Time 11:46 Rev Time 0.00
Received By jgomez Date 2014-10-07 Time 10:01 Sent To  
Notes
2014-10-09 10:03:08R02

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-17 Cont ID  
Sent By dhayes Date 2014-09-17 Time 17:06 Rev Time 0.00
Received By dhayes Date 2014-08-13 Time 18:29 Sent To  
Notes
2014-08-14 18:56:188/14 EXPEDITED REQUEST SUBMITTED
  
2014-08-14 18:35:45R10

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2014-10-24 Cont ID  
Sent By jgomez Date 2014-10-24 Time 17:28 Rev Time 0.00
Received By jgomez Date 2014-10-24 Time 17:28 Sent To  
Notes
2014-10-24 17:28:54NO FEES DUE. MU-14-021078. JG.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-09-12 Cont ID  
Sent By jgomez Date 2014-09-12 Time 14:04 Rev Time 0.00
Received By jgomez Date 2014-09-12 Time 14:03 Sent To  
Notes
2014-09-12 14:04:201- BRING PLANS TO PALM BEACH COUNTY TO VERIFY IF IMPACT
 FEES ARE DUE. BRING BACK COUNTY STAMPED PLANS AND COPY
 OF PAID RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY
 IMPACT FEE ORDINANCE OF THE LAND DEVELOPMENT CODE.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-10-27 Cont ID  
Sent By HMOSER Date 2014-10-27 Time 11:33 Rev Time 0.00
Received By jgomez Date 2014-10-27 Time 11:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2014-08-20 Time   Rev Time 0.25
Received By   Date   Time   Sent To  
Notes
2014-08-20 15:37:36PLEASE PROVIDE ENERGY SHEETS FOR ALL NEW SPACES

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-10-18 Cont ID  
Sent By tklarge Date 2014-10-18 Time 05:37 Rev Time 0.00
Received By tklarge Date 2014-10-18 Time 05:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-09-12 Cont ID  
Sent By tklarge Date 2014-09-01 Time 12:04 Rev Time 0.00
Received By tklarge Date 2014-09-01 Time 08:58 Sent To  
Notes
2014-09-01 09:00:501) SUBMIT SANITARY & WATER RISER DIAGRAMS FOR ALL NEW
 WORK TO BE DONE. WPB ADMIN. AMEND. TO 2010 FBC
 SEC.107.2.1.
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2014-09-12 Cont ID  
Sent By jgomez Date 2014-09-12 Time 14:04 Rev Time 0.00
Received By jgomez Date 2014-09-12 Time 14:04 Sent To  
Notes
2014-09-12 14:05:511- ROOFING TILE FL7804-R7.
 2- ROOFING TILE ADHESIVE FL6332-R4.
 3- ROOFING UNDERLAYMENT FL11915-R3.
  

Review Stop Z ZONING
Rev No 2 Status N Date 2014-10-27 Cont ID  
Sent By fmitner Date 2014-10-27 Time 11:45 Rev Time 0.00
Received By jgomez Date   Time   Sent To  
Notes
2014-10-27 11:46:01ALREADY APPROVED 8/13/14. JG.

Review Stop Z ZONING
Rev No 1 Status P Date 2014-08-13 Cont ID  
Sent By fmittner Date 2014-08-13 Time 09:28 Rev Time 0.00
Received By fmittner Date 2014-08-13 Time 09:28 Sent To  
Notes
***NONE***