Plan Review Details - Permit 14080538
Plan Review Stops For Permit 14080538
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-09-15 Cont ID  
Sent By jwitmer Date 2014-09-15 Time 16:20 Rev Time 0.00
Received By jwitmer Date 2014-09-15 Time 16:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-09-15 Cont ID  
Sent By jwitmer Date 2014-09-15 Time 12:03 Rev Time 0.00
Received By jwitmer Date 2014-09-15 Time 12:03 Sent To  
Notes
2014-09-15 12:05:09BUILDING PLAN REVIEW
 PERMIT: 14080538
 ADD: 1920 PALM BEACH LAKES SUITE #214-215
 CONT: PROFESSIONAL FINISHES INC
 TEL: (561)746-1517
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. SEPT.15/ 2014
 ACTION: DENIED
  
 1) 2010 F ACCESSIBILITY CODE 706.1 GENERAL. A BUILDING,
 FACILITY, OR ELEMENT THAT IS ALTERED SHALL COMPLY WITH
 THE PROVISIONS OF THE FLORIDA BUILDING CODE,
 ACCESSIBILITY.
 THE PERMIT APPLICATION INDICATES THE BUILDING VALUATION
 OF $5800.00, 20% OF THIS FIGURE OR $1160.00 NEEDS TO GO
 TOWARDS ACCESSIBLE UPGRADES TO THIS SUITE. PLEASE
 REVIEW IN ORDER WHAT THE UPGRADES ARE REQUIRED WITH
 $1,160.00 OF FUNDS.
 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 IF THE FRONT ENTRY IS ACCESSIBLE THEN THE 2ND AREA OF
 ALTERATIONS TO ALTERED AREAS. THE DOORS TO THE BUSINESS
 AREA AND OFFICE BOTH ARE NOT
 2'-10" DOORS NOR DOES EITHER OF THE DOORS HAVE 18
 INCHES ON THE LATCH SIDE OF THE DOOR. SEE FL ACCESS
 TABLE 404.2.4.1.
  
 THE NEXT AREA OF ACCESSIBILITY UPGRADES WOULD BE TO
 MAKE A 2'-10" RESTROOM AND BACKING REQUIREMENTS AND
 GRAB BARS, PLEASE PROVIDE A COST BREAK DOWN OF WHAT
 WORK THAT CAN BE DONE FOR THE $1,160.00 AND AND ADJUST
 THE PLANS TO CORRESPOND TO THE ACCESSIBLE UPGRADE LIST.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-08-25 Cont ID  
Sent By jwitmer Date 2014-08-25 Time 16:55 Rev Time 0.00
Received By jwitmer Date 2014-08-25 Time 16:37 Sent To  
Notes
2014-08-25 16:55:01BUILDING PLAN REVIEW
 PERMIT: 14080538
 ADD: 1920 PALM BEACH LAKES SUITE #214-215
 CONT: PROFESSIONAL FINISHES INC
 TEL: (561)746-1517
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. AUG. 25/2014
 ACTION: DENIED
  
 1) 2010 F ACCESSIBILITY CODE 706.1 GENERAL. A BUILDING,
 FACILITY, OR ELEMENT THAT IS ALTERED SHALL COMPLY WITH
 THE PROVISIONS OF THE FLORIDA BUILDING CODE,
 ACCESSIBILITY.
 THE PERMIT APPLICATION INDICATES THE BUILDING VALUATION
 OF $5800.00, 20% OF THIS FIGURE OR $1160.00 NEEDS TO GO
 TOWARDS ACCESSIBLE UPGRADES TO THIS SUITE. PLEASE
 REVIEW IN ORDER WHAT THE UPGRADES ARE REQUIRED WITH
 $1,160.00 OF FUNDS.
 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 IF THE FRONT ENTRY IS ACCESSIBLE THEN THE 2ND AREA OF
 ALTERATIONS TO ALTERED AREAS. THE DOORS TO THE BUSINESS
 AREA AND OFFICE BOTH ARE NOT
 2'-10" DOORS NOR DOES EITHER OF THE DOORS HAVE 18
 INCHES ON THE LATCH SIDE OF THE DOOR. SEE FL ACCESS
 TABLE 404.2.4.1.
  
 THE NEXT AREA OF ACCESSIBILITY UPGRADES WOULD BE TO
 MAKE A 2'-10" RESTROOM AND BACKING REQUIREMENTS AND
 GRAB BARS, PLEASE PROVIDE A COST BREAK DOWN OF WHAT
 WORK THAT CAN BE DONE FOR THE $1,160.00 AND AND ADJUST
 THE PLANS TO CORRESPOND TO THE ACCESSIBLE UPGRADE LIST.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-08-27 Cont ID  
Sent By rlecky Date 2014-08-27 Time 14:51 Rev Time 0.00
Received By rlecky Date 2014-08-27 Time 14:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-08-18 Cont ID  
Sent By scaldero Date 2014-08-18 Time 11:00 Rev Time 0.00
Received By scaldero Date 2014-08-18 Time 10:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-08-27 Cont ID  
Sent By rlecky Date 2014-08-27 Time 14:51 Rev Time 0.00
Received By rlecky Date 2014-08-12 Time 18:42 Sent To  
Notes
2014-08-12 18:44:27B19