Plan Review Details - Permit 14080395
Plan Review Stops For Permit 14080395
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2014-08-29 Cont ID  
Sent By shill Date 2014-08-29 Time 13:27 Rev Time 0.00
Received By shill Date 2014-08-29 Time 13:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-08-22 Cont ID  
Sent By shill Date 2014-08-22 Time 14:43 Rev Time 0.00
Received By shill Date 2014-08-22 Time 14:43 Sent To  
Notes
2014-08-22 15:06:49****PROVISO****
 ****REVISION REQUIRED****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 THE PRODUCT APPROVALS SUBMITTED WERE ALREADY SUBMITTED
 WITH THE MASTER. THEREFORE, THE PRODUCT APPROVALS
 SUBMITTED WITH THIS APPLICATION WILL NOT BE STAMPED.
  
 ENGINEERING PREPARED BY TURQUOISE ENGINEERING LLC DATED
 8/18/2014 REFERS TO TABLE 1D, SYSTEM E, SYSTEM W9, PG
 6/16. ASSEMBLY CIRCLED ON THE PRODUCT APPROVAL IS A
 DIFFERENT ASSEMBLY, AND THE PRODUCT APPROVAL IS 24
 PAGES. ENHANCED FASTENING PROPOSED APPEARS COMPLIANT,
 BUT ENGINEERING SHOULD REFER TO THE CORRECT ASSEMBLY
 AND PAGE NUMBER. REVISE ENGINEERING AND SUBMIT AS A
 REVISION WITH FEES.
  
 ALTERNATIVELY, APPLICANT CAN RESUBMIT.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-08-21 Cont ID  
Sent By shill Date 2014-08-21 Time 18:03 Rev Time 0.00
Received By shill Date 2014-08-21 Time 18:03 Sent To  
Notes
2014-08-21 18:05:04****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. REVIEW CANNOT BE DONE AT THIS TIME. THE FIRST
 SUBMITTAL HAS BEEN SENT TO ZONING FOR REVIEW.
 CONTRACTOR SHOULD WAIT UNTIL ALL REVIEWS ARE COMPLETE
 BEFORE RESUBMITTING.
  
 PLEASE ADVISE WHEN ALL REVIEWS FROM THE FIRST SUBMITTAL
 ARE COMPLETE (ZONING).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-08-13 Cont ID  
Sent By shill Date 2014-08-13 Time 15:12 Rev Time 0.00
Received By shill Date 2014-08-13 Time 15:12 Sent To  
Notes
2014-08-13 15:37:58****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. ON THE METAL ROOFING PRODUCT APPROVAL, INDICATE
 METHOD OF FASTENING PROPOSED FOR ZONES 1, 2, AND 3, FBC
 1609.
  
 2. THE ASSEMBLY PROPOSED FOR THE FLAT DECK HAS A DESIGN
 PRESSURE LIMITATION OF -52.5. THIS DOES NOT MEET THE
 DESIGN PRESSURES FOR ZONES 2 & 3. SEE NOTE 8 ON PAGE 2;
 EITHER PROVIDE ENGINEERING FOR ENHANCED FASTENING OR
 SELECT A DIFFERENT ASSEMBLY IF ONE IS AVAILABLE WHICH
 MEETS THE MINIMUM DESIGN PRESSURES. SEE COMMENT # 3.
  
 3. PROVIDE THE BUILDING HEIGHT SO DESIGN PRESSURES CAN
 BE DETERMINED OR CONFIRMED (IF PROVIDED BY CONTRACTOR
 UPON RESUBMITTAL), FBC 1609.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-08-22 Cont ID  
Sent By shill Date 2014-08-22 Time 16:00 Rev Time 0.00
Received By shill Date 2014-08-21 Time 18:02 Sent To  
Notes
2014-08-21 18:03:08TO SH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-08-29 Cont ID  
Sent By shill Date 2014-08-13 Time 13:26 Rev Time 0.00
Received By shill Date 2014-08-13 Time 15:12 Sent To  
Notes
2014-08-13 15:12:42TO ZONING
 (DMP)
  

Review Stop Z ZONING
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2014-08-13 15:54:328/13/14 ZONING SENT TO AA. SG