| 2014-09-16 11:02:38 | DATE: 9/16/2014 |
| | PROJECT: BATHROOM AND KITCHEN RENNOVATION |
| | PERMIT#: 14080339 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) FLOOR PLAN TO BE REVISED TO SHOW ALL REQUIRED |
| | RECEPTACLE OUTLETS IN THE KITCHEN AND BATH. BATHROOM |
| | BRANCH CIRCUITS IN ADDITION TO THE NUMBER OF BRANCH |
| | CIRCUITS REQUIRED BY OTHER PARTS OF THIS SECTION, AT |
| | LEAST ONE 20-AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO |
| | SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH CIRCUITS |
| | SHALL HAVE NO OTHER OUTLETS. PLEASE INDICATE COMPLIANCE |
| | WITH THE NEC ARTICLE 210.11(C)(3) |
| | |
| | 2) KITCHEN COUNTER TOP RECEPTACLES SHALL BE SUPPLIED BY |
| | NO FEWER THAN TWO SMALL APPLIANCE BRANCH CIRCUITS. NEC |
| | 210.52(B)(3) AT LEAST ONE RECEPTACLE OUTLET SHALL BE |
| | INSTALLED AT EACH ISLAND COUNTERTOP SPACE WITH A LONG |
| | DIMENSION OF 24" OR GREATER AND A SHORT DIMENSION OF |
| | 12" OR GREATER. NEC 210.52(C)(2) |
| | |
| | 3) INDICATE OR VERIFY THE INSTALLATION OF SMOKE AND CO |
| | DETECTORS AT ALL SLEEPING ROOMS. WHEN ALTERATIONS, |
| | REPAIRS, OR ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN |
| | ONE OR MORE SLEEPING ROOMS ARE ADDED OR CREATED IN |
| | EXISTING DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL |
| | BE EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR |
| | NEW DWELLINGS. FBC-RESIDENTIAL 314 AND 315. REVISE PLAN |
| | TO INDICATE OR VERIFY THE REQUIRED SMOKE AND CO |
| | DETECTORS. |
| | |
| | 4) ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI |
| | PROTECTED. NEC 210.12 REVISE ACCORDINGLY |
| | |
| | 5) NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 |
| | REVISE ACCORDINGLY |
| | |
| | 6) OUTLET BOXES OR OUTLET BOX SYSTEMS USED AS THE SOLE |
| | SUPPORT OF A CEILING-SUSPENDED (PADDLE) FAN SHALL BE |
| | LISTED, SHALL BE MARKED BY THEIR MANUFACTURER AS |
| | SUITABLE FOR THIS PURPOSE, AND SHALL NOT SUPPORT |
| | CEILING-SUSPENDED (PADDLE) FANS THAT WEIGH MORE THAN 32 |
| | KG (70 LB). FOR OUTLET BOXES OR OUTLET BOX SYSTEMS |
| | DESIGNED TO SUPPORT CEILING-SUSPENDED (PADDLE) FANS |
| | THAT WEIGH MORE THAN 16 KG (35 LB), THE REQUIRED |
| | MARKING SHALL INCLUDE THE MAXIMUM WEIGHT TO BE |
| | SUPPORTED. NEC314.27(D) REVISE ACCORDINGLY |
| | |
| | 7) CLAIRFICATION IS REQUIRED. THERE ARE NUMBER AND |
| | LLETTER DESIGNATIONS USED THROUGHOUT THE PLAN HOWEVER |
| | THERE IS NO SYMBOLS KEY USED FOR REFFERENCE. REVISE |
| | PLAN FOR CLAIRIFICATION. WPB AMENDMENTS TO THE FBC |
| | 107.3.2 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |