Plan Review Details - Permit 14080326
Plan Review Stops For Permit 14080326
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-10-11 Cont ID  
Sent By shill Date 2014-10-11 Time 12:05 Rev Time 0.00
Received By shill Date 2014-10-11 Time 12:05 Sent To  
Notes
2014-10-11 12:06:37PROVISO
  
 FUTURE APPLICATIONS TO INCLUDE TWO COMPLETE SETS AND
 ALL APPLICABLE PRODUCT APPROVALS
  
 DISCUSSED WITH CONTRACTOR
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-10-07 Cont ID  
Sent By shill Date 2014-10-07 Time 17:31 Rev Time 0.00
Received By shill Date 2014-10-07 Time 17:31 Sent To  
Notes
2014-10-07 17:34:34****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 2ND REVIEW:
  
 1. OK
  
 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR
 THE ROOF PANEL AND FOR ACM FASCIA PANELS, FAC9N-3, FBC
 1609.
  
 ON THE PRODUCT APPROVAL, INDICATE METHOD OF ATTACHMENT
 IF THERE IS MORE THAN ONE OPTION.
  
 2ND REVIEW, PRODUCT APPROVALS NOT PROVIDED.
  
 3. PROVIDE ROOF PRESSURES FOR ZONES 1, 2, AND 3.
 PRODUCT APPROVAL TO BE CLEAR AS TO WHICH FASTENING
 PROPOSED FOR EACH ZONE, FBC 1609.
  
 2ND REVIEW, PRODUCT APPROVALS NOT PROVIDED. THEY ARE
 REFERENCED ON THE ENGINEERING PLAN BUT THE ACTUAL
 PRODUCT APPROVALS ARE REQUIRED FOR PLAN REVIEW AND FOR
 INSPECTIONS.
  
 NEW COMMENT:
  
 4. ONE SET WAS CHECKED OUT BY CONTRACTOR. PLEASE RETURN
 AS TWO COMPLETE SETS OF PLANS ARE REQUIRED FOR PERMIT
 ISSUANCE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-09-02 Cont ID  
Sent By shill Date 2014-09-02 Time 16:58 Rev Time 0.00
Received By shill Date 2014-09-02 Time 16:58 Sent To  
Notes
2014-09-02 17:02:28****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC 1609, PLEASE CLARIFY ROOF PRESSURES. WERE
 PRESSURES CALCULATED FOR C&C OR MWFRS? THEY APPEAR LOW
 FOR C&C. IF PLYWOOD SHEATHING IS TO BE DESIGNED WITH
 C&C PRESSURES, WHY WOULD MWFRS PRESSURES BE USED, IF
 THAT IS THE CASE? PLEASE EITHER REVISE PRESSURES OR
 PROVIDE EXPLANATION. FEEL FREE TO CONTACT ME IF YOU
 NEED MORE CLARIFICATION.
  
 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR
 THE ROOF PANEL AND FOR ACM FASCIA PANELS, FAC9N-3, FBC
 1609.
  
 ON THE PRODUCT APPROVAL, INDICATE METHOD OF ATTACHMENT
 IF THERE IS MORE THAN ONE OPTION.
  
 3. PROVIDE ROOF PRESSURES FOR ZONES 1, 2, AND 3.
 PRODUCT APPROVAL TO BE CLEAR AS TO WHICH FASTENING
 PROPOSED FOR EACH ZONE, FBC 1609.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-02 Cont ID  
Sent By shill Date 2014-09-02 Time 17:02 Rev Time 0.00
Received By shill Date 2014-08-08 Time 14:54 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2014-08-11 Cont ID  
Sent By shill Date 2014-09-02 Time 17:02 Rev Time 0.00
Received By sgraham Date 2014-08-11 Time 11:55 Sent To B
Notes
***NONE***