Plan Review Details - Permit 14080325
Plan Review Stops For Permit 14080325
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-10-16 Cont ID  
Sent By jwitmer Date 2014-10-16 Time 15:59 Rev Time 0.00
Received By jwitmer Date 2014-10-16 Time 15:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-08-27 Cont ID  
Sent By jwitmer Date 2014-08-27 Time 16:38 Rev Time 0.00
Received By jwitmer Date 2014-08-27 Time 12:26 Sent To  
Notes
2014-08-27 16:38:04BUILDING PLAN REVIEW
 PERMIT: 14080325
 ADD: 6710 S DIXIE HWY
 CONT: RAPP CONSTRUCTION
 TEL: (561)842-3299
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. AUG. 27/2014
 ACTION: DENIED
  
 1) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS:
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 2. OCCUPANCY GROUP: 304.1 BUSINESS GROUP B. ANIMAL
 HOSPITALS, KENNELS AND POUNDS
 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503).
 4. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: SCHEMATIC
 FIRE SPRINKLERS. FIRE SPRINKLERS YES OR NO
 5) LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL
 INCLUDE THE FOLLOWING REQUIREMENTS:
 6) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD : GROSS OR NET TABLE 1004.1.1
 MEANS OF EGRESS : EXIT ACCESS TRAVEL DISTANCES
  
 2) SHEET A3:
 2A) THE BUILDING HAS A OCCUPANT LOAD OF OVER 50
 OCCUPANTS, MANY OF THE DOORS SWING AGAINST THE MEANS OF
 EGRESS AND WILL NEED TO COMPLY WITH: 2010 FBC-B
 1008.1.2 DOOR SWING. DOORS SHALL SWING IN THE DIRECTION
 OF EGRESS TRAVEL WHERE SERVING AN OCCUPANT LOAD OF 50
 OR MORE PERSONS.
  
 2B) DOORS ALSO HAVE CARD READERS ON ALOT OF EGRESS
 DOORS, PLEASE COMPLY WITH 1008.1.4.4 ACCESS-CONTROLLED
 EGRESS DOORS.
  
 2C) DOORS ARE NOT NUMBERED TO IDENTIFY THERE LOCATION,
 ONLY THE TYPE OF DOOR. THERE ARE MANY DOORS THAT DO NOT
 MEET THE 2010 FL ACCESSIBILITY CODE. PLEASE REVIEW
 TABLE 404.2.4.1.
  
 2D) THERE ARE EXISITNG AS WELL AS NEW DOORS, THE 2010
 FBC-B 1008.1.1 SIZE OF DOORS. THE MINIMUM WIDTH OF EACH
 DOOR OPENING SHALL BE SUFFICIENT FOR THE OCCUPANT LOAD
 THEREOF AND SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES
 (813 MM). CLEAR OPENINGS OF DOORWAYS WITH SWINGING
 DOORS SHALL BE MEASURED BETWEEN THE FACE OF THE DOOR
 AND THE STOP, WITH THE DOOR OPEN 90 DEGREES.
 2010 FL ACCESSIBILITY CODE 04.2.3 CLEAR WIDTH. DOOR
 OPENINGS SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES (815
 MM) MINIMUM. CLEAR OPENINGS OF DOORWAYS WITH SWINGING
 DOORS SHALL BE MEASURED BETWEEN THE FACE OF THE DOOR
 AND THE STOP, WITH THE DOOR OPEN 90 DEGREES.
  
 3) THE 2010 FL ACCESSIBILITY CODE WILL REQUIRE
 ACCESSIBLE UPGRADES UP TO 20% OF THE CONTRACT VALUE OR
 $45,000.00 OF ADDITIONAL VALUE OF WORK. 202.4.1
 DISPROPORTIONATE COST. ALTERATIONS MADE TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO THE ALTERED AREA WILL BE
 DEEMED DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN
 THE COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO
 THE PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 EITHER THE DESIGNER OR CONTRACTOR WILL NEED TO MAKE UP
 A ITEMIZED LIST WHERE THESE MONIES WILL BE SPENT IN
 ACCESSIBLE UPGRADES.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-10-09 Cont ID  
Sent By rlecky Date 2014-10-09 Time 11:03 Rev Time 0.00
Received By rlecky Date 2014-10-09 Time 10:45 Sent To  
Notes
2014-10-09 11:05:28ENGINEER'S LETTER PLACED IN FILE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-08-27 Cont ID  
Sent By rlecky Date 2014-08-27 Time 10:52 Rev Time 0.00
Received By rlecky Date 2014-08-26 Time 14:06 Sent To  
Notes
2014-08-27 10:55:2014080325
 6710 S. DIXIE HWY
 POSH PET HOTEL
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE ELECTRIC PLAN
 WHICH SHOWS COMPLIANCE WITH THE FLORIDA BUILDING ENERGY
 CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.5;
 505.5.3; T. 505.5.3
  
 CONFIRM THAT THE INTERIOR AND EXTERIOR LIGHTING
 CONTROLS PROVIDED FUNCTION IN ACCORDANCE WITH THE
 FLORIDA ENERGY CODE. EXTERIOR AUTOMATIC CONTROLS SHALL
 BE CAPABLE OF RETAINING PROGRAMMING AND THE TIME
 SETTING DURING LOSS OF POWER FOR A PERIOD OF AT LEAST
 10 HOURS. VERIFY THE LIGHTING AND SIGN TIME CLOCKS HAVE
 BATTERY BACKUP. FBC ENERGY CONSERVATION 505.2
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE ELECTRIC SERVICE, PANEL BOARDS AND MAIN
 DISCONNECTING MEANS. NEC 110.16, 110.22
  
 PROVIDE AN ELECTRICAL RISER PLAN OF THE ELECTRICAL
 SERVICE WITH A SUMMERY LOAD CALCULATION. PROVIDE PANEL
 BOARD SCHEDULES SHOWING THE BRANCH CIRCUITS AS
 BALANCED. INDICATE THE FAULT CURRENT RATINGS OF THE
 EQUIPMENT. VERIFY THE ELECTRICAL SERVICE MAINS SERVING
 THIS BUILDING ARE SIX OR LESS AND GROUPED IN ONE
 LOCATION. VERIFY SAFE WORKING CLEARANCE HAVE BEEN
 PROVIDED FOR THE SERVICE, PANEL BOARDS AND DISCONNECTS.
 NEC 110.26, 215.5, 230.71 240.24(D)
  
 VERIFY THE ELECTRICAL DISCONNECTING MEANS AND PANEL
 BOARDS HAVE A FAULT CURRENT RATING THAT IS SUFFICIENT
 AT NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. INDICATE THE MAXIMUM AVAILABLE FAULT
 CURRENT AT THE SERVICE POINT FROM THE ELECTRICAL
 UTILITY. NEC 110.9, 110.10
  
 PROVIDE SHOW WINDOW LIGHTING RECEPTACLES. NEC 210.62
  
 PROVIDE A SIGN CIRCUIT AND DISCONNECT. NEC 600.5,
  
 VERIFY EXISTING HEATING AND AIR CONDITIONING EQUIPMENT
 HAVE A GFCI PROTECTED RECEPTACLE AVAILABLE WITHIN 25
 FEET. NEC 210.63
  
 NOTE: A SEPARATE PERMIT AND PLANS ARE REQUIRED FOR FIRE
 ALARM SYSTEMS, VIDEO, SECURITY, VOICE, POS, SITE
 LIGHTING, SIGNS AND DATA SYSTEMS
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
 561-373-3701
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-10-14 Cont ID  
Sent By pleduc Date 2014-10-14 Time   Rev Time 0.00
Received By pleduc Date 2014-10-14 Time 12:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-08-12 Cont ID  
Sent By pleduc Date 2014-08-12 Time   Rev Time 0.00
Received By pleduc Date 2014-08-12 Time 13:06 Sent To  
Notes
2014-08-12 14:38:15THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THIS OCCUPANCY AND PROPOSED PLAN SHALL MEET OR EXCEED
 THE REQUIREMENTS OF NFPA 150, FIRE AND LIFE SAFETY IN
 ANIMAL HOUSING FACILITIES.
  
 THE BUILDING PLAN DOES NOT INCLUDE THE BUILDING SQUARE
 FOOTAGE AND CONSTRUCTION TYPE/CLASS, ROOF SYSTEM.
  
 A LIFE SAFETY PLAN, INCLUDING ALL OCCUPANCY COUNTS,
 HUMAN AND ANIMAL, COMMON PATHS OF TRAVEL, EXITS, EXIT
 DISCHARGES AND FIRE EXTINGUISHER LOCATIONS SHALL BE
 INCLUDED.
  
 AN EXIT PATH SHALL NOT EXCEED 75 FEET FROM ANY AREA OF
 THE BUUILDING.
  
 A NFPA 72 COMPLIANT FIRE ALARM SYSTEM IS REQUIRED OR
 THIS OCCUPANCY. THE FIRE ALARM SHALL BE MONITORED
 UNLESS THE FACILTIY IS MANNED 24 HOURS A DAY.
  
 A KNOX BOX KEY SYSTEM IS REQUIRED FOR 24 HOUR EMERGENCY
 RESPONDER ACCESS.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-11-06 Cont ID  
Sent By hmoser Date 2014-11-06 Time 09:52 Rev Time 0.00
Received By hmoser Date 2014-11-01 Time 06:13 Sent To  
Notes
2014-11-01 06:13:42C17

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-10-25 Cont ID  
Sent By tklarge Date 2014-10-25 Time 08:28 Rev Time 0.00
Received By tklarge Date 2014-10-02 Time 14:33 Sent To  
Notes
2014-10-02 14:34:06RE-SUBMITTAL SENT TO C6 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-03 Cont ID  
Sent By   Date 2014-09-03 Time   Rev Time 0.00
Received By shill Date 2014-08-08 Time 10:00 Sent To  
Notes
2014-08-15 10:14:46C08
  
 (MOVED - HAS STRUCTURAL AND > 5000SF)
  
2014-08-09 14:08:06B25

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2014-08-27 Cont ID  
Sent By jwitmer Date 2014-08-27 Time 16:38 Rev Time 0.00
Received By jwitmer Date 2014-08-27 Time 12:26 Sent To  
Notes
2014-08-27 16:38:45NOT A CHANGE IN OCCUPANCY.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2014-11-06 Cont ID  
Sent By HMOSER Date 2014-11-06 Time 09:09 Rev Time 0.00
Received By hmoser Date 2014-11-06 Time 09:05 Sent To  
Notes
2014-11-06 09:08:55PASS PROVISO
 REFER TO SECTION 601.4 BALANCED RETURN AIR.
 2010 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX-561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2014-10-08 Cont ID  
Sent By rbergsma Date 2014-10-08 Time   Rev Time 1.00
Received By rbergsma Date 2014-10-08 Time   Sent To  
Notes
2014-10-08 15:35:38504.5 MAKEUP AIR.
 INSTALLATIONS EXHAUSTING MORE THAN 200 CFM (0.09M3/S)
 SHALL BE PROVIDED WITH MAKEUP AIR
  
 PLEASE PROVIDE A DUCT OR DOOR GRILL INTO THE LAUNDRY
 AREA FROM THE CORRIDOR TO PROVIDE REQUIRED M/U AIR
 AND SHOW DRYER DUCT TO THE OUTSIDE
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-08-19 Cont ID  
Sent By hmoser Date 2014-08-19 Time 10:25 Rev Time 0.00
Received By hmoser Date 2014-08-19 Time 09:22 Sent To  
Notes
2014-08-19 10:25:03PLAN DENIED
  
 1) PROVIDE FRESH AIR CALCULATIONS PER TABLE
 401.3 FBC (M) 2010
 2) REFER TO SECTION 601.4 BALANCED RETURN AIR
 LOBBY, TRAINING AREA 2010 FBC (M)
 3) REFER TO SECTION 607.5.1 FIRE WALLS
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 3 Status P Date 2014-11-05 Cont ID  
Sent By TKLARGE Date 2014-11-05 Time 10:49 Rev Time 0.00
Received By tklarge Date 2014-11-05 Time 10:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2014-10-25 Cont ID  
Sent By tklarge Date 2014-10-25 Time 08:24 Rev Time 0.00
Received By tklarge Date 2014-10-25 Time 08:24 Sent To  
Notes
2014-10-25 08:25:511) NONE OF THE PREVIOUS TWELVE PLUMBING REVIEW COMMENTS
 HAVE BEEN ADDRESSED. COMPLY W/ALL PREVIOUS COMMENTS
 FROM THE PLUMBING REVIEW DATED 9/3/14.
  
 COMMENTS FROM REVIEW DATED 9/3/14:
  
 1) THIS IS CONSIDERED A LEVEL III ALTERATION PER THE
 2010 EXISTING BUILDING CODE. INDICATE THIS ON THE
 PLANS.
 2) SUBMIT THE TOTAL OCCUPANT LOAD AND THE SQUARE
 FOOTAGE OF THE BUILDINGIN ACCORDANCE WITH TABLE 1004.1
 OF THE 2010 FL. BLDG. CODE AND THE 2010 WPB ADMIN.
 AMEND. TO 2010 FBC.
 3) THE UNISEX TOILET ROOM SHALL CONTAIN ONLY ONE WATER
 CLOSET AND/OR ONE URINAL AND A LAVATORY PER THE 2010
 FL. PLBG.CODE SEC.403.5.2.
 4) SEPARATE SANITARY FACILITIES SHALL BE PROVIDED FOR
 EACH SEX PER THE 2010 FPC SEC.403.2. THE TOTAL NUMBER
 OF MINIMUM REQUIRED FIXTURES CANNOT BE DETERMINED UNTIL
 AN OCCUPANT LOAD IS SUBMITTED.
 5) SHOW THE REQUIRED TURNING SPACE IN THE ALTERED
 TOILET ROOMS PER THE 2010 FLORIDA ACCESSIBILITY CODE
 SEC.304.2, 304.3.
 6) SHOW THE REQUIRED CLEAR FLOOR SPACE AT THE FIXTURES
 PER THE FAC SEC.305.
 7) THE WASHING MACHINES AND CLOTHES DRYERS SHALL BE
 ACCESSIBLE AND HAVE THE REQUIRED CLEAR FLOOR SPACES PER
 THE 2010 FAC SECS.611.1 THRU 611.4 AND SEC.305 AND 309.
 SHOW THE HEIGHT AND REACH RANGES ON THE PLAN. DETAISL
 14 & 15 ON SHT. A-10.
 8) THE DOG KITCHEN SINK SHALL BE ACCESSIBLE AND COMPLY
 W/THE FAC SEC.606.1 THRU 606.5.
 9) REMOVE THE BROKEN LINES FROM THE ARCHITECTURAL PAGES
 THAT SHOW THE EXISTING PLUMBING FIXTURES IN THE ROOMS.
 SHOW JUST THE NEW LAYOUT. WPB ADMIN. AMEND. TO 2010 FBC
 SEC.107.2.1.
 10) SHT. P-0.1- NOTES 23 & 24- DELETE THESE NOTES.THEY
 REFER TO AN ELEVATOR AND THERE IS NO ELEVATOR IN THIS
 BUILDING.
 11) SUBMIT A SANITARY AND WATER RISER FOR REVIEW FOR
 THE CHANGES BEING MADE TO THE PLUMBING SYSTEM. WPB
 ADMIN. AMEND. TO 2010 FBC SEC.107.2.1.
 12) SHUTOFF VALVES SHALL BE INSTALLED IN THE WATER
 DISTRIBUTION SYSTEM PER THE 2010 FPC SEC.606.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE-
 CHIEF PLUMBING INSPECTOR
 TEL:561-805-6692
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-09-03 Cont ID  
Sent By tklarge Date 2014-10-25 Time 08:26 Rev Time 0.00
Received By tklarge Date 2014-09-03 Time 08:27 Sent To  
Notes
2014-09-03 09:20:181) THIS IS CONSIDERED A LEVEL III ALTERATION PER THE
 2010 EXISTING BUILDING CODE. INDICATE THIS ON THE
 PLANS.
 2) SUBMIT THE TOTAL OCCUPANT LOAD AND THE SQUARE
 FOOTAGE OF THE BUILDINGIN ACCORDANCE WITH TABLE 1004.1
 OF THE 2010 FL. BLDG. CODE AND THE 2010 WPB ADMIN.
 AMEND. TO 2010 FBC.
 3) THE UNISEX TOILET ROOM SHALL CONTAIN ONLY ONE WATER
 CLOSET AND/OR ONE URINAL AND A LAVATORY PER THE 2010
 FL. PLBG.CODE SEC.403.5.2.
 4) SEPARATE SANITARY FACILITIES SHALL BE PROVIDED FOR
 EACH SEX PER THE 2010 FPC SEC.403.2. THE TOTAL NUMBER
 OF MINIMUM REQUIRED FIXTURES CANNOT BE DETERMINED UNTIL
 AN OCCUPANT LOAD IS SUBMITTED.
 5) SHOW THE REQUIRED TURNING SPACE IN THE ALTERED
 TOILET ROOMS PER THE 2010 FLORIDA ACCESSIBILITY CODE
 SEC.304.2, 304.3.
 6) SHOW THE REQUIRED CLEAR FLOOR SPACE AT THE FIXTURES
 PER THE FAC SEC.305.
 7) THE WASHING MACHINES AND CLOTHES DRYERS SHALL BE
 ACCESSIBLE AND HAVE THE REQUIRED CLEAR FLOOR SPACES PER
 THE 2010 FAC SECS.611.1 THRU 611.4 AND SEC.305 AND 309.
 SHOW THE HEIGHT AND REACH RANGES ON THE PLAN. DETAISL
 14 & 15 ON SHT. A-10.
 8) THE DOG KITCHEN SINK SHALL BE ACCESSIBLE AND COMPLY
 W/THE FAC SEC.606.1 THRU 606.5.
 9) REMOVE THE BROKEN LINES FROM THE ARCHITECTURAL PAGES
 THAT SHOW THE EXISTING PLUMBING FIXTURES IN THE ROOMS.
 SHOW JUST THE NEW LAYOUT. WPB ADMIN. AMEND. TO 2010 FBC
 SEC.107.2.1.
 10) SHT. P-0.1- NOTES 23 & 24- DELETE THESE NOTES.THEY
 REFER TO AN ELEVATOR AND THERE IS NO ELEVATOR IN THIS
 BUILDING.
 11) SUBMIT A SANITARY AND WATER RISER FOR REVIEW FOR
 THE CHANGES BEING MADE TO THE PLUMBING SYSTEM. WPB
 ADMIN. AMEND. TO 2010 FBC SEC.107.2.1.
 12) SHUTOFF VALVES SHALL BE INSTALLED IN THE WATER
 DISTRIBUTION SYSTEM PER THE 2010 FPC SEC.606.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE-
 CHIEF PLUMBING INSPECTOR
 TEL:561-805-6692
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2014-10-16 Cont ID  
Sent By llouie Date 2014-10-16 Time 10:38 Rev Time 0.00
Received By llouie Date 2014-10-16 Time 10:38 Sent To  
Notes
2014-10-16 10:47:07ZONING APPROVED WITH THE FOLLOWING PROVISO:
  
 1.) SEPARATE PERMITS REQUIRED FOR: LANDSCAPING, AWNINGS
 (IF TO BE REPLACED), SIGNAGE, OUTDOOR PLAY AREA AN NEW
 DUMPSTER ENCLOSURE.
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2014-08-28 Cont ID  
Sent By dkittrid Date 2014-08-28 Time 16:22 Rev Time 0.00
Received By llouie Date 2014-08-28 Time 16:22 Sent To  
Notes
2014-08-28 16:23:14** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) ZBA3308 CONDITION OF APPROVAL FOR THE PET CARE
 FACILITY USE WITH OVERNIGHT BOARDING AND AN OUTDOOR
 PLAY AREA ON THE PROPERTY REQUIRES THE OUTDOOR PLAY
 AREA TO BE EQUIPPED WITH SOUND ABSORPTION PANELS TO
 MITIGATE THE NOISE ON THE ADJACENT PROPERTIES. AT
 MINIMUM, A NOTATION SHOULD BE PROVIDED IN THE PLANS TO
 ENSURE THIS CONDITION WILL BE MET.
  
 2.) DEPICT THE DUMPSTER ENCLOSURE IN SITE PLAN.
  
 3.) NOTE ON SHEET A-2: "PROPOSED REMOVAL OF EXISTING
 BRICK PAVERS FOR NEW LANDSCAPING - SEE LANDSCAPE
 ARCHITECT'S PLANS" IS NOT DEPICTED IN THE LANDSCAPE
 PLAN. PLEASE ADDRESS. (NOTE: ANY LANDSCAPE IMPROVEMENTS
 MADE IN THE RIGHT OF WAY ALONG DIXIE HIGHWAY REQUIRES
 FDOT APPROVAL).
  
 4.) THE LANDSCAPE PLAN DEPICTS A NEW COCONUT PALM TO BE
 PLANTED IN THE SWALE AREA ON LYTLE STREET. ANY
 IMPROVEMENTS/PLANTINGS MADE IN THE RIGHT-OF-WAY IS
 REQUIRED TO OBTAIN APPROVAL FROM THE ENGINEERING
 DEPARTMENT.
  
 5.) NOTE: FDOT/ENGINEERING APPROVAL REQUIRED FOR THE
 REPLACEMENT OF ANY AWNINGS OVER SIDEWALKS.
  
 6.) SEPARATE PERMITS AND REVIEW REQUIRED FOR:
 LANDSCAPING, AWNINGS (IF TO BE REPLACED), SIGNAGE,
 OUTDOOR PLAY AREA, AND DUMPSTER ENCLOSURE.
  
 PLEASE NOTE THAT ANY CHANGES ON THE RESUBMITTED PLANS
 MAY RESULT IN ADDITIONAL COMMENTS. CONTACT LINDA LOUIE
 @ (561) 822-1458 IF YOU HAVE QUESTIONS.
  
  
  
2014-08-26 13:29:538/26/14


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved