Plan Review Details - Permit 14080268
Plan Review Stops For Permit 14080268
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-08-20 Cont ID  
Sent By jwitmer Date 2014-08-20 Time 11:59 Rev Time 0.00
Received By jwitmer Date 2014-08-20 Time 09:39 Sent To  
Notes
2014-08-20 11:59:31BUILDING PLAN REVIEW
 PERMIT: 14080268
 ADD: 1301 BELVEDERE RD
 CONT: WESTLAKE LLC
 TEL: (267)251-8336
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. AUG. 20/2014
 ACTION: BUILDING PROVISO
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1A) SHEET G001 OCCUPANCY TYPE SHOULD BE NOT A R2 BUT A
 R1 HOTEL 2010 FBC-B 310.1.
  
 1B) SHEET G001 EXISTING BUILDING CODE LEVEL 1, PLEASE
 SEE 2010 EXISTING BUILDING CODE LEVEL II 404.1 SCOPE.
 LEVEL 2 ALTERATIONS INCLUDE THE RECONFIGURATION OF
 SPACE, THE ADDITION OR ELIMINATION OF ANY DOOR OR
 WINDOW, THE RECONFIGURATION OR EXTENSION OF ANY SYSTEM,
 OR THE INSTALLATION OF ANY ADDITIONAL EQUIPMENT.
  
 LEVEL II. 701.3 COMPLIANCE. ALL NEW CONSTRUCTION
 ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY
 WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE,
 BUILDING.
  
 2) SHEET A100 NOTE # 4 REMOVE DOORS IN ENTIRETY INSTALL
 ALUMINUM STOREFRONT AND GLAZING TO MATCH. SHEET A101
 INDICATES NEW STUCCO / METAL STUD INFILL WALLS WITH
 HORIZONTAL SLIDING DOORS.
  
 2A) PLEASE PROVIDE THE WIND DESIGN FOR THIS OPENING,
 NEGATIVE PRESSURES ARE TAKEN FROM THE ROOF. 2010 FBC-B
 1609.1.1 DETERMINATION OF WIND DESIGN- CHAPTER 6 OF
 ASCE 7-10. 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
  
 2A)(1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 2A)(2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE
 7-10.
  
 2A)(3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 2A)(4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 2A)(5) COMPONENTS & CLADDING PRESSURES POSITVE &
 NEGATIVE TABLE 1609.2(2) .
  
  
 2B) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) , EFIS SYSTEMS,
  
 2C) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2D) THE INFILL EXTERIOR WALLS WILL NEED TO SHOW HOW
 THEY WILL BE ABLE TO RESIST WIND AND PART OF THE MAIN
 WIND FORCE RESISTING SYSTEM. 2010 FBC-B 1609.1.1.
  
 2D) THE PLANS DEPICT THE USE OF WHAT APPEARS TO BE
 HORIZONTAL SLIDING DOORS WILL NEED TO MEET THE
 REQUIREMENTS OF:
  
 1008.1.4.3 HORIZONTAL SLIDING DOORS.
 IN OTHER THAN GROUP H OCCUPANCIES, HORIZONTAL SLIDING
 DOORS PERMITTED TO BE A COMPONENT OF A MEANS OF EGRESS
 IN ACCORDANCE WITH EXCEPTION 6 TO SECTION 1008.1.2
 SHALL COMPLY WITH ALL OF THE FOLLOWING CRITERIA:
  
 1. THE DOORS SHALL BE POWER OPERATED AND SHALL BE
 CAPABLE OF BEING OPERATED MANUALLY IN THE EVENT OF
 POWER FAILURE.
  
 2. THE DOORS SHALL BE OPENABLE BY A SIMPLE METHOD FROM
 BOTH SIDES WITHOUT SPECIAL KNOWLEDGE OR EFFORT.
  
 3. THE FORCE REQUIRED TO OPERATE THE DOOR SHALL NOT
 EXCEED 30 POUNDS (133 N) TO SET THE DOOR IN MOTION AND
 15 POUNDS (67 N) TO CLOSE THE DOOR OR OPEN
 IT TO THE MINIMUM REQUIRED WIDTH.
  
 4. THE DOOR SHALL BE OPENABLE WITH A FORCE NOT TO
 EXCEED 15 POUNDS (67 N) WHEN A FORCE OF 250 POUNDS
 (1100 N) IS APPLIED PERPENDICULAR TO THE DOOR
 ADJACENT TO THE OPERATING DEVICE.
  
 5. THE DOOR ASSEMBLY SHALL COMPLY WITH THE APPLICABLE
 FIRE PROTECTION RATING AND, WHERE RATED, SHALL BE
 SELF-CLOSING OR AUTOMATIC CLOSING BY SMOKE
 DETECTION IN ACCORDANCE WITH SECTION 715.4.8.3, SHALL
 BE INSTALLED IN ACCORDANCE WITH NFPA 80 AND SHALL
 COMPLY WITH SECTION 715.
  
 6. THE DOOR ASSEMBLY SHALL HAVE AN INTEGRATED STANDBY
 POWER SUPPLY.
  
 7. THE DOOR ASSEMBLY POWER SUPPLY SHALL BE ELECTRICALLY
 SUPERVISED.
  
 8. THE DOOR SHALL OPEN TO THE MINIMUM REQUIRED WIDTH
 WITHIN 10 SECONDS AFTER ACTIVATION OF THE OPERATING
 DEVICE.
  
 9. IN APARTMENT BUILDINGS, HOTELS AND DORMITORIES,
 HORIZONTAL SLIDING DOORS SHALL NOT BE USED ACROSS
 CORRIDORS.
  
 1008.1.10 PANIC AND FIRE EXIT HARDWARE.
 DOORS SERVING A GROUP H OCCUPANCY AND DOORS SERVING
 ROOMS OR SPACES WITH AN OCCUPANT LOAD OF 50 OR MORE IN
 A GROUP A OR E OCCUPANCY SHALL NOT BE PROVIDED WITH A
 LATCH OR LOCK UNLESS IT IS PANIC HARDWARE OR FIRE EXIT
 HARDWARE.
 EXCEPTIONS: 1. A MAIN EXIT OF A GROUP A OCCUPANCY IN
 COMPLIANCE WITH SECTION 1008.1.9.3, ITEM 2.
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-09-06 Cont ID  
Sent By dhayes Date 2014-09-06 Time 15:52 Rev Time 0.00
Received By dhayes Date 2014-09-06 Time 15:28 Sent To  
Notes
2014-09-06 15:52:42DATE: 9/6/2014
 PROJECT: HOLIDAY INN LOBBY RENNOVATION.
 PERMIT#: 14080268
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) PROVIDE LOAD CALCULATION FOR THE ELECTRICAL SERVICE
 AND PANEL MDP INDICATING THE AVAILABLE CAPACITY TO
 INSTALL THE ADDITIONAL LOAD FOR THE NEW PROPOSED 125AMP
 PANEL P1
  
 SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, PLANS, AND SHOP
 DRAWINGS AS REQUIRED FOR, ACCESS CONTROL, FIRE ALARM,
 SECURITY, CCTV, DATA/COM, NETWORK, STRUCTURED CABLING,
 AUDIO/VIDEO, AND SIGNAGE.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-08-12 Cont ID  
Sent By pleduc Date 2014-08-12 Time   Rev Time 0.00
Received By pleduc Date 2014-08-12 Time 12:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-09-23 Cont ID  
Sent By tklarge Date 2014-09-23 Time 06:06 Rev Time 0.00
Received By tklarge Date 2014-09-23 Time 05:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-19 Cont ID  
Sent By tklarge Date 2014-09-19 Time 15:13 Rev Time 0.00
Received By tklarge Date 2014-09-15 Time 08:37 Sent To  
Notes
2014-09-19 15:14:449/19/14 - DENIED/E-MAILED CONTRACTOR/PLANS PLACED IN
 LARGE " W". TKL.
2014-09-16 08:37:43RE-SUBMITTAL SENT TO TIM LARGE'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-07 Cont ID  
Sent By   Date 2014-09-07 Time   Rev Time 0.00
Received By jwitmer Date 2014-08-07 Time 14:42 Sent To  
Notes
2014-08-07 14:42:31INCOMING SENT TO B-29. JW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-08-15 Cont ID  
Sent By jdariton Date 2014-08-15 Time 11:26 Rev Time 0.00
Received By jdariton Date 2014-08-15 Time 11:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2014-09-23 Cont ID  
Sent By tklarge Date 2014-09-23 Time 05:27 Rev Time 0.00
Received By tklarge Date 2014-09-23 Time 05:18 Sent To  
Notes
2014-09-23 05:29:13*** SEPARATE PERMIT REQD. FOR GREASE INTERCEPTOR**

Review Stop P PLUMBING
Rev No 2 Status F Date 2014-09-19 Cont ID  
Sent By tklarge Date 2014-09-19 Time 14:51 Rev Time 0.00
Received By tklarge Date 2014-09-19 Time 14:51 Sent To  
Notes
2014-09-19 15:09:351) ALL THE COMMENTS FROM THE PREVIOUS REVIEW HAVE NOT
 BEEN ADDRESSED.
 2) 2ND REQUEST - SHOW THE LENGTH AND WIDTH OF THE
 URINAL AND TOILET STALLS ON THE FLOOR PLAN. COMPLY WITH
 THE 2010 FLORIDA PLUMBING CODE SEC.405.3.1.AND THE FAC
 SEC.604.8.2.1. SEE SHEETS A101,102, 150, 151.
 3) 2ND REQUEST - TOILET COMPARTMENT DOORS SHALL NOT
 SWING INTO THE REQUIRED COMPARTMENT AREA PER THE 2010
 FAC SEC.603.2.3, 604.8.2.2.
 4) 2ND REQUEST - DOORS SHALL NOT SWING INTO THE URINAL
 COMPARTMENTS PER THE 2010 FAC SEC. 604.8.2.2. SHT A201
 - DETAILS #1, #3, AND #7 SHOW VERTICAL GRAB BARS. GRAB
 BARS ARE NOT PERMITTED TO BE INSTALLED IN A VERTICAL
 POSITION PER THE 2010 FAC SEC. 609.4.
 5) THE REVISED PLUMBING SHEETS P-202 & P-401 SHALL BE
 INSERTED INTO THE PLANS AND THE OLD SHEETS REMOVED.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-09-07 Cont ID  
Sent By tklarge Date 2014-09-07 Time 07:19 Rev Time 0.00
Received By tklarge Date 2014-08-20 Time 09:39 Sent To  
Notes
2014-09-07 07:39:13WPB ADMIN. AMEND. TO 2010 FBC SEC.107.2.1.
 1) SHOW THE LENGTH AND WIDTH OF THE URINAL AND TOILET
 STALLS ON THE FLOOR PLAN. COMPLY W/ 2010 FLORIDA
 PLUMBING CODE SEC.405.3.1 & FAC SEC.604.8.2.1. SHTS.
 A101,102,150,151.
 2)THE DOOR CANNOT SWING IN TO THE CLEAR FLOOR SPACE
 REQUIRED FOR THE TOILET COMPARTMENTS PER THE 2010 FL.
 ACCESSIBILITY CODE SEC.603.2.3, 604.8.2.2.
 3) DOORS SHALL NOT NOT SWING INTO THE URINAL
 COMPARTMENTS PER THE FL. ACCESSIBILITY CODE SEC.
 604.8.2.2.
 SHT. A201 - DETAILS #1, #3, & #7 SHOW VERTICAL GRAB
 BARS. GRAB BARS INSTALLED IN A VERTICAL POSITION ARE
 NOT PERMITTED PER THE 2010 FAC SEC.609.4.
 4) SHT. P401 - SUBMIT A LEGEND FOR THE CIRCLED NUMBERS
 SHOWN ON THE PLANS ( E.G. #1,11,12,14).
 5)SUBMIT MANUFACTURERE'S SPECIFICATION SHEETS FOR THE
 SCHIER GREASE TRAP.
 5) SUBMIT SIZING CALCULATIONS FOR THE GREASE TRAP AS TO
 THE AMOUNT GREASE THAT WILL BE GENERATED TO SPECIFY THE
 SIZE OF THIS TRAP.
 6) SHT. P-401 - A URINAL CANNOT BE INSTALLED ON A
 HORIZONTAL WET VENT PER THE 2010 FPC SEC.909.1
 7) SHT. P-401- THE LAVATORIES ON THE SANITARY RISER ARE
 SHOWN AS BEING S-TRAPPED.S-TRAPS ARE NOT PERMITTED PER
 THE 2010 FPC SEC.1002.3
 8) SHT.P-401- NOT MORE THAN ONE WET-VENTED FIXTURE
 DRAIN SHALL DISCHARGE UPSTREAM OF THE DRY-VENTED
 FIXTURE DRAIN CONNECTION.FPC SEC.909.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE-
 CHIEF PLUMBING INSPECTOR
 TEL:561-805-6692
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2014-08-14 Cont ID  
Sent By ajones Date 2014-08-14 Time 16:42 Rev Time 0.00
Received By ajones Date 2014-08-14 Time 16:42 Sent To  
Notes
***NONE***