| 2014-08-20 11:59:31 | BUILDING PLAN REVIEW |
| | PERMIT: 14080268 |
| | ADD: 1301 BELVEDERE RD |
| | CONT: WESTLAKE LLC |
| | TEL: (267)251-8336 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. AUG. 20/2014 |
| | ACTION: BUILDING PROVISO |
| | |
| | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | 1A) SHEET G001 OCCUPANCY TYPE SHOULD BE NOT A R2 BUT A |
| | R1 HOTEL 2010 FBC-B 310.1. |
| | |
| | 1B) SHEET G001 EXISTING BUILDING CODE LEVEL 1, PLEASE |
| | SEE 2010 EXISTING BUILDING CODE LEVEL II 404.1 SCOPE. |
| | LEVEL 2 ALTERATIONS INCLUDE THE RECONFIGURATION OF |
| | SPACE, THE ADDITION OR ELIMINATION OF ANY DOOR OR |
| | WINDOW, THE RECONFIGURATION OR EXTENSION OF ANY SYSTEM, |
| | OR THE INSTALLATION OF ANY ADDITIONAL EQUIPMENT. |
| | |
| | LEVEL II. 701.3 COMPLIANCE. ALL NEW CONSTRUCTION |
| | ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY |
| | WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE, |
| | BUILDING. |
| | |
| | 2) SHEET A100 NOTE # 4 REMOVE DOORS IN ENTIRETY INSTALL |
| | ALUMINUM STOREFRONT AND GLAZING TO MATCH. SHEET A101 |
| | INDICATES NEW STUCCO / METAL STUD INFILL WALLS WITH |
| | HORIZONTAL SLIDING DOORS. |
| | |
| | 2A) PLEASE PROVIDE THE WIND DESIGN FOR THIS OPENING, |
| | NEGATIVE PRESSURES ARE TAKEN FROM THE ROOF. 2010 FBC-B |
| | 1609.1.1 DETERMINATION OF WIND DESIGN- CHAPTER 6 OF |
| | ASCE 7-10. 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | |
| | 2A)(1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 2A)(2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE |
| | 7-10. |
| | |
| | 2A)(3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 2A)(4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 2A)(5) COMPONENTS & CLADDING PRESSURES POSITVE & |
| | NEGATIVE TABLE 1609.2(2) . |
| | |
| | |
| | 2B) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) , EFIS SYSTEMS, |
| | |
| | 2C) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 2D) THE INFILL EXTERIOR WALLS WILL NEED TO SHOW HOW |
| | THEY WILL BE ABLE TO RESIST WIND AND PART OF THE MAIN |
| | WIND FORCE RESISTING SYSTEM. 2010 FBC-B 1609.1.1. |
| | |
| | 2D) THE PLANS DEPICT THE USE OF WHAT APPEARS TO BE |
| | HORIZONTAL SLIDING DOORS WILL NEED TO MEET THE |
| | REQUIREMENTS OF: |
| | |
| | 1008.1.4.3 HORIZONTAL SLIDING DOORS. |
| | IN OTHER THAN GROUP H OCCUPANCIES, HORIZONTAL SLIDING |
| | DOORS PERMITTED TO BE A COMPONENT OF A MEANS OF EGRESS |
| | IN ACCORDANCE WITH EXCEPTION 6 TO SECTION 1008.1.2 |
| | SHALL COMPLY WITH ALL OF THE FOLLOWING CRITERIA: |
| | |
| | 1. THE DOORS SHALL BE POWER OPERATED AND SHALL BE |
| | CAPABLE OF BEING OPERATED MANUALLY IN THE EVENT OF |
| | POWER FAILURE. |
| | |
| | 2. THE DOORS SHALL BE OPENABLE BY A SIMPLE METHOD FROM |
| | BOTH SIDES WITHOUT SPECIAL KNOWLEDGE OR EFFORT. |
| | |
| | 3. THE FORCE REQUIRED TO OPERATE THE DOOR SHALL NOT |
| | EXCEED 30 POUNDS (133 N) TO SET THE DOOR IN MOTION AND |
| | 15 POUNDS (67 N) TO CLOSE THE DOOR OR OPEN |
| | IT TO THE MINIMUM REQUIRED WIDTH. |
| | |
| | 4. THE DOOR SHALL BE OPENABLE WITH A FORCE NOT TO |
| | EXCEED 15 POUNDS (67 N) WHEN A FORCE OF 250 POUNDS |
| | (1100 N) IS APPLIED PERPENDICULAR TO THE DOOR |
| | ADJACENT TO THE OPERATING DEVICE. |
| | |
| | 5. THE DOOR ASSEMBLY SHALL COMPLY WITH THE APPLICABLE |
| | FIRE PROTECTION RATING AND, WHERE RATED, SHALL BE |
| | SELF-CLOSING OR AUTOMATIC CLOSING BY SMOKE |
| | DETECTION IN ACCORDANCE WITH SECTION 715.4.8.3, SHALL |
| | BE INSTALLED IN ACCORDANCE WITH NFPA 80 AND SHALL |
| | COMPLY WITH SECTION 715. |
| | |
| | 6. THE DOOR ASSEMBLY SHALL HAVE AN INTEGRATED STANDBY |
| | POWER SUPPLY. |
| | |
| | 7. THE DOOR ASSEMBLY POWER SUPPLY SHALL BE ELECTRICALLY |
| | SUPERVISED. |
| | |
| | 8. THE DOOR SHALL OPEN TO THE MINIMUM REQUIRED WIDTH |
| | WITHIN 10 SECONDS AFTER ACTIVATION OF THE OPERATING |
| | DEVICE. |
| | |
| | 9. IN APARTMENT BUILDINGS, HOTELS AND DORMITORIES, |
| | HORIZONTAL SLIDING DOORS SHALL NOT BE USED ACROSS |
| | CORRIDORS. |
| | |
| | 1008.1.10 PANIC AND FIRE EXIT HARDWARE. |
| | DOORS SERVING A GROUP H OCCUPANCY AND DOORS SERVING |
| | ROOMS OR SPACES WITH AN OCCUPANT LOAD OF 50 OR MORE IN |
| | A GROUP A OR E OCCUPANCY SHALL NOT BE PROVIDED WITH A |
| | LATCH OR LOCK UNLESS IT IS PANIC HARDWARE OR FIRE EXIT |
| | HARDWARE. |
| | EXCEPTIONS: 1. A MAIN EXIT OF A GROUP A OCCUPANCY IN |
| | COMPLIANCE WITH SECTION 1008.1.9.3, ITEM 2. |
| | |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |