| 2014-08-13 10:04:55 | DATE: 8/13/2014 |
| | PROJECT: FED EX REVISION |
| | REVISION #14080241 PERMIT#: 13120825 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE A LOAD CALCULATION TO INDICATE THE TOTAL |
| | CONNECTED LOAD INCLUDING THE NEW 225AMP CIRCUIT FOR |
| | CONVEYOR CONTROL PANEL. |
| | 2) REVISE THE ONE LINE RISER DIAGRAM TO INDICATE |
| | ADAQUATE WIRE SIZE TO SUPPORT THE 1600AMP MDP |
| | NEC230.90(A), 310.16 |
| | 3) REVISE THE RISER DIAGRAM TO ADDRESS THE LACK OF GFP |
| | OF EQUIPMENT AS PER NEC 230.95 |
| | 4) REVISE GROUNDING ELECTRODE CONDUCTOR SIZE TO THE |
| | MAXIMUM 3/0CU. PER NEC 250.66 NOTES: WHERE MULTIPLE |
| | SETS OF SERVICE-ENTRANCE CONDUCTORS ARE USED AS |
| | PERMITTED IN 230.40, EXCEPTION NO. 2, THE EQUIVALENT |
| | SIZE OF THE LARGEST SERVICE-ENTRANCE CONDUCTOR SHALL BE |
| | DETERMINED BY THE LARGEST SUM OF THE AREAS OF THE |
| | CORRESPONDING CONDUCTORS OF EACH SET. THE SERVICE |
| | ENTRANCE CALLS FOR 4 SETS OF 4, 600MCM. PLEASE INDICATE |
| | CONDUCTOR AND INSULATION TTYPE ON ALL WIRE. |
| | 5) REVISE THE PANEL SCHEDULE MDP TO INCLUDE THE NEW |
| | 225AMP CIRCUIT FOR CONVEYOR CONTROL PANEL. WPB |
| | AMENDMENTS TO FBC CHAPER 1 SECTION 107.2.1 |
| | 6) REVISE PANEL PP1 TO ADD NOTE "LO" TO INDICATE LOCK |
| | ON DEVICE FOR THAT CIRCUIT. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT |
| | /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| | ITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |