| 2014-08-07 08:42:19 | DATE: 8/6/2014 |
| | PROJECT: FACADE RENNOVATION 409 24TH ST |
| | PERMIT#: MASTER:13110608 ELECTRIC SUB: 14011697 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE ELECTRICAL PLANS TO INDICATE THE FOLLOWING: |
| | FBC 107.2.1 |
| | LOCATION OF THE EXISTING JUNCTION BOX WITH 110V |
| | CIRCUIT. |
| | LOCATION OF THE TRANSFORMER. |
| | LOCATION OF THE TIMER. |
| | LOCATION AND NUMBER OF REMOTE LED DRIVER(S). |
| | LOCATION OF LED LIGHTING. |
| | WIRING AND TERMINATION DETAIL INDICATING THE METHODS |
| | AND MATERIALS USED FROM THE SOURCE JUNCTION BOX TO THE |
| | LED LIGHTING. |
| | THE TOTAL LENGTH AND CONNECTED LOAD OF LED LIGHTING. |
| | NAME AND SIGNATURE OF THE DESIGN PROFESSIONAL |
| | |
| | |
| | 2) PROVIDE ITEM NUMBERS AND MAUFACTURER LISTING FROM |
| | APPROVED TESTING LABRATORY ON THE FOLLOWING: NEC110.3 |
| | LED DRIVER. |
| | LED LIGHTING |
| | TRANSFORMER |
| | TIMER |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT |
| | /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| | ITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |