Plan Review Details - Permit 14080148
Plan Review Stops For Permit 14080148
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-09-03 Cont ID  
Sent By jwitmer Date 2014-09-03 Time 09:06 Rev Time 0.00
Received By jwitmer Date 2014-08-30 Time 07:47 Sent To  
Notes
2014-09-03 08:55:50BUILDING PLAN REVIEW
 PERMIT: 14080148 FOUNDATION
 ADD: 1950 GOLDEN LAKES BLVD.
 CONT: ANTIOCH CONTRACTING
 TEL: (813)220-0281
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: WED. SEPT. 03/ 2014
 ACTION: BUILDING PROVISO:
  
 2010 CHAPTER 1 ADMINISTRATIVE CODE 105.13.
 SPECIAL PHASED PERMIT APPROVAL
  
 AFTER SUBMITTAL OF THE APPROPRIATE CONSTRUCTION
 DOCUMENTS, THE BUILDING OFFICIAL IS AUTHORIZED TO ISSUE
 A PERMIT FOR THE CONSTRUCTION OF FOUNDATIONS OR ANY
 OTHER PART OF A BUILDING OR STRUCTURE BEFORE THE
 CONSTRUCTION DOCUMENTS FOR THE WHOLE BUILDING OR
 STRUCTURE HAVE BEEN SUBMITTED. THE HOLDER OF SUCH
 PERMIT FOR THE FOUNDATION OR OTHER PARTS OF A BUILDING
 OR STRUCTURE SHALL PROCEED AT THE HOLDER'S OWN RISK
 WITH THE BUILDING OPERATION AND WITHOUT ASSURANCE THAT
 A
 PERMIT FOR THE ENTIRE STRUCTURE WILL BE GRANTED.
 CORRECTIONS MAY BE REQUIRED TO MEET THE REQUIREMENTS OF
 THE TECHNICAL CODES. THIS PROVISION IS ONLY FOR THE
 FLORIDA BUILDING CODE, ALL OTHER AGENCY APPROVALS
 NECESSARY FOR CONSTRUCTION MUST BE SECURED PRIOR TO
 THIS PROVISION BEING APPLIED.
  
 I SPOKE WITH THE CONTRACTOR FRI. AUG 29/14 WILL NEED
 CALCULATIONS & PRODUCT DATA SHEETS FOR THE OIL
 SEPARATOR. WILL NEED TO INSTALL OIL SEPARAQTOR BEFORE
 THE START OF FOUNDATIONS IN THIS AREA.COMPLY WITH: 2010
 FBC-B 1804.1 EXCAVATION NEAR FOUNDATIONS.
 EXCAVATION FOR ANY PURPOSE SHALL NOT REMOVE LATERAL
 SUPPORT FROM ANY FOUNDATION WITHOUT FIRST UNDERPINNING
 OR PROTECTING THE FOUNDATION AGAINST SETTLEMENT OR
 LATERAL TRANSLATION.
  
 1804.2 PLACEMENT OF BACKFILL.
 THE EXCAVATION OUTSIDE THE FOUNDATION SHALL BE
 BACKFILLED WITH SOIL THAT IS FREE OF ORGANIC MATERIAL,
 CONSTRUCTION DEBRIS, COBBLES AND BOULDERS OR WITH A
 CONTROLLED LOW-STRENGTH MATERIAL (CLSM). THE BACKFILL
 SHALL BE PLACED IN LIFTS AND COMPACTED IN A MANNER THAT
 DOES NOT DAMAGE THE FOUNDATION OR THE WATERPROOFING OR
 DAMPPROOFING MATERIAL.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-09-09 Cont ID  
Sent By dhayes Date 2014-09-09 Time 16:44 Rev Time 0.00
Received By dhayes Date 2014-09-09 Time 16:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-09-08 Cont ID  
Sent By dhayes Date 2014-09-08 Time 15:46 Rev Time 0.00
Received By dhayes Date 2014-09-08 Time 15:46 Sent To  
Notes
2014-09-08 16:05:48DATE: 9/8/2014
 PROJECT: LUX AUTO SPA
 PERMIT#: 14080148
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW FOR FOUNDATION PERMIT ONLY
 ACTION: DENIED
  
 1) PG. E-3. THERE ARE A COUPLE OF SYMBOLS AND A NOTE
 THAT REFFERENCE GOUNDING BUT NO DETAILS THAT REFFERENCE
 THE FOUNDATION STEEL REQUIRED BY NEC 250.52(3)
 CONCRETE-ENCASED ELECTRODE.
 PROVIDE A COMPLETE GROUNDING ELECTRODE SYSTEM PER NEC
 250 PART III. GROUNDING ELECTRODE SYSTEM INCLUDING THE
 CONCRETE ENCASED ELECTRODE PER NEC 250.52.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2014-08-13 Cont ID  
Sent By Mgonzale Date 2014-08-13 Time   Rev Time 1.00
Received By mgonzale Date 2014-08-13 Time   Sent To Z
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-08-06 Cont ID  
Sent By pleduc Date 2014-08-06 Time   Rev Time 0.00
Received By pleduc Date 2014-08-06 Time 11:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-09 Cont ID  
Sent By dhayes Date 2014-09-09 Time 16:44 Rev Time 0.00
Received By dhayes Date 2014-09-09 Time 16:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-05 Cont ID  
Sent By tklarge Date 2014-09-05 Time 12:59 Rev Time 0.00
Received By tklarge Date 2014-09-05 Time 12:59 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2014-09-09 Cont ID  
Sent By shill Date 2014-09-09 Time 13:53 Rev Time 0.00
Received By shill Date 2014-09-09 Time 13:53 Sent To  
Notes
2014-09-09 13:54:09EXISTING USE CREDIT, NO FEE
 MU 2014-19961
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-08-30 Cont ID  
Sent By jwitmer Date 2014-08-30 Time 07:46 Rev Time 0.00
Received By jwitmer Date 2014-08-30 Time 07:46 Sent To  
Notes
2014-08-30 07:47:10BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-09-05 Cont ID  
Sent By tklarge Date 2014-09-05 Time 12:54 Rev Time 0.00
Received By tklarge Date 2014-09-05 Time 12:54 Sent To  
Notes
2014-09-05 12:58:22*****PROVISO*****
 A REVISED WATER AND SANITARY RISER SHALL BE SUBMITTED
 FOR REVIEW AND APPROVAL PRIOR TO THE FIRST ROUGH
 PLUMBING INSPECTION. TWO COPIES SIGNED AND SEALED BY
 THE DESIGN PROFESSIONAL OF RECORD ARE REQUIRED.
 SEE PLUMBING PLAN REVIEW COMMENTS FOR APPLICATION #
 14050151 REGARDING THE UNDERGROUND PIPING.

Review Stop Z ZONING
Rev No 1 Status P Date 2014-08-14 Cont ID  
Sent By dkittred Date 2014-08-14 Time 14:16 Rev Time 0.00
Received By dkittred Date 2014-08-14 Time 09:29 Sent To  
Notes
***NONE***