| 2014-09-03 08:55:50 | BUILDING PLAN REVIEW |
| | PERMIT: 14080148 FOUNDATION |
| | ADD: 1950 GOLDEN LAKES BLVD. |
| | CONT: ANTIOCH CONTRACTING |
| | TEL: (813)220-0281 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: WED. SEPT. 03/ 2014 |
| | ACTION: BUILDING PROVISO: |
| | |
| | 2010 CHAPTER 1 ADMINISTRATIVE CODE 105.13. |
| | SPECIAL PHASED PERMIT APPROVAL |
| | |
| | AFTER SUBMITTAL OF THE APPROPRIATE CONSTRUCTION |
| | DOCUMENTS, THE BUILDING OFFICIAL IS AUTHORIZED TO ISSUE |
| | A PERMIT FOR THE CONSTRUCTION OF FOUNDATIONS OR ANY |
| | OTHER PART OF A BUILDING OR STRUCTURE BEFORE THE |
| | CONSTRUCTION DOCUMENTS FOR THE WHOLE BUILDING OR |
| | STRUCTURE HAVE BEEN SUBMITTED. THE HOLDER OF SUCH |
| | PERMIT FOR THE FOUNDATION OR OTHER PARTS OF A BUILDING |
| | OR STRUCTURE SHALL PROCEED AT THE HOLDER'S OWN RISK |
| | WITH THE BUILDING OPERATION AND WITHOUT ASSURANCE THAT |
| | A |
| | PERMIT FOR THE ENTIRE STRUCTURE WILL BE GRANTED. |
| | CORRECTIONS MAY BE REQUIRED TO MEET THE REQUIREMENTS OF |
| | THE TECHNICAL CODES. THIS PROVISION IS ONLY FOR THE |
| | FLORIDA BUILDING CODE, ALL OTHER AGENCY APPROVALS |
| | NECESSARY FOR CONSTRUCTION MUST BE SECURED PRIOR TO |
| | THIS PROVISION BEING APPLIED. |
| | |
| | I SPOKE WITH THE CONTRACTOR FRI. AUG 29/14 WILL NEED |
| | CALCULATIONS & PRODUCT DATA SHEETS FOR THE OIL |
| | SEPARATOR. WILL NEED TO INSTALL OIL SEPARAQTOR BEFORE |
| | THE START OF FOUNDATIONS IN THIS AREA.COMPLY WITH: 2010 |
| | FBC-B 1804.1 EXCAVATION NEAR FOUNDATIONS. |
| | EXCAVATION FOR ANY PURPOSE SHALL NOT REMOVE LATERAL |
| | SUPPORT FROM ANY FOUNDATION WITHOUT FIRST UNDERPINNING |
| | OR PROTECTING THE FOUNDATION AGAINST SETTLEMENT OR |
| | LATERAL TRANSLATION. |
| | |
| | 1804.2 PLACEMENT OF BACKFILL. |
| | THE EXCAVATION OUTSIDE THE FOUNDATION SHALL BE |
| | BACKFILLED WITH SOIL THAT IS FREE OF ORGANIC MATERIAL, |
| | CONSTRUCTION DEBRIS, COBBLES AND BOULDERS OR WITH A |
| | CONTROLLED LOW-STRENGTH MATERIAL (CLSM). THE BACKFILL |
| | SHALL BE PLACED IN LIFTS AND COMPACTED IN A MANNER THAT |
| | DOES NOT DAMAGE THE FOUNDATION OR THE WATERPROOFING OR |
| | DAMPPROOFING MATERIAL. |
| | |