Plan Review Details - Permit 14080118
Plan Review Stops For Permit 14080118
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-10-02 Cont ID  
Sent By jwitmer Date 2014-10-02 Time 08:33 Rev Time 0.00
Received By jwitmer Date 2014-10-02 Time 07:34 Sent To  
Notes
2014-10-02 08:33:29BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) THE CONTRACTOR & DESIGN TEAM HAS ELECTED TO HAVE THE
 ROOFING CONTRACTOR TO SUBMIT THE ROOFING PRODUCT
 APPROVAL UNDER THE ROOFING PERMIT WITH SEPARATE REVIEW
 & ASSOCIATED FEES.
  
 2) NOTE SHEET D-1 NO WORK ON EXISTING EXTERIOR WALK-IN
 COOLERS AND FREEZERS. PRODUCT TESTING SUBMITTED NOT
 REVIEWED, NOT STAMPED. WILL REQUIRE A SEPARATE PERMIT
 FOR TRACKING PURPOSES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-08-26 Cont ID  
Sent By jwitmer Date 2014-08-26 Time 08:36 Rev Time 0.00
Received By jwitmer Date 2014-08-26 Time 07:28 Sent To  
Notes
2014-08-26 08:33:38BUILDING PLAN REVIEW
 PERMIT: 14080118
 ADD: 1531 BELVEDERE RD.
 CONT: CORPORATE PROPERTY SERVICES, INC
 TEL: (954) 426-5144
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. AUG.26/ 2014
 ACTION: DENIED
  
 1) THE SUBMITTED PRODUCT APPROVALS HAVE NOT BEEN
 REVIEWED BY THE DESIGNER OF RECORD. 2010 FBC 107.3.4.1
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED
 BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2) SUBMITTED NOA 12-0201.07 SMI-090 ALUMINUM WINDOW
 WALL SYSTEM MISSING THE NOA FOR THE NEW GLAZED DOOR ON
 THE DRIVE THRU ELEVATION. 2010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
 3) THE ROOFING APPROVAL FL 16039-R3 WAS SUBMITTED, NO
 SUB-SYSTEM NOR PRESSURES WERE IDENTIFIED. 2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY
 THE CODE, THE CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE,
 DESCRIBE AND DELINEATE THE TYPE OF ROOFING SYSTEM,
 MATERIALS, FASTENING REQUIREMENTS, FLASHING
 REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE
 REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR
 THE SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR
 ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH
 THE CONSTRUCTION DOCUMENTS
  
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-10-02 Cont ID  
Sent By rlecky Date 2014-10-02 Time 11:28 Rev Time 0.00
Received By rlecky Date 2014-10-02 Time 11:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-08-07 Cont ID  
Sent By rlecky Date 2014-08-07 Time 14:49 Rev Time 0.00
Received By rlecky Date 2014-08-07 Time 13:59 Sent To  
Notes
2014-08-07 14:50:01PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE ELECTRIC PLAN
 SHOWING COMPLIANCE WITH THE FLORIDA BUILDING ENERGY
 CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.5;
 505.5.3; T. 505.5.3
  
 PROVIDE OR CONFIRM THAT THE INTERIOR AND EXTERIOR
 LIGHTING CONTROLS PROVIDED FUNCTION IN ACCORDANCE WITH
 THE FLORIDA ENERGY CODE. EXTERIOR AUTOMATIC CONTROLS
 SHALL BE CAPABLE OF RETAINING PROGRAMMING AND THE TIME
 SETTING DURING LOSS OF POWER FOR A PERIOD OF AT LEAST
 10 HOURS. FBC ENERGY CONSERVATION 505.2
  
 PROVIDE LIGHTING CONTROLS ON THE SIGN CIRCUIT.
 AUTOMATIC CONTROLS SHALL BE CAPABLE OF RETAINING
 PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER
 FOR A PERIOD OF AT LEAST 10 HOURS. FBC ENERGY
 CONSERVATION 505.2
  
 ROBERT LECKY
 ELECTRICAL PLANS REVIEW
 561-805-6700
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-10-07 Cont ID  
Sent By pleduc Date 2014-10-07 Time   Rev Time 0.00
Received By pleduc Date 2014-10-06 Time 12:48 Sent To  
Notes
2014-10-07 10:07:31THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. NO EXIT DOOR SHALL BE LOCKED FROM THE EGRESS SIDE.
 ANY AND ALL LOCKING MECHANISMS SHALL BE COMPLAINT WITH
 CHAPTER 7 OF THE FLORIDA FIRE PREVENTION CODE AND
 PRE-APPROVED (PRIOR TO INSTALLATION) BY THE BUREAU OF
 FIRE PREVENTION. CLOSE COORDINATION WITH THE BUREAU OF
 FIRE PREVENTION IS STRONGLY ENCOURAGED TO AVOID
 MISUNDERSTANDINGS, MISINTERPRETATIONS AND DELAYS
 RELATED TO EGRESS REQUIREMENTS.
  
 2. NOTICE IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR
 ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR
 MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH AN APPROVED SYMBOL. THE APPROVED SYMBOL SHALL BE
 PLACED WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY
 DOOR.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-11-10 Cont ID  
Sent By jwitmer Date 2014-11-10 Time 07:49 Rev Time 0.00
Received By jwitmer Date 2014-10-29 Time 14:50 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-10-22 Cont ID  
Sent By tklarge Date 2014-10-22 Time 06:14 Rev Time 0.00
Received By tklarge Date 2014-10-22 Time 06:14 Sent To  
Notes
2014-09-29 16:46:14RE-SUBMITTAL SENT TO B8 SHELF FORT REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-12 Cont ID  
Sent By tklarge Date 2014-09-12 Time 11:34 Rev Time 0.00
Received By tklarge Date 2014-08-04 Time 09:23 Sent To  
Notes
2014-09-12 11:36:549/12/14- DENIED/E-MAILED CONTRACTOR/ PLACED IN DENIED
 LARGE "C". TKL.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-10-08 Cont ID  
Sent By rbergsma Date 2014-10-08 Time   Rev Time 0.50
Received By rbergsma Date   Time   Sent To  
Notes
2014-10-08 08:18:44NEW BEVERAGE REMOTE CONDENSERS ON NOA STANDS ONLY, SEE
 A1.3

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-08-16 Cont ID  
Sent By hmoser Date 2014-08-16 Time 09:17 Rev Time 0.00
Received By hmoser Date 2014-08-16 Time 09:02 Sent To  
Notes
2014-08-16 09:20:42PLAN DENIED
  
 NO MECHANICAL PLAN SUBMITTED EXCEPT FOR
 CONDENSER PIPE DETAIL ON PAGE A1.3
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-10-22 Cont ID  
Sent By tklarge Date 2014-10-22 Time 06:12 Rev Time 0.00
Received By tklarge Date 2014-10-22 Time 06:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-09-12 Cont ID  
Sent By tklarge Date 2014-09-12 Time 11:32 Rev Time 0.00
Received By tklarge Date 2014-09-12 Time 11:15 Sent To  
Notes
2014-09-12 11:30:351) SHOW THE CLEAR FLOOR SPACE FOR THE URINAL ON SHT.
 A7.2. COMPLY W/ FL. ACCESS. CODE.SEC.305.
 2) THE PLANS SHOW THE DOORS ON THE TOILET COMPARTMENTS
 SWINGING INTO THE COMPARTMENT. THE DOORS CANNOT SWING
 INTO THE COMPARTMENT PER THE FAC SEC.604.8.1.2. REVISE
 ALL SHEETS.
 3) SHT. A7.2-TYPICAL TOILET ROOM DIMENSIONS SHOWS GRAB
 BARS INSTALLED IN A VERTICAL POSITION.GRAB BARS SHALL
 BE INSTALLED HORIZONTALLY PER THE FAC SEC. 609.4.
 4) SHT. P1.1 - BEVERAGE DISPENSERS SHALL BE EQUIPPED W/
 BACKFLOW PREVENTERS PER THE 2010 FPC SEC.608.16.1.
 5)THE FLOOR PLAN SHOWS FIXTURES BEING REMOVED AND
 RELOCATED IN THE RESTROOMS; SUBMIT A WATER RISER AND
 SANITARY RISER FOR ALL THE CHANGES BEING MADE TO THE
 PLUMBING SYSTEM.
 60 SUBMIT A LEGEND FOR THE CIRCLED NUMBERS AT THE
 PLUMBING FIXTURES SHOWN IN THE RESTROOMS.WPB ADMIN.
 AMEND. TO 2010 FBC SEC. 107.2.1.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2014-11-10 Cont ID  
Sent By jwitmer Date 2014-11-10 Time 07:51 Rev Time 0.00
Received By jwitmer Date 2014-11-10 Time 07:51 Sent To  
Notes
2014-11-10 07:51:37ROOF REVIEW
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) THE CONTRACTOR & DESIGN TEAM HAS ELECTED TO HAVE THE
 ROOFING CONTRACTOR TO SUBMIT THE ROOFING PRODUCT
 APPROVAL UNDER THE ROOFING PERMIT WITH SEPARATE REVIEW
 & ASSOCIATED FEES.

Review Stop Z ZONING
Rev No 3 Status P Date 2014-11-07 Cont ID  
Sent By jwitmer Date 2014-11-10 Time 07:50 Rev Time 0.00
Received By jroach Date 2014-11-07 Time 13:41 Sent To  
Notes
2014-11-07 13:44:18ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 11.07.2014
 PERMIT NO.: 14080118
 ADDRESS: 1531 BELVEDERE ROAD
 CONTRACTOR/CONTACT: BRANDI
 TELEPHONE NO.: 954.426.5144
 SCOPE OF REVIEW: RENOVATIONS TO EXISTING DRIVE-THRU
 RESTAURANT.
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. WHEEL STOPS SHALL BE INSTALLED AT 2 FEET FROM THE
 FACE OF THE CURB. WHEEL STOPS SHOWN ON THE PLAN AT THE
 ANGLED PARKING SPACES ARE TOO FAR FROM THE CURB LINE.
  
 2. PRIOR TO FINAL INSPECTION, AN APPLICATION SHALL BE
 SUBMITTED FOR A LANDSCAPE PERMIT. SUCH PERMIT SHALL BE
 APPROVED AND ALL LANDSCAPING SHALL BE INSTALLED IN
 ACCORDANCE WITH THE APPROVED PERMIT PRIOR TO THE
 ISSUANCE OF A CERTIFICATE OF OCCUPANCY.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1448
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.WPB.ORG
  

Review Stop Z ZONING
Rev No 2 Status F Date 2014-10-16 Cont ID  
Sent By jroach Date 2014-10-16 Time 16:02 Rev Time 0.00
Received By jroach Date 2014-10-16 Time 15:26 Sent To  
Notes
2014-10-16 16:02:19ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 10.16.2014
 PERMIT NO.: 14080118
 ADDRESS: 1531 BELVEDERE ROAD
 CONTRACTOR/CONTACT: BRANDI
 TELEPHONE NO.: 954.426.5144
 SCOPE OF REVIEW: RENOVATIONS TO EXISTING DRIVE-THRU
 RESTAURANT.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. (REPEAT COMMENT) PURSUANT TO SECTION 94-441 OF THE
 CITY'S ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDRS),
 BECAUSE THE PROPOSED SCOPE OF WORK EXCEEDS 50 PERCENT
 OF THE VALUE OF THE EXISTING STRUCTURE, THE SITE SHALL
 BE BROUGHT INTO COMPLIANCE WITH ARTICLE XIV
 (LANDSCAPING) OF THE ZLDRS. PLANS SHALL BE SUBMITTED
 INDICATING SUCH. IF EXISTING MATERIAL IS SHOWN ON THE
 PLANS AND ALL PROVISIONS OF ARTICLE XIV HAVE BEEN MET,
 THEN NO ADDITIONAL PERMIT/INSTALLATION IS REQUIRED. IF
 THE EXISTING MATERIAL ON SITE DOES NOT CONFORM TO ALL
 OF THE REQUIREMENTS OF ARTICLE XIV, THEN ADDITIONAL
 MATERIAL WILL NEED TO BE SHOWN ON THE PLANS AND
 PERMITTED UNDER A LANDSCAPE PERMIT. PLEASE NOTE THAT
 PLANS SHOULD INCLUDE, BUT NOT BE LIMITED TO, THE
 FOLLOWING:
  
  A. THE LOCATION OF ALL EXISTING AND PROPOSED
 STRUCTURES, IMPROVEMENTS, ETC.
  
  B. THE LOCATION OF ALL EXISTING AND PROPOSED TREES,
 SHRUBS, GROUND COVERS, ETC.
  
  C. THE LOCATION OF UTILITY AND DRAINAGE EASEMENTS,
 OVERHEAD LINES, WATER METERS, TRANSFORMERS, CHECK
 VALVES, CLEAN OUTS, FIRE HYDRANTS, LIGHT POLES, ETC.
 THAT MAY IMPACT LANDSCAPING.
  
  D. TABULATION TABLE INDICATING HOW THE EXISTING AND
 PROPOSED PLANT MATERIAL COMPLIES WITH ARTICLE XIV.
  
  E. SPECIES, QUANTITY, HEIGHT, SPREAD, SPACING, AND
 LOCATION OF THE EXISTING AND PROPOSED PLANT MATERIAL.
  
  F. STATEMENT THAT ALL LANDSCAPE AREAS WILL BE PROVIDED
 WITH A PERMANENT AUTOMATIC IRRIGATION SYSTEM, INCLUDING
 THE ADJACENT RIGHT-OF-WAY (PLEASE NOTE THAT ANY NEW
 IRRIGATION SHALL BE DONE UNDER A SEPARATE PERMIT).
  
 2. (REPEAT COMMENT) A SEPARATE PERMIT APPLICATION WILL
 NEED TO BE SUBMITTED FOR THE PROPOSED LANDSCAPE WORK.
 SUCH APPLICATION SHALL INCLUDED 2 SETS OF SIGNED /
 SEALED PLANS, ALONG WITH A CERTIFIED COST ESTIMATE
 (LABOR AND MATERIALS).
  
 3. THE LENGTH OF THE ANGELED PARKING SPACES AT THE
 NORTH END OF THE PARKING LOT ARE TOO SHORT. PLEASE
 REFER TO SECTION 94-485 (FIGURE XV-2) FOR THE MINIMUM
 PARKING STALL DIMENSIONS.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1448
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.WPB.ORG
  
 8/14/14
2014-10-15 13:15:4310/15/14

Review Stop Z ZONING
Rev No 1 Status F Date 2014-09-09 Cont ID  
Sent By jroach Date 2014-09-09 Time 08:07 Rev Time 0.00
Received By jroach Date 2014-08-26 Time 15:21 Sent To  
Notes
2014-09-09 08:08:10ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 09.08.2014
 PERMIT NO.: 14080118
 ADDRESS: 1531 BELVEDERE ROAD
 CONTRACTOR/CONTACT: BRANDI
 TELEPHONE NO.: 954.426.5144
 SCOPE OF REVIEW: RENOVATIONS TO EXISTING DRIVE-THRU
 RESTAURANT.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PURSUANT TO SECTION 94-441 OF THE CITY'S ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS), BECAUSE THE
 PROPOSED SCOPE OF WORK EXCEEDS 50 PERCENT OF THE VALUE
 OF THE EXISTING STRUCTURE, THE SITE SHALL BE BROUGHT
 INTO COMPLIANCE WITH ARTICLE XIV (LANDSCAPING) OF THE
 ZLDRS. PLANS SHALL BE SUBMITTED INDICATING SUCH. IF
 EXISTING MATERIAL IS SHOWN ON THE PLANS AND ALL
 PROVISIONS OF ARTICLE XIV HAVE BEEN MET, THEN NO
 ADDITIONAL PERMIT/INSTALLATION IS REQUIRED. IF THE
 EXISTING MATERIAL ON SITE DOES NOT CONFORM TO ALL OF
 THE REQUIREMENTS OF ARTICLE XIV, THEN ADDITIONAL
 MATERIAL WILL NEED TO BE SHOWN ON THE PLANS AND
 PERMITTED UNDER A LANDSCAPE PERMIT. PLEASE NOTE THAT
 PLANS SHOULD INCLUDE, BUT NOT BE LIMITED TO, THE
 FOLLOWING:
  
  A. THE LOCATION OF ALL EXISTING AND PROPOSED
 STRUCTURES, IMPROVEMENTS, ETC.
  
  B. THE LOCATION OF ALL EXISTING AND PROPOSED TREES,
 SHRUBS, GROUND COVERS, ETC.
  
  C. THE LOCATION OF UTILITY AND DRAINAGE EASEMENTS,
 OVERHEAD LINES, WATER METERS, TRANSFORMERS, CHECK
 VALVES, CLEAN OUTS, FIRE HYDRANTS, LIGHT POLES, ETC.
 THAT MAY IMPACT LANDSCAPING.
  
  D. TABULATION TABLE INDICATING HOW THE EXISTING AND
 PROPOSED PLANT MATERIAL COMPLIES WITH ARTICLE XIV.
  
  E. SPECIES, QUANTITY, HEIGHT, SPREAD, SPACING, AND
 LOCATION OF THE EXISTING AND PROPOSED PLANT MATERIAL.
  
  F. STATEMENT THAT ALL LANDSCAPE AREAS WILL BE PROVIDED
 WITH A PERMANENT AUTOMATIC IRRIGATION SYSTEM, INCLUDING
 THE ADJACENT RIGHT-OF-WAY (PLEASE NOTE THAT ANY NEW
 IRRIGATION SHALL BE DONE UNDER A SEPARATE PERMIT).
  
 2. A SEPARATE PERMIT APPLICATION WILL NEED TO BE
 SUBMITTED FOR THE PROPOSED LANDSCAPE WORK. SUCH
 APPLICATION SHALL INCLUDED 2 SETS OF SIGNED / SEALED
 PLANS, ALONG WITH A CERTIFIED COST ESTIMATE (LABOR AND
 MATERIALS).
  
 3. THE PARKING CALCULATIONS SHOWN ON SHEETS C0.1 AND
 C2.0 SHOULD BE 1 SPACE PER 3 SEATS, NOT 1 SPACE PER 40
 SQUARE FEET. PLEASE ENSURE THAT THE NEW OUTDOOR SEATING
 IS REFLECTED IN THIS CALCULATION.
  
 4. SHEET EQ1.1 SHOWS THE NUMBER OF SEATS AS 83, WHILE
 SHEET EQ1.2 SHOWS 82. PLEASE ENSURE THAT ALL PLANS ARE
 CONSISTENT.
  
 5. ON SHEET C0.1, THE TABLE SHOWS 45 PARKING SPACES ARE
 PROVIDED, BUT INDICATES THAT THERE ARE 2 HANDICAP
 SPACES AND 46 REGULAR SPACES; THIS TOTALS TO 48.
  
 6. IS THE EXISTING PARKING LOT BEING RESTRIPED? IT IS
 UNCLEAR IF SEALCOATING AND/OR RESTRIPING OF THE
 REMAINDER OF THE LOT ARE INCLUDED IN THE SCOPE OF WORK.
 PLEASE CLARIFY.
  
 7. PLEASE PROVIDE THE ANGLE OF THE SPACES ALONG THE
 NORTH PROPERTY LINE. ADDITIONALLY, DIMENSION ALL
 PARKING ROWS, DRIVE AISLES, ETC.
  
 8. PLEASE CLARIFY THE BOLD LINE AT THE HEAD OF THE
 PARKING STALLS EAST OF THE BUILDING. STRIPING IS ONLY
 NEEDED BETWEEN THE SPACES AND WHEEL STOPS SHOULD BE
 PROVIDED AT THE HEADS OF THE PARKING STALLS IN
 ACCORDANCE WITH THE PARKING DETAIL.
  
 9. THE PARKING DETAIL SHOWN ON SHEET C4.0 SHOWS THE
 HANDICAP ACCESS AISLE AS 8 FEET IN WIDTH, WHILE ALL
 OTHER DRAWINGS INDICATE 5 FEET; ONLY 5 FEET IS
 REQUIRED. ADDITIONALLY, WHEEL STOPS NEED TO BE PROVIDED
 AND THE BOLLARDS / SIGNS SHOULD NOT BE LOCATED IN THE
 VEHICLE OVERHANG.
  
 10. THE ELEVATIONS ARE LABELED INCORRECTLY (FRONT,
 REAR, ETC.).
  
 11. PLEASE NOTE THAT SIGNAGE SHALL BE SUBMITTED UNDER A
 SEPARATE PERMIT APPLICATION AND WILL BE REVIEWED FOR
 COMPLIANCE AT THAT TIME.
  
 12. SHEET C2.0 DOES NOT SHOW THE PROPOSED CANOPY OVER
 THE DRIVE-THRU WINDOWS. PLEASE INDICATE SUCH AND
 PROVIDE DIMENSIONS ACCORDINGLY.
  
 13. PLEASE PROVIDE DETAILS / INFORMATION INDICATING
 THAT THE NEW MECHANICAL EQUIPMENT PROPOSED TO BE
 INSTALLED ON THE ROOF WILL NOT BE VISIBLE. HOW HIGH IS
 THE PARAPET ABOVE THE HEIGHT OF THE ROOF DECK? HOT TALL
 IS THE MECHANICAL EQUIPMENT? A CROSS-SECTION MAY NEED
 TO BE PROVIDED.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1448
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.WPB.ORG
  
2014-08-14 17:07:218/14/14


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved