| 2014-08-08 16:16:25 | BUILDING PLAN REVIEW |
| | PERMIT: 14080109 |
| | ADD: 1045 CHARLOTTE |
| | CONT: THE CARPENTER'S SON |
| | TEL: ()452-2191 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRIDAY AUG. 08/2014 |
| | ACTION: DENIED |
| | |
| | 1) THE SUBMITTED PLAN IS A STATE APPROVED PLANS FOR A |
| | RESIDENTIAL STORAGE SHED (BUILDING CATEGORY I) , 180 |
| | VALT / EXP. D, PLEASE REVIEW ISSUES AT HAND: |
| | 1A) THE OCCUPANCY CLASSIFICATION IS BEING CHANGED TO A |
| | BUSINESS OCCUPANCY, A GUARD SHACK, THE BUILDING |
| | CATEGORY II HAS CHANGED, THIS WILL INCREASE THE |
| | REQUIRED PRESSURES. |
| | 1B) WITH THE OCCUPANCY CHANGE REQUIRING THE BUILDING TO |
| | BE A BUILDING CATEGORY LL THIS MAY AFFECT THE ANCHORING |
| | OF THE STRUCTURE, THE ANCHORING ENGINEERING WILL ALSO |
| | NEED TO BE REVIEWED. |
| | 1C) PLEASE NOTE ALSO THE REQUIREMENT FOR COMPONENTS AND |
| | CLADDING WINDOWS AND DOORS WILL NEED TO HAVE EITHER |
| | LARGE MISSILE IMPACT GLAZING OR STORM SHUTTERS. 2010 |
| | FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| | COMPONENTS & CLADDING.FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| | PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | 1D) THE STATE PLANS SHEET 1 NOTE # 11 INDICATE FOR A |
| | RESIDENTIAL USE A ACCESORY SRUCTURE THE DOOR MAY BE 72 |
| | INCHES, NOTE # 12 FOR COMMERCIAL USE THE DOOR MUST BE |
| | 6'-8" TALL. FBC-B 1008.1.1. |
| | 1E) THE STATE APPROVED PLANS DO INDICATE THAT THE NOTE |
| | # 4 THE GUTTER SYSTEM IS A SITE INSTALLED SYSTEM AND |
| | THE CONTRACTOR WILL NEED TO SUBMIT THE GUTTER AND DOWN |
| | SPOUT TO BE INSTALLED. 2010 FBC-B 1503.7 PROTECTION |
| | AGAINST DECAY AND TERMITES. |
| | CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT |
| | LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL, |
| | WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR |
| | SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON |
| | ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM) |
| | HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON |
| | A ROOF ABOVE ANOTHER ROOF. |
| | |
| | 2) IT WOULD APPEAR THE MANUFACTURER OF THE BUILDING |
| | SHOULD MAKE A REVISION TO THE STATE APPROVED PLANS FOR |
| | THE BUSINESS USE OCCUPANCY, THEN THE STATE APPROVED |
| | PLANS WOULD ADDRESS THE COMMENTS 1A-1D. |
| | 1E) GUTTERS WILL STILL BE A SITE INSTALLED BY THE |
| | CONTRACTOR. |
| | |
| | 3) PLEASE IDENTIFY WHICH TYPE OF BUILDING TO BE |
| | INSTALLED, GABLE END, HIP OR SHED TYPE ROOF. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |