Plan Review Details - Permit 14080085
Plan Review Stops For Permit 14080085
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-10-03 Cont ID  
Sent By jgomez Date 2014-10-03 Time 13:57 Rev Time 0.00
Received By jgomez Date 2014-10-03 Time 13:57 Sent To  
Notes
2014-10-03 13:58:55BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- GARAGE IS CONVERTED TO BEDROOM (SEE BEDROOM
 DEFINITION IN CHAPTER 2 OF 2010 FBC-ENERGY
 CONSERVATION). SHOW COMPLIANCE WITH THE EGRESS
 REQUIREMENTS OF SEC. R310.
  
 2- PROVIDE EGRESS WINDOW PRODUCT APPROVAL (2 COPIES).
 DCA RULE 9N-3. COORDINATE WITH ITEM #1 ABOVE.
  
 3- NEW INSULATION NOTE ON SHEET A-1: PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS SHOWING HOW PROVIDING R-7.8
 INSULATION ON INSIDE OF EXISTING CMU EXTERIOR WALLS.
 SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-10-02 Cont ID  
Sent By JGOMEZ Date 2014-10-02 Time 14:46 Rev Time 0.00
Received By jgomez Date 2014-10-02 Time 14:46 Sent To  
Notes
2014-10-02 15:04:56RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW
 CHECKLIST:
 CODE: 2010 FBC.
  
 1- GARAGE IS CONVERTED TO BEDROOM (SEE BEDROOM
 DEFINITION IN CHAPTER 2 OF 2010 FBC-ENERGY
 CONSERVATION). PLANS NEED TO PROVIDE SPECIFICATIONS
 SHOWING COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC.
 R310 OF 2010 FBC-RESIDENTIAL.
 REPEAT COMMENT. NEED MEANS OF EGRESS. SEE THE
 DEFINITION OF BEDROOM IN THE 2010 FBC-ENERGY
 CONSERVATION. A ROOM WITH A CLOSET IS CONSIDERED A
 BEDROOM. NO HAVING A DOOR DOESN'T EXEMPT IT FROM BEING
 A BEDROOM. (NOTE: AN STUDIO OR A LOFT DON'T HAVE DOORS
 EITHER). REVISE PLANS AS REQUIRED.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR THE NEW EGRESS WINDOW.
  
 3- NEW INSULATION NOTE ON SHEET A-1: PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS SHOWING HOW PROVIDING R-7.8
 INSULATION ON INSIDE OF EXISTING CMU EXTERIOR WALLS AS
 REQUIRED BY SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-09-11 Cont ID  
Sent By jgomez Date 2014-09-11 Time 14:13 Rev Time 0.00
Received By jgomez Date 2014-09-11 Time 14:07 Sent To  
Notes
2014-09-11 14:16:41RESIDENTIAL (R3) GARAGE CONVERSION AND GENERAL
 ALTERATIONS, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- THE PLANS SUBMITTED ARE FOR THE CONVERSION OF GARAGE
 TO LIVING AREA. BRING PLANS TO PALM BEACH COUNTY (2300
 N. JOG RD.) TO VERIFY IF IMPACT FEES ARE DUE. BRING
 BACK COUNTY STAMPED PLANS AND COPY OF PAID RECEIPT IF
 FEES ARE DUE. REQUIRED BY THE COUNTY IMPACT FEE
 ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 101.4.3 OF 2010 FBC-ENERGY CONSERVATION.
  
 3- ARCHITECT TO COORDINATE INFORMATION IN PLANS WITH
 THE ENERGY CALCULATION. PROVIDE INFORAMTION AS REQUIRED
 BY SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 3- GARAGE IS CONVERTED TO BEDROOM (SEE BEDROOM
 DEFINITION IN CHAPTER 2 OF 2010 FBC-ENERGY
 CONSERVATION). PLANS NEED TO PROVIDE SPECIFICATIONS
 SHOWING COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC.
 R310 OF 2010 FBC-RESIDENTIAL.
  
 4- PER CONVERSATION WITH FRIEDERIKE MITTNER FROM
 HISTORIC PRESERVATION, THE GARAGE CONVERSION WAS
 APPROVED WITH THE CONDITION THAT THE EXISTING GARAGE
 DOOR IS GOING TO STAY. ARCHITECT TO REVISE PLANS
 SHOWING FRAMING DETAILS AND LEAVING THE GARAGE DOOR.
 AND, REVISE EXTERIOR ELEVATION SHOWING THE GARAGE DOOR.
 SEC. 107.2.1.3 CITY AMENDMENTS TO FBC.
  
 5- ARCHITECT TO REVISE EXTERIOR FRAME WALL SECTION
 DETAIL:
 A) NEED TO SPECIFY 7/8" MIN. STUCCO THICKNESS AS
 REQUIRED BY TABLE R702.1(1) OF 2010 FBC-RESIDENTIAL.
  
 B) NEED TO SPECIFY TWO LAYERS OF AN APPROVED
 WATER-RESISTANT BARRIER AS REQUIRED BY SEC. R703.6.3 OF
 2010 FBC-RESIDENTIAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2014-10-03 Cont ID  
Sent By skennedy Date 2014-10-03 Time 11:10 Rev Time 0.00
Received By skennedy Date 2014-10-03 Time 11:10 Sent To  
Notes
2014-10-03 11:11:07THERE IS A SEPARATE ELECTRICAL APPLICATION 14090076,
 WHICH IS NOT A SUB-PERMIT TYPE. THE ELECTRICAL REVIEW
 SHOULD BE DONE ON THAT NUMBER AND THAT ELECTRICAL
 PERMIT NUMBER STAMPED ON THE PLAN.
2014-10-02 16:41:05NEW DRAWINGS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2014-09-03 Cont ID  
Sent By skennedy Date 2014-09-03 Time 15:25 Rev Time 0.00
Received By skennedy Date 2014-09-03 Time 15:25 Sent To  
Notes
2014-09-03 16:04:40THERE IS A SEPARATE ELECTRICAL APPLICATION 14090076,
 WHICH IS NOT A SUB-PERMIT TYPE. THE ELECTRICAL REVIEW
 SHOULD BE DONE ON THAT NUMBER AND THAT ELECTRICAL
 PERMIT NUMBER STAMPED ON THE PLAN.

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2014-10-03 Cont ID  
Sent By fmittner Date 2014-10-03 Time 11:18 Rev Time 0.00
Received By fmittner Date 2014-10-03 Time 11:18 Sent To  
Notes
2014-10-02 16:41:28NEW DRAWINGS SUBMITTED. JG.

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2014-09-02 Cont ID  
Sent By fmittner Date 2014-09-02 Time 15:17 Rev Time 0.00
Received By fmittner Date 2014-09-02 Time 15:17 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2014-08-19 Cont ID  
Sent By fmittner Date 2014-08-19 Time 15:42 Rev Time 0.00
Received By fmittner Date 2014-08-19 Time 15:42 Sent To  
Notes
2014-08-19 15:44:25PROPERTY IN HISTORIC DISTRICT. BLANK WALL NOT PERMITTED
 ON WEST ELEVATION. SCOPE OF WORK IS GREATER THAN
 DESCRIBED. INCLUDES EXTERIOR WORK....ENCLOSING OF
 GARAGE. QUESTIONS CONTACT FRIEDERIKE MITTNER, CITY
 HISTORIC PRESERVATION PLANNER AT 822-1457.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-10-03 Cont ID  
Sent By jgomez Date 2014-10-03 Time 13:48 Rev Time 0.00
Received By jgomez Date 2014-10-03 Time 13:46 Sent To  
Notes
2014-10-03 13:48:5110/3/14 MET WITH MR. DAN. HE SAID OK TO ISSUE PERMIT
 WITH PROVISO. HE WILL ASK THE ARCHITECT TO REVISE PLANS
 AND WILL PROVIDE PROPER REVISED DRAWINGS AND PRODUCT
 APPROVALS. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-10-03 Cont ID  
Sent By tklarge Date 2014-10-03 Time 11:56 Rev Time 0.00
Received By tklarge Date 2014-09-25 Time 14:56 Sent To  
Notes
2014-09-26 15:04:30R12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-11 Cont ID  
Sent By jgomez Date 2014-09-11 Time 17:37 Rev Time 0.00
Received By jgomez Date 2014-08-04 Time 14:38 Sent To  
Notes
2014-08-04 14:38:48ROUTE TO R11

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2014-10-02 Cont ID  
Sent By JGOMEZ Date 2014-10-02 Time 16:08 Rev Time 0.00
Received By jgomez Date 2014-10-02 Time 16:08 Sent To  
Notes
2014-10-02 16:11:35NO FEES MU- 2014-20680 BY D.B.. SEE SHEET A-1 FOR
 COUNTY STAMPED PLAN. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-09-11 Cont ID  
Sent By jgomez Date 2014-09-11 Time 14:56 Rev Time 0.00
Received By jgomez Date 2014-09-11 Time 14:56 Sent To  
Notes
2014-09-11 14:58:401- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2014-10-03 Cont ID  
Sent By jgomez Date 2014-10-03 Time 14:32 Rev Time 0.00
Received By jgomez Date 2014-10-03 Time 14:32 Sent To  
Notes
2014-10-03 14:36:181-PROVIDE COMPLETE AND CORRECT INFORMATION (PLANS AND
 EQUIPMENT SIZING CALCULATIONS) UNDER A SEPARATE PERMIT.
 ***NOTE: A/C WORK VALUE IS NOT INCLUDED IN THE MAIN
 PERMIT APPLICATION. SEPARATE MECHANICAL PERMIT TO
 INCLUDE THE VALUE OF ALL A/C WORK.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2014-10-02 Cont ID  
Sent By J GOMEZ Date 2014-10-02 Time 18:18 Rev Time 0.00
Received By jgomez Date 2014-10-02 Time 18:18 Sent To  
Notes
2014-10-02 18:25:53RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- A/C PLAN SUBMITTED IN DRAWING M-1 DOESN'T MATCH
 ARCHITECTURAL PLAN. A/C PLAN SHOWS 14 X 8 PASS-THROUGH
 RETURN, WHILE ARCHITECTURAL PLAN ON SHEET A-1 SHOWS
 R.A.G. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 2- PERSON RESPONSIBLE FOR THE A/C DESIGN TO PROVIDE
 NAME AND SIGNATURE AS REQUIRED BY SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 ***NOTE: SEPARATE MECHANICAL PERMIT WILL BE REQUIRED
 AND VALUATION FOR THE MECHANICAL WORK IS NOT INCLUDED
 IN THE MASTER PERMIT APPLICATION
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2014-08-26 Time   Rev Time 1.00
Received By   Date   Time   Sent To  
Notes
2014-08-26 15:30:15PLEASE PROVIDE DUCT PLANS WITH SIZES OF DUCTWORK,
 GRILLS, TYPICAL CONDENSER AND AIR HANDLER DETAIL,
 ENERGY FOR NEWLY AIRCONDITIONED SPACE (STATE ENERGY
 FORMS). SHOW LOUVERED DOOR FOR LAUNDRY AND RETURN
 OPENING(S) FOR A/H, NOT THRU BED RM

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-10-03 Cont ID  
Sent By tklarge Date 2014-10-03 Time 11:51 Rev Time 0.00
Received By tklarge Date 2014-10-03 Time 11:51 Sent To  
Notes
2014-10-03 11:53:29****PROVISO****
 1) SHOWER TO BE A MIN. OF 900 SQ. INCHES AND MIN. 30
 INCHES INSIDE FINISHED DIMENSION L X W PER 2010 FBCR
 SEC. P2708.1.
 2) SANITARY RISER SHALL BE SUBMITTED FOR REVIEW &
 APPROVAL PRIOR TO FIRST PLBG. INSPECTION.
  
 PLUMBING PLAN REVIEW
 TIM LARGE-
 CHIEF PLUMBING INSPECTOR
 TEL:561-805-6692
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
2014-10-03 11:25:08SEE 14090773,
2014-10-02 16:42:27NEW DRAWINGS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-09-12 Cont ID  
Sent By tklarge Date 2014-09-06 Time 12:05 Rev Time 0.00
Received By tklarge Date 2014-09-06 Time 08:44 Sent To  
Notes
2014-09-06 08:49:22****PROVISO****
 1) SHOWER TO BE A MIN. OF 900 SQ. INCHES AND MIN. 30
 INCHES INSIDE FINISHED DIMENSION L X W PER 2010 FBCR
 SEC. P2708.1.
 2) SANITARY RISER SHALL BE SUBMITTED FOR REVIEW &
 APPROVAL PRIOR TO FIRST PLBG. INSPECTION.
  
 PLUMBING PLAN REVIEW
 TIM LARGE-
 CHIEF PLUMBING INSPECTOR
 TEL:561-805-6692
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2014-10-03 Cont ID  
Sent By fmittner Date 2014-10-03 Time 11:18 Rev Time 0.00
Received By fmittner Date 2014-10-03 Time 11:18 Sent To  
Notes
2014-10-02 16:41:50NEW DRAWINGS SUBMITTED. JG.

Review Stop Z ZONING
Rev No 2 Status P Date 2014-09-02 Cont ID  
Sent By fmittner Date 2014-09-02 Time 15:17 Rev Time 0.00
Received By fmittner Date 2014-09-02 Time 15:17 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2014-08-19 Cont ID  
Sent By fmittner Date 2014-08-19 Time 15:40 Rev Time 0.00
Received By fmittner Date 2014-08-19 Time 15:40 Sent To  
Notes
2014-08-19 15:42:36MUST DEMONSTRATE THAT THERE ARE THREE OFF STREET
 PARKING SPACES AVAILABLE.
2014-08-05 17:33:528/5/14


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved