Plan Review Details - Permit 14080077
Plan Review Stops For Permit 14080077
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-01-17 Cont ID  
Sent By tklarge Date 2015-01-17 Time 03:02 Rev Time 0.00
Received By tklarge Date 2015-01-17 Time 02:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-08-07 Cont ID  
Sent By jwitmer Date 2014-08-07 Time 13:36 Rev Time 0.00
Received By jwitmer Date 2014-08-07 Time 13:36 Sent To  
Notes
2014-08-07 13:49:55BUILDING PLAN REVIEW
 PERMIT: 14080077
 ADD: 104 CLEMATIS ST
 CONT: ATLANTIC GENERAL CONTRACTING
 TEL: (561)434-4171
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. AUGUST 07/2014
 ACTION: DENIED
  
 1) 1210.1 FLOORS AND WALL BASE FINISH MATERIALS.
 IN OTHER THAN DWELLING UNITS, TOILET, BATHING AND
 SHOWER ROOM FLOOR FINISH MATERIALS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE. THE INTERSECTIONS OF SUCH
 FLOORS WITH WALLS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT VERTICAL BASE THAT EXTENDS UPWARD ONTO THE
 WALLS AT LEAST 4 INCHES (102 MM).
  
 2) 1210.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF URINALS
 AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE, TO A HEIGHT OF 4 FEET (1219 MM)
 ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE
 THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-01-17 Cont ID  
Sent By dhayes Date 2015-01-17 Time 15:05 Rev Time 0.00
Received By dhayes Date 2015-01-17 Time 15:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-08-04 Cont ID  
Sent By dhayes Date 2014-08-04 Time 13:48 Rev Time 0.00
Received By dhayes Date 2014-08-04 Time 13:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-08-11 Cont ID  
Sent By scaldero Date 2014-08-11 Time 16:06 Rev Time 0.00
Received By scaldero Date 2014-08-11 Time 16:06 Sent To  
Notes
2014-08-11 16:06:54PERMIT # 14080077
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ADD AN EMERGENCY LIGHT WITH BATTERY BACK-UP IN THIS
 SPACE.
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-01-17 Cont ID  
Sent By dhayes Date 2015-01-17 Time 15:05 Rev Time 0.00
Received By dhayes Date 2015-01-15 Time   Sent To  
Notes
2015-01-16 10:58:18SENT TO T. K. LARGES' DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-08-15 Cont ID  
Sent By jdariton Date 2014-08-15 Time 13:06 Rev Time 0.00
Received By jdariton Date 2014-08-04 Time 13:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2014-08-15 Cont ID  
Sent By jdariton Date 2014-08-15 Time 13:01 Rev Time 0.00
Received By jdariton Date 2014-08-15 Time 13:04 Sent To  
Notes
2014-08-15 13:05:30NO MECHANICAL WORK SHOWN ON PLANS.

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-01-17 Cont ID  
Sent By tklarge Date 2015-01-17 Time 03:02 Rev Time 0.00
Received By tklarge Date 2015-01-17 Time 02:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-01-08 Cont ID  
Sent By tklarge Date 2015-01-08 Time 10:52 Rev Time 0.00
Received By tklarge Date 2015-01-08 Time 09:57 Sent To  
Notes
2015-01-08 10:51:501) SHOW THE REQUIRED KNEE AND TOE CLEARANCES UNDER THE
 LAVATORY. COMPLY WITH THE 2010 FBC, ACCESSIBILITY
 SECS.306 & 606.
 2) THE HEIGHT OF THE GRAB BARS SHALL BE MEASURED FROM
 THE FINISH FLOOR TO THE TOP OF THE GRIPPING SURFACE,
 NOT TO THE CENTERLINE OF THE GRAB BAR AS SHOWN. FL.
 ACCESSIBILITY CODE SEC. 609.4.
 3) SUBMIT A WATER RISER DIAGRAM FOR REVIEW PER THE WPB
 AMEND TO 2010 FBC SEC. 107.3.5.1.3.
 4) A CLEANOUT IS REQUIRED IN THE BASE OF THE WASTE
 STACK PER THE 2010 FPC SEC.708.3.4.
 5) INDICATE IF THE DOOR TO THE RESROOM IS EQUIPPED WITH
 A CLOSER AND LATCH. IF SO THEN A MIN. OF 12 INCHES OF
 CLEARANCE SHALL BE PROVIDED PARALLEL TO THE DOORWAY
 BEYOND THE LATCH SIDE PER THE FAC TABLE 404.2.4.1.SHOW
 THE DIMENSION ON THE PLAN.
 6) COMPLY WITH THE BUILDING PLAN REVIEW COMMENTS FOR
 THE WALLS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-08-07 Cont ID  
Sent By jwitmer Date 2014-08-07 Time 13:36 Rev Time 0.00
Received By jwitmer Date 2014-08-07 Time 13:35 Sent To  
Notes
2014-08-07 13:46:41PLUMBING PLAN REVIEW
 PERMIT: 14080077
 ADD: 104 CLEMATIS ST
 CONT: ATLANTIC GENERAL CONTRACTING
 TEL: (561)434-4171
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. AUGUST 07/2014
 ACTION: DENIED
  
 1) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.3 PLUMBING
 1. MINIMUM PLUMBING FACILITIES
 2. FIXTURE REQUIREMENTS
 3. WATER SUPPLY PIPING
 4. SANITARY DRAINAGE
 5. WATER HEATERS
 6. VENTS
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]