Plan Review Details - Permit 14080063
Plan Review Stops For Permit 14080063
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-08-07 Cont ID  
Sent By jwitmer Date 2014-08-07 Time 12:28 Rev Time 0.00
Received By jwitmer Date 2014-08-07 Time 12:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-10-31 Cont ID  
Sent By wjolin Date 2014-10-31 Time 12:00 Rev Time 0.00
Received By wjolin Date 2014-10-31 Time 11:38 Sent To  
Notes
2014-10-31 11:59:566701 NORTH JOG ROAD - MAINTENANCE BUILDING RACK STORAGE
 PERMIT #14080063
 MASTER #12030240
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 OPEN GUARDS SHALL PROHIBIT THE PASSAGE OF A 4-INCH
 DIAMETER SPHERE UP TO A HEIGHT OF 34-INCHES. THE
 TRIANGULAR OPENINGS FORMED BY THE RISER, TREAD AND
 BOTTOM ELEMENT OF THE GUARDRAIL SHALL PROHIBIT THE
 PASSAGE OF A 6-INCH DIAMETER SPHERE. GUARDS, AT LEAST
 42-INCHES TALL, SHALL BE PROVIDED AT THE OPEN SIDES OF
 MEANS OF EGRESS (STAIRS, MEZZANINE, ETC.) THAT EXCEED
 30-INCHES ABOVE THE FLOOR.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-08-13 Cont ID  
Sent By wjolin Date 2014-08-13 Time 10:21 Rev Time 0.00
Received By wjolin Date 2014-08-13 Time 09:06 Sent To  
Notes
2014-08-13 10:21:226701 NORTH JOG ROAD - MAINTENANCE BUILDING RACK STORAGE
 PERMIT #14080063
 MASTER #12030240
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 A DETAILED NARRATIVE/PLAN IS NEEDED INDICATING THE
 PROPOSED STORAGE HEIGHTS, COMMODITY CLASSIFICATIONS,
 STORAGE ARRANGEMENT (PALLETIZED, SOLID PILED, BIN BOX,
 SHELF), ENCAPSULATED/NON-ENCAPSULATED STORAGE,
 FLAMMABLE LIQUIDS, HAZARDOUS CHEMICALS, ETC.
  
 PROVIDE MEZZANINE DETAILS FOR STAIR, HANDRAILS, AND
 GUARDRAILS. CLEARLY INDICATE THE LOCATION OF ALL
 GUARDRAILS.
  
 A REVISED LIFE SAFETY PLAN IS NEEDED FOR THE MASTER
 PERMIT MAINTENANCE BUILDING (#12030240) TO ACCOMODATE
 FOR THE PROPOSED RACK STORAGE AND MEZZANINE. EXIT
 SIGNAGE, LIGHTING, FIRE EXTINGUISHER LOCATIONS, FIRE
 ALARM DEVICES, SPRINKLER TYPES AND LOCATIONS MAY ALL BE
 AFFECTED.
  
 THE SPRINKLER DESIGN (PERMIT #12030242) DOES NOT APPEAR
 TO BE IN ACCORDANCE WITH NFPA 13 FOR HIGH-PILED STORAGE
 (+12 FEET). ADDITIONALLY, NO SPRINKLER PROTECTION
 PROVIDED BELOW MEZZANINE STORAGE. IF SPRINKLER
 PROTECTION IS NEEDED BELOW THE MEZZANINE, THE STRUCTURE
 WILL NEED TO SUPPORT THE LOAD OF THE SPRINKLER PIPING
 PER NFPA 13 (5 X THE WEIGHT OF A WATER FILLED PIPE,
 PLUS 250 LBS).
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-10-31 Cont ID  
Sent By cpuell Date 2014-10-31 Time 13:29 Rev Time 0.00
Received By cpuell Date 2014-10-14 Time 09:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-08-13 Cont ID  
Sent By cpuell Date 2014-08-13 Time 14:02 Rev Time 0.00
Received By cpuell Date 2014-08-04 Time 16:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2014-10-31 Cont ID  
Sent By cpuell Date 2014-10-31 Time 15:03 Rev Time 0.00
Received By cpuell Date 2014-10-31 Time 15:03 Sent To  
Notes
***NONE***